background image

6

•  The B5SM-120 air handler has a dual circuit coil and 

the B5SM-090 has a single circuit coil.

•  The B5SM-120 air handler is charged through service 

valves on the end of the liquid tube for each circuit. 
These must be removed before brazing the line sets. 
The B5SM-090 is charged through a service valve 
inside the unit, which should not be removed.

•  Before brazing the B5SM-090, remove the core from 

the service port. Failure to do this may result in a leak 
at the service valve. Replace the core and cap once 
brazing is complete.

•  Optional equipment such as liquid line solenoid valves, 

low ambient, etc., should be installed in strict accordance 
with the manufacturer’s installation instructions.

Filter Requirements
B5SM air handlers are shipped with three permanent 
1” fi lters; however the fi lter rack can be converted to 
accommodate a 2” fi lter. To convert to a 2” fi lter:
1. Remove all fi lters from the unit.
2. Locate and remove the 4 screws (Figure 1) holding 

the bottom fi lter slide assembly (latch end) to the fi lter 
rack frame. NOTE: Be careful when removing the slide 
assembly so it does not drop into unit and cause damage 
to the coil.

3. Remove the 4 screws securing the “L” bracket to the 

“Z” bracket.

4. Rotate the “L” bracket 180 degrees, and reposition it so 

it mounts fl ush with the “Z” bracket. See Figure 1.

5. Secure the fi lter slide assembly together with the four 

screws. 

Table 2. Electrical Rating Data

MODEL

VOLTAGE

PHASE

Hz

FLA

HP

MCA

MOP

-090 & -120 J

208-230/460 

3

60

6.6-6.6/3.3

2

8.3-8.3/4.2

15

-090 & -120 K

208-230 

1

60

11.3-10.0

2

14.2-12.5

25-20

FLA = Full Load Amps, MCA = Minimum Circuit Ampacity, MOP = Maximum Over-Current Protection

Table 1. Pressure Drop Across Filters

Model

B5SM

Nominal

CFM

Filter

Size

Resistance 

(W.C.)

090

2200

18 x 24 (1”)

0.03

2600

0.04

3000

0.05

3400

0.07

3800

0.08

4200

0.09

120

3000

18 x 24 (1”)

0.05

3400

0.07

3800

0.08

4200

0.09

4600

0.11

5000

0.13

6. Re-install the fi lter slide assembly back into the fi lter rack 

frame and secure with the 4 screws removed earlier.  If 
replacing factory supplied fi lters with disposable fi lters, 
use only 2” disposable fi lters.

Accessing the fi lters does not require tools and can be 
performed from either side of the fi lter-rack. On the service 
side of the unit, locate the release knob at the base of 
the fi lter rack and rotate clockwise to unlock, then pull up 
and out to remove the fi lter access panel. On the blower 
side, use the same method but rotate counter-clockwise 
to unlock. 

Figure 1. Converting from 1” Filter to 2” Filter Applications

BRACKET CONFIGURATION FOR 

2” FILTER APPLICATIONS

BRACKET CONFIGURATION

FOR 1” FILTER APPLICATIONS

(FACTORY SETTING)

“Z” BRACKET

“L” BRACKET

REMOVE 4 SCREWS FROM 

FILTER RACK FRAME

FILTERS

FILTER BRACKET

LOCATION

REMOVE 4 SCREWS SECURING

“Z” BRACKET AND “L” BRACKET

Summary of Contents for B5SM -090 Series

Page 1: ...ss to it in the future If a problem occurs check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions a...

Page 2: ...6 Electrical Wiring 7 Pre Electrical Checklist 7 Line Voltage 7 Thermostat Connections 7 Electrical Wiring with a Duct Heater 7 Unbalanced 3 Phase Supply Voltage 8 Grounding 8 Startup Adjustments 8 Pr...

Page 3: ...type equipment All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Ele...

Page 4: ...be given to availability of electric power service access noise and shade Field Connections for Electrical Power Supply All wiring must comply with current provisions of the National Electrical Code...

Page 5: ...hes Note It is recommended that a secondary drain pan be used when the unit is hung above an enclosed ceiling Connecting Refrigerant Tubing WARNING Evaporator Coils are factory shipped with a nitrogen...

Page 6: ...Z bracket See Figure 1 5 Secure the filter slide assembly together with the four screws Table 2 Electrical Rating Data MODEL VOLTAGE PHASE Hz FLA HP MCA MOP 090 120 J 208 230 460 3 60 6 6 6 6 3 3 2 8...

Page 7: ...re making any electrical connections to the unit See Figure 6 page 13 These air handlers can be purchased in both single and three phase power configurations all single phase equipment is shipped from...

Page 8: ...d verify the moveable face is properly secured Grounding WARNING The unit cabinet must have an uninterrupted or unbrokenelectricalgroundtominimizepersonal injury if an electrical fault should occur Do...

Page 9: ...zedorrotating equipment Always disconnect electrical power and allowallrotatingequipmenttostopbeforeservicing the unit Failure to do so may result in personal injury loss of limb or death from electri...

Page 10: ...57 Filter Rack Frame 60 1 4 Cabinet Width 1 5 8 1 5 8 25 1 16 Filter Rack 16 1 4 Electrical Knock outs Condensate Drain Figure 4 B5SM Physical Dimensions for Horizontal Installations 47 5 8 Center to...

Page 11: ...er Rack Frame 60 1 4 Cabinet Width 18 13 16 Supply Duct Opening 22 1 16 19 3 8 27 3 8 Cabinet Depth without Filter Rack 2 16 1 4 Supply Duct Opening 9 1 8 29 5 16 Depth with Filter Rack 25 1 16 Filter...

Page 12: ...8 0 9 1 0 CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw B5SM 120 2HP 60 Hz Fully Closed 4789 868 2 12 4640 868 2 00 4442 870 1 95 4208 873 1 87 40...

Page 13: ...ONLY NOTES 1 Disconnect all power before servicing 2 If wiring must be replaced use only 105 C copper wire of the same gauge 3 For economizer application remove black wire from low voltage board Y te...

Page 14: ...0 GRN GRY YEL BLK ORN RED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 NOTES 1 C W2 to be connected to electric heat 2 Remove BLACK wire from air handler low voltage terminal...

Page 15: ...ANGE RED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 BLACK BLACK GREEN BROWN SINGLE STAGE HEAT PUMP THERMOSTAT NOTE 1 NOTE 2 NOTE 4 NOTE 5 NOTE 3 G Y E R O B W2 C NOTES 1 Ju...

Page 16: ...all coil connections for leaks x Air Handler Assm Inspect Mounting Hardware for security and corrosion x Inspect Filter Rack mounting hardware for security x Inspect panel assemblies for proper insta...