background image

5

AIR HANDLER INSTALLATION

Packaging Removal
Remove the shipping crate and User’s Manual from the 
equipment. Take care not to damage the tubing connections 
when removing the crate.

Minimum Clearance Requirements
This air handler must be installed with ample clearance 
for easy access to the air fi lters, blower assembly, and, 
controls. Allow 24 inches minimum clearance from the 
front of the motor and refrigerant access panels for 
service and maintenance. However 36 inches is strongly 
recommended.

Horizontal Mounting Applications
B5SM air handlers can be suspended from support rods 
at each corner and are supplied with the required 1/2-13 
NC hardware. The installer only needs to supply the ½” 
full threaded support rods in an appropriate length for 
their application. NOTE: These units can be supported 
with 3/8” full threaded support rods, however all mounting 
hardware must be fi eld supplied. Once in position, verify 
the unit is level. See Figure 4 (page 10).

 

CAUTION:

When raising the air-handler for horizontal 
mounting, always use safe lifting methods 
and equipment. Always support the unit along 
its entire width. Failure to do so may result in 
damage to the lower panels or other equipment. 
If determined safe for your application the 
shipping pallet may be utilized with a forklift 
for this operation.

Vertical Mounting Applications
Verify the unit is level and there is adequate clearances to 
service the unit and provide the minimum 2” trap needed 
for the condensate drain. See Figure 5 (page 11).

Condensate Drain
B5SM air handlers have condensate drain ports on both 
sides of the unit, and may be confi gured for drainage from 
the left, right or both sides (Figures 4 or 5). Connection to 
the drains can be made with a ¾” threaded PVC adapter.

Units are confi gured at the factory with the service side 
drain open and a threaded PVC drain plug installed on 
the opposite side. Each drain line installed requires its 
own drain trap. To ensure proper drainage, the installed 
drain trap(s) must provide a minimum trap of 2 inches. 
Note: It is recommended that a secondary drain pan be 
used when the unit is hung above an enclosed ceiling.

Connecting Refrigerant Tubing

 

WARNING

:

Evaporator Coils are factory shipped with a 
nitrogen charge. Avoid direct face exposure or 
contact with valve when gas is escaping. Always 
ensure adequate ventilation is present during 
the depressurization process. Any uncertainties 
should be addressed before proceeding.

• When connecting refrigerant linesets together, it is 

recommended that dry nitrogen be fl owing through the 
joints during brazing. This will prevent internal oxidation 
and scaling from occurring.

•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 
in the tubing.

•  Refrigerant tubing should be supported in a manner 

that the tubing will not vibrate or abrade during system 
operation.

•  Tubing should be kept clean of foreign debris during 

installation.

•  Every effort should be made by the installer to ensure 

that the fi eld installed refrigerant containing components 
of the system have been installed in accordance with 
these instructions and sound installation practices to 
insure reliable system operation and longevity.

•  Always refer to the installation instructions supplied with 

the outdoor unit for piping requirements. The suction 
and liquid lines must be sized in accordance with the 
condensing unit specifi cations.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 
contact of the refrigerant lines with metal surfaces.

•  A fi lter dryer is provided with the unit and must be 

installed in the liquid line of the system. If the installation 
replaces a system with a fi lter dryer already present 
in the liquid line, the fi lter dryer must be replaced with 
the one supplied with the unit. The fi lter dryer must be 
installed in strict accordance with the manufacturer’s 
installation instructions.

•  B5SM air handlers are supplied with a direct expansion 

refrigerant coil and thermostatic expansion valves. 
Refrigerant line connections are located on the motor 
side (service side) of cabinet and require sweat 
connections.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

Summary of Contents for B5SM -090 Series

Page 1: ...ss to it in the future If a problem occurs check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions a...

Page 2: ...6 Electrical Wiring 7 Pre Electrical Checklist 7 Line Voltage 7 Thermostat Connections 7 Electrical Wiring with a Duct Heater 7 Unbalanced 3 Phase Supply Voltage 8 Grounding 8 Startup Adjustments 8 Pr...

Page 3: ...type equipment All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Ele...

Page 4: ...be given to availability of electric power service access noise and shade Field Connections for Electrical Power Supply All wiring must comply with current provisions of the National Electrical Code...

Page 5: ...hes Note It is recommended that a secondary drain pan be used when the unit is hung above an enclosed ceiling Connecting Refrigerant Tubing WARNING Evaporator Coils are factory shipped with a nitrogen...

Page 6: ...Z bracket See Figure 1 5 Secure the filter slide assembly together with the four screws Table 2 Electrical Rating Data MODEL VOLTAGE PHASE Hz FLA HP MCA MOP 090 120 J 208 230 460 3 60 6 6 6 6 3 3 2 8...

Page 7: ...re making any electrical connections to the unit See Figure 6 page 13 These air handlers can be purchased in both single and three phase power configurations all single phase equipment is shipped from...

Page 8: ...d verify the moveable face is properly secured Grounding WARNING The unit cabinet must have an uninterrupted or unbrokenelectricalgroundtominimizepersonal injury if an electrical fault should occur Do...

Page 9: ...zedorrotating equipment Always disconnect electrical power and allowallrotatingequipmenttostopbeforeservicing the unit Failure to do so may result in personal injury loss of limb or death from electri...

Page 10: ...57 Filter Rack Frame 60 1 4 Cabinet Width 1 5 8 1 5 8 25 1 16 Filter Rack 16 1 4 Electrical Knock outs Condensate Drain Figure 4 B5SM Physical Dimensions for Horizontal Installations 47 5 8 Center to...

Page 11: ...er Rack Frame 60 1 4 Cabinet Width 18 13 16 Supply Duct Opening 22 1 16 19 3 8 27 3 8 Cabinet Depth without Filter Rack 2 16 1 4 Supply Duct Opening 9 1 8 29 5 16 Depth with Filter Rack 25 1 16 Filter...

Page 12: ...8 0 9 1 0 CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw B5SM 120 2HP 60 Hz Fully Closed 4789 868 2 12 4640 868 2 00 4442 870 1 95 4208 873 1 87 40...

Page 13: ...ONLY NOTES 1 Disconnect all power before servicing 2 If wiring must be replaced use only 105 C copper wire of the same gauge 3 For economizer application remove black wire from low voltage board Y te...

Page 14: ...0 GRN GRY YEL BLK ORN RED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 NOTES 1 C W2 to be connected to electric heat 2 Remove BLACK wire from air handler low voltage terminal...

Page 15: ...ANGE RED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 BLACK BLACK GREEN BROWN SINGLE STAGE HEAT PUMP THERMOSTAT NOTE 1 NOTE 2 NOTE 4 NOTE 5 NOTE 3 G Y E R O B W2 C NOTES 1 Ju...

Page 16: ...all coil connections for leaks x Air Handler Assm Inspect Mounting Hardware for security and corrosion x Inspect Filter Rack mounting hardware for security x Inspect panel assemblies for proper insta...

Reviews: