background image

15

Figure 8. Typical Heat Pump Thermostat Connections

BLOWER

MOTER

GND

BLACK

BLACK

GREEN

BROWN

TO FIELD
SUPPLIED DISCONNECT

SINGLE STAGE

HEAT PUMP THERMOSTAT

OUTDOOR

SECTION

NOTE 1

NOTE 2

FREEZESTAT

TYPICAL HEAT PUMP THERMOSTAT CONNECTION (NO ECONOMIZER)

AIR HANDLER

SECTION

TERMINAL

BOARD

G
C

W2

O

R
Y

W1

C

Y

R

G Y

E

R O

B

L1

L2

L3

O

W2

W2

C

NOTES:

1. Jumper between W2 and E is required.

2. C &W2 to be connected to electric heat.

TYPICAL HEAT PUMP THERMOSTAT CONNECTION (WITH ECONOMIZER)

BLOWER

MOTER

GND

TO FIELD
SUPPLIED DISCONNECT

OUTDOOR

SECTION

FREEZESTAT

AIR HANDLER

SECTION

TERMINAL

BOARD

G
C

W2

O
R

Y

W1

C

Y

R

L1

L2

L3

O

W2

s

C7400A

B

Y1

OPTIONAL

ECONOMIZER

W7459A

C7150
M.A.S.

TB-11

M7415A

T

T1MA

MIN.

POT.

P1

P

TR1

TR

Y2

S

TR 1

TR

o

S

1

3

2

4

T

P

T1

2K

JUMPER

WIRE

5

P1

r

1S

1S

A

B

7

9

4

6

1

3

BLU-14”

YEL-18”

GRY-90”

GREEN

GREY

YELLOW

BLACK

ORANGE

RED

RED

WHITE

BLUE

VIO-14”

GRN-18”
GRN-18”

RED-12”

GRY-12”

BLK-12”

BLU-12”

BLK-12”

BLACK

BLACK

GREEN

BROWN

SINGLE STAGE

HEAT PUMP THERMOSTAT

NOTE 1

NOTE 2

NOTE 4

NOTE 5

NOTE 3

G Y

E

R O

B

W2

C

NOTES:

1. Jumper between W2 and is required.

2. W2 to be connected to electric heat.
3. Remove BLACK wire from air handler low voltage terminal board
    terminal and connect to YELLOW wire from economizer.
4. 2nd Stage refrigerant cooling with optional economizer installed. A 2 
    stage thermostat is required for simultaneous operation of the economizer
    and refrigerant system. Connect Y2 from 2 stage thermostat to BLUE 
    wire from economizer. If installing an economizer in this unit, refer to the 
    Economizer installation instructions for proper set up and operation. 
5. Heat Pump Economizer Relay. Connect B from thermostat to GREY 
    wire from Economizer. Required for proper operation of an economizer 
    (optional) in the heat pump Heating mode. If installing an economizer in
    this unit, refer to the Economizer installation instructions for proper set 
    up and operation.  

Summary of Contents for B5SM -090 Series

Page 1: ...ss to it in the future If a problem occurs check the instructions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions a...

Page 2: ...6 Electrical Wiring 7 Pre Electrical Checklist 7 Line Voltage 7 Thermostat Connections 7 Electrical Wiring with a Duct Heater 7 Unbalanced 3 Phase Supply Voltage 8 Grounding 8 Startup Adjustments 8 Pr...

Page 3: ...type equipment All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Ele...

Page 4: ...be given to availability of electric power service access noise and shade Field Connections for Electrical Power Supply All wiring must comply with current provisions of the National Electrical Code...

Page 5: ...hes Note It is recommended that a secondary drain pan be used when the unit is hung above an enclosed ceiling Connecting Refrigerant Tubing WARNING Evaporator Coils are factory shipped with a nitrogen...

Page 6: ...Z bracket See Figure 1 5 Secure the filter slide assembly together with the four screws Table 2 Electrical Rating Data MODEL VOLTAGE PHASE Hz FLA HP MCA MOP 090 120 J 208 230 460 3 60 6 6 6 6 3 3 2 8...

Page 7: ...re making any electrical connections to the unit See Figure 6 page 13 These air handlers can be purchased in both single and three phase power configurations all single phase equipment is shipped from...

Page 8: ...d verify the moveable face is properly secured Grounding WARNING The unit cabinet must have an uninterrupted or unbrokenelectricalgroundtominimizepersonal injury if an electrical fault should occur Do...

Page 9: ...zedorrotating equipment Always disconnect electrical power and allowallrotatingequipmenttostopbeforeservicing the unit Failure to do so may result in personal injury loss of limb or death from electri...

Page 10: ...57 Filter Rack Frame 60 1 4 Cabinet Width 1 5 8 1 5 8 25 1 16 Filter Rack 16 1 4 Electrical Knock outs Condensate Drain Figure 4 B5SM Physical Dimensions for Horizontal Installations 47 5 8 Center to...

Page 11: ...er Rack Frame 60 1 4 Cabinet Width 18 13 16 Supply Duct Opening 22 1 16 19 3 8 27 3 8 Cabinet Depth without Filter Rack 2 16 1 4 Supply Duct Opening 9 1 8 29 5 16 Depth with Filter Rack 25 1 16 Filter...

Page 12: ...8 0 9 1 0 CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw CFM RPM Kw B5SM 120 2HP 60 Hz Fully Closed 4789 868 2 12 4640 868 2 00 4442 870 1 95 4208 873 1 87 40...

Page 13: ...ONLY NOTES 1 Disconnect all power before servicing 2 If wiring must be replaced use only 105 C copper wire of the same gauge 3 For economizer application remove black wire from low voltage board Y te...

Page 14: ...0 GRN GRY YEL BLK ORN RED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 NOTES 1 C W2 to be connected to electric heat 2 Remove BLACK wire from air handler low voltage terminal...

Page 15: ...ANGE RED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 BLACK BLACK GREEN BROWN SINGLE STAGE HEAT PUMP THERMOSTAT NOTE 1 NOTE 2 NOTE 4 NOTE 5 NOTE 3 G Y E R O B W2 C NOTES 1 Ju...

Page 16: ...all coil connections for leaks x Air Handler Assm Inspect Mounting Hardware for security and corrosion x Inspect Filter Rack mounting hardware for security x Inspect panel assemblies for proper insta...

Reviews: