background image

14

 WARNING:

Single Packaged Heat Pumps are 
shipped fully charged and ready for 
installation. When a system is installed 
according to these instructions, no 
refrigerant charging is required. 
If repairs make it necessary for 
evacuation and charging, it should 
only be done by qualifi ed,  trained 
personnel thoroughly familiar with this 
equipment. Some local codes require 
licensed installation/service personnel 
to service this type of equipment. 
Under no circumstances should the 
owner attempt to install and/or service 
this equipment. Failure to comply with 
this warning could result in property 
damage, personal injury, or death.

 CAUTION:

Use care when removing parts from 
this unit. Personal injury can result 
from sharp metal edges present 
in all equipment of sheet metal 
construction.

Routine Maintenance — 

Proper maintenance is 

important to achieve optimum performance from 

the heat pump. The ability to properly perform 
maintenance on this equipment requires certain 
mechanical skills and tools. If you do not possess 
these skills, contact your dealer for maintenance. 
Consult your local dealer about the availability of 
maintenance contracts. At a minimum, routine 
maintenance should include the following:

1.  Inspect and clean or replace air fi lters at 

the beginning of each heating and cooling 
season, or more frequently if required.

2.  Inspect the condensate drain and outdoor 

coil at the beginning of each cooling season. 
Remove any debris. Clean the outdoor coil 
and louvers as necessary using a mild 
detergent and water. Rinse thoroughly with 
water.

3.  Inspect the electrical connections for 

tightness at the beginning of each 
heating and cooling season. Service as 
necessary.

 CAUTION:

The unit should never be operated 
without a fi lter in the return air system. 
Replace disposable fi lters  with  the 
same type and size.

4.  The motors for the circulating air blower 

and the outdoor fan are pre-lubricated at 
the factory. No further oiling is required for 
the life of this product.

Table 1. Blower Curves

* Denotes factory set cooling and heat pump speed
** Denotes factory set electric heating speed

Model Number

External Static Pressure 

Drop - inches water column

Q4RD

0.1

0.2

0.3

0.4

0.5

0.6

060

Tap T1

1515

1450

1380

1350

1300

1250

Tap T2

1580

1520

1460

1400

1360

1300

Tap T3

1740

1690

1650

1600

1540

1500

Tap T4

1960

1910

1840

1820

1780

1740

Tap T5

2090

2050

2010

1975

1940

1900

Summary of Contents for Q4RD 060

Page 1: ...g appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national a...

Page 2: ...2...

Page 3: ...a the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat transfer section in...

Page 4: ...oned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand the outdoor fan off for approximately six minutes following a previous operation or...

Page 5: ...ecautionsintheliterature on tags and on labels provided with the unit and or approved field installed kits The type of hazard and severity are described on each label or tag Pressures Within The Syste...

Page 6: ...URN DUCT OPENING 23 5 1 25 Power Entry 1 75 Power Entry Capped 0 88 Control Wiring Entry 23 6 27 2 30 1 8 4 00 13 5 16 0 14 7 13 5 16 0 13 45 11 75 22 75 55 8 C SUPPLY RETURN 4 0 CONDENSING COIL 5 0 8...

Page 7: ...hat drains well See Figure 6 AIR DUCTS This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire Protection A...

Page 8: ...ion SMACNA application standard for duct liners Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC 25 50 or less Fiber duct work may be used in place of inter...

Page 9: ...achieve maximum performance Locating and Installing the Supply Damper s When locating the supply damper s carefully check floor joists and frame members that could interfere with the installation of...

Page 10: ...tionandplasticsleeve should be pulled over the connection and clamped f For homes with multiple supply ducts or for special applications a Y fitting is available to divide the supply air so it can be...

Page 11: ...stalled circuit breaker kits are used inside the control compartment Use only copper wire for the line voltagepowersupplytothisunit Usepropercode agency listed conduit and a conduit connector for conn...

Page 12: ...0 minutes 60 minutes and 90 minutes Time setting selection is dependent on the climate where the unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Ex...

Page 13: ...essor and fan energize and that the temperature of the discharge air is cooler than the room temperature This is available only for the single phase models System Cooling 1 Set the thermostat system s...

Page 14: ...out the availability of maintenance contracts At a minimum routine maintenance should include the following 1 Inspect and clean or replace air filters at the beginning of each heating and cooling seas...

Page 15: ...1 Stage Cool 1 Stage Electric Heat Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat Figure 12 Typical Heat Pump Thermostat Connections E O G R...

Page 16: ...173 253 174 270 175 81 222 175 238 177 255 178 272 179 289 180 83 226 179 242 181 258 182 274 183 291 184 85 245 185 261 186 278 187 293 188 87 265 190 281 192 297 193 89 284 196 301 197 91 304 202 93...

Page 17: ...SETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3 4 5...

Page 18: ...RESETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3...

Page 19: ...19...

Page 20: ...5460 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 05 06 708546 INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE H...

Reviews: