background image

11

If any of the original wire as supplied with the 
unit must be replaced, it must be replaced with 
material of the same gage and temperature 
rating.

 WARNING:

To avoid the risk of electrical shock, 
personal injury, or death, disconnect 
all electrical power to the unit before 
performing any maintenance or 
service. The unit may have more than 
one electrical power supply.

Line Voltage — 

Before proceeding with the 

electrical connections, make certain that the 
voltage, frequency, and phase of the supply 
source are the same as those specifi ed on the unit 
rating plate. Also verify that the service provided 
by the utility is suffi cient to handle the additional 
load imposed by this equipment.

See the unit wiring label for proper high and low 
voltage wiring. Make all electrical connections 
in accordance with all applicable codes and 
ordinances.

Use a separate branch electrical circuit for this 
unit. A means of electrical disconnect must be 
located within sight of and readily accessibility 
to the unit. Internally mounted circuit breakers 
are available as fi eld installed options. These 
circuit breakers can be used as an electrical 
disconnect.

The unit is shipped from the factory wired for 240 
volt transformer operation. For 208 volt operation, 
remove the lead from the transformer terminal 
marked 240V and connect it to the terminal 
marked 208V. For maximum ampacity and over 
current protection, see the unit rating plate.

Provide power supply (or supplies) for the unit in 
accordance with the unit wiring diagram, and the 
unit rating plate. Connect the line-voltage leads 
to the corresponding terminals on the contactor 
(or the circuit breaker when the fi eld installed 
circuit breaker kits are used) inside the control 
compartment. Use only copper wire for the line 
voltage power supply to this unit. Use proper code 
agency listed conduit and a conduit connector 
for connecting the supply wires to the unit and 
for obtaining proper grounding. Grounding may 
also be accomplished by using the grounding 
lug provided in the control box.

 WARNING:

The unit cabinet must have and 
uninterrupted or unbroken electrical 
ground to minimize personal injury if 
an electrical fault should occur. This 
ground may consist of electrical wire 
or approved conduit when installed in 
accordance with existing national or 
local codes.

Blower Speed — 

For optimum system 

performance and comfort, it may be necessary 
to change the factory set speed. To change the 
blower speed:

1.   Disconnect all electrical power to the unit 

and remove the blower panel. 

2.  Locate the orange and red wires 

terminated to the blower motor. The 
orange wire controls cooling operation 
while the red wire controls heating 
operation.

3.  Verify the required speed from the airfl ow 

data found in table 3. Place appropriate 
wire on the appropriate motor speed tap 

for the required airfl ow point.

NOTE: If the same speed is required for both 
heating and cooling. Obtain the jumper wire 
from the homeowners packet and connect it 
to the blower relays at the NO & NC terminals. 
Be sure to only connect the speed necessary 
to one side of the jumper wire.

 CAUTION:

To avoid personal injury or property 
damage, make certain that the motor 
leads cannot come into contact with 
any uninsulated metal components 
of the unit.

Check all factory wiring per the unit wiring 
diagram and inspect the factory wiring connec-
tions to be sure none loosened during shipping 
or installation.

Low Voltage Connections 

Room Thermostat  — 

Several options are 

available for a room thermostat depending on 

Summary of Contents for Q4RD 060

Page 1: ...g appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national a...

Page 2: ...2...

Page 3: ...a the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat transfer section in...

Page 4: ...oned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand the outdoor fan off for approximately six minutes following a previous operation or...

Page 5: ...ecautionsintheliterature on tags and on labels provided with the unit and or approved field installed kits The type of hazard and severity are described on each label or tag Pressures Within The Syste...

Page 6: ...URN DUCT OPENING 23 5 1 25 Power Entry 1 75 Power Entry Capped 0 88 Control Wiring Entry 23 6 27 2 30 1 8 4 00 13 5 16 0 14 7 13 5 16 0 13 45 11 75 22 75 55 8 C SUPPLY RETURN 4 0 CONDENSING COIL 5 0 8...

Page 7: ...hat drains well See Figure 6 AIR DUCTS This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire Protection A...

Page 8: ...ion SMACNA application standard for duct liners Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC 25 50 or less Fiber duct work may be used in place of inter...

Page 9: ...achieve maximum performance Locating and Installing the Supply Damper s When locating the supply damper s carefully check floor joists and frame members that could interfere with the installation of...

Page 10: ...tionandplasticsleeve should be pulled over the connection and clamped f For homes with multiple supply ducts or for special applications a Y fitting is available to divide the supply air so it can be...

Page 11: ...stalled circuit breaker kits are used inside the control compartment Use only copper wire for the line voltagepowersupplytothisunit Usepropercode agency listed conduit and a conduit connector for conn...

Page 12: ...0 minutes 60 minutes and 90 minutes Time setting selection is dependent on the climate where the unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Ex...

Page 13: ...essor and fan energize and that the temperature of the discharge air is cooler than the room temperature This is available only for the single phase models System Cooling 1 Set the thermostat system s...

Page 14: ...out the availability of maintenance contracts At a minimum routine maintenance should include the following 1 Inspect and clean or replace air filters at the beginning of each heating and cooling seas...

Page 15: ...1 Stage Cool 1 Stage Electric Heat Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat Figure 12 Typical Heat Pump Thermostat Connections E O G R...

Page 16: ...173 253 174 270 175 81 222 175 238 177 255 178 272 179 289 180 83 226 179 242 181 258 182 274 183 291 184 85 245 185 261 186 278 187 293 188 87 265 190 281 192 297 193 89 284 196 301 197 91 304 202 93...

Page 17: ...SETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3 4 5...

Page 18: ...RESETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3...

Page 19: ...19...

Page 20: ...5460 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 05 06 708546 INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE H...

Reviews: