INSTALLATION AND OPERATION MANUAL

Nordmann SPA Display

2591871-A  EN  1903

Summary of Contents for SPA Display

Page 1: ...INSTALLATION AND OPERATION MANUAL Nordmann SPA Display 2591871 A EN 1903...

Page 2: ...oduced used or disclosed to others without the written authorisation of Nordmann Engineering AG except to the extent required for installation or maintenance of recipient s equipment Liability Notice...

Page 3: ...ing 11 4 4 2 On wall mounting 17 4 5 Connecting the Nordmann SPA Display to the Nordmann Omega or to the Condair Delta SPA Control Box 23 5 Configuration and operation of the Nordmann SPA Display 27 5...

Page 4: ...ssioning operation and trouble shooting of the Nordmann SPA Display and is meant for well trained personnel being sufficiently qualified for their respective work This installation and operation manua...

Page 5: ...ta SPA Control Box with which the Nordmann SPA Display is used changes hands the documentation should be passed on to the new operator If the documentation gets mislaid please contact your Nordmann re...

Page 6: ...resentative It is assumed that all persons working with the Nordmann SPA Display are familiar and comply with the appropriate regulations on work safety and the prevention of accidents This unit may n...

Page 7: ...ircumstances if the Nordmann SPA Display is damaged if the Nordmann SPA Display is no longer operating correctly if the connecting cable is damaged All persons working with the Nordmann SPA Display mu...

Page 8: ...iew 6 3 2a 7 3 6 2b 7 8 Fig 3 Back view Fig 4 Back view 3 Product Overview 1 Touch sensitive display 2a In wall mounted housing 2b On wall mounted housing 3 Connecting terminals CAN BUS 4 Decorative c...

Page 9: ...c bag containing mounting material Decoration cover with pre mounted centring frame and sealing if ordered Please check the equipment for damage Please report any damage to your Nordmann representativ...

Page 10: ...the CAN BUS cables with which the Nordmann Omega or the Condair Delta SPA Control Box and the Nordmann SPA Display s are interconnected is not exceeded 4 4 Mounting the Nordmann SPA Display CAUTION Th...

Page 11: ...e only 9 mm and on the top and bottom side only 8 5 mm 8 5 mm 141 mm 124 mm 87 mm 9 mm 4 mm T 100 mm 8 5 mm 141 mm 124 mm 87 mm 9 mm 4 mm T 100 mm Cavity wall Tmin 15 mm Massive wall Tmin 35 mm Fig 5...

Page 12: ...ortar Fig 7 Mounting the in wall mounted housing to the wall opening 4 Free the shielding of the CAN BUS cable s by removing the insulation from the appropriate clamp ing position to the end of the ca...

Page 13: ...the suitable wire end ferrules and insert the cable wires as far as possible into the correct connection opening of the sup plied CAN BUS connecting plug Then connect the CAN BUS connecting plug to t...

Page 14: ...4 5 Important If two CAN BUS cables are connected to the Nordmann SPADisplay board jumper JP1 terminator on the Nordmann SPA Display must be removed X3 JP1 1 4 L H 24V GND L H 24V GND L H 24V GND X2 1...

Page 15: ...of the Nordmann Omega SPA Display 7 After function tests have been passed carefully place the Nordmann SPA Display onto the in wall mounted housing Make sure the supply cable is not getting pinched Th...

Page 16: ...ay Fig 12 Adjusting the display 9 Finally attach the decoration cover the decoration cover is held by the magnets in the in wall mounted housing and seal the gap between the decoration cover and the w...

Page 17: ...mm depth 35 mm Note If the mounting location does not permit bolt mounting e g on a glass wall the aluminum on wall mounted housing can also be glued over its entire surface to the underground If the...

Page 18: ...sed shielding to about 2 cm then fix the end of the remaining shielding with a piece of shrink tubing as shown in Fig 15 and secure the exposed shielding with the shielding clamp s to the housing In w...

Page 19: ...using the screws supplied align housing with the help of a spirit level and fasten den screws for the mounting on a wooden wall Fix on wall mounted housing to the wall using the countersunk screws su...

Page 20: ...the suitable wire end ferrules and insert the cable wires as far as possible into the correct connection opening of the sup plied CAN BUS connecting plug Then connect the CAN BUS connecting plug to t...

Page 21: ...4 5 Important If two CAN BUS cables are connected to the Nordmann SPADisplay board jumper JP1 terminator on the Nordmann SPA Display must be removed X3 JP1 1 4 L H 24V GND L H 24V GND L H 24V GND X2 1...

Page 22: ...unted housing make sure the supply cable is not getting pinched Then fix the Nordmann SPA Display to the on wall mounted housing using the four screws supplied Seal the cable entry at the bottom of th...

Page 23: ...Omega or the Condair Delta SPA Control Box respectively are very sensitive to electrostatic discharge When the unit is open for installation work appropriate measures must be taken to protect these c...

Page 24: ...manual for the Nordmann Omega or the Condair Delta SPA Control Box SPA Display D2 2 D2 x X3 JP1 X3 X2 1 4 1 4 X11 L H 24V GND GND 24V H L L H 24V GND SF X23 X24 JP1 SW1 SPA Display D1 JP1 X3 X2 1 4 1...

Page 25: ...24 JP1 SW1 SPA Display D1 JP1 X3 X2 1 4 1 4 L H 24V GND L H 24V GND SPA Display D2 Condair Delta SPA Control Box Nordmann Omega A B B Fig 23 Wiring diagram variant 2 with one or more Nordmann SPA Disp...

Page 26: ...ttom in the housing of the Nordmann Omega Fig 24 Feeding the cable s through the ferrite ring s and fixing the cable shield s in the clamp holder s 7 Remount front panel of the Nordmann Omega or Conda...

Page 27: ...must be assigned to each connected SPA display For each connected SPA display go to the menu Engineering Administration Display Server ID Display and assign an individual address to the Nordmann SPA D...

Page 28: ...roke is not detected in the correct location Displayisnotcalibratedcorrectly If possible access the calibration function Path Menu Engineer ing Admin Display Cali brate and start the calibration funct...

Page 29: ...nd any other system components if necessary unmounted by a qualified service technician 7 2 Disposal Recycling Components not used any more must not be disposed of in the domestic waste Please dispose...

Page 30: ...ated power 2 W Admissible ambient temperature 20 70 C Admissible ambient humidity 10 80 rh non condensing Type of protection IP44 IP44 IP33 1 Conformity CE Control ARM Cortex M4 high performance micro...

Page 31: ...2595477 6 SPA Display adapter cable 2595479 Plug for CAN BUS cable 5 pcs 2591662 CAN BUS cable shielded 50 m 2591666 Clamp holder for shielding 5 pcs 2591667 Foldable ferrite ring for EMC 2594845 If...

Page 32: ...Notes...

Page 33: ...Notes...

Page 34: ...Notes...

Page 35: ......

Page 36: ...CH94 0002 01 Nordmann Engineering AG Lindenhofstrasse 28 4052 Basel Switzerland Phone 41 61 404 46 50 Fax 41 61 404 46 79 www nordmann engineering com info nordmann engineering com...