Nordic R-45 Installation And Service Manual Download Page 7

1-Nov-2021 

Page   7 

001200MAN-09 

 

Sizing 

TABLE 2 - Heat Pump Size vs.  Heated Area 

                  for an Open Loop System 

Model

 

ft

2

 

m

2

 

R/RH-45 

1800 

165 

R/RH-55 

2500 

230 

R/RH-65 

3200 

295 

R/RH-75 

3800 

355 

R-80 

4200 

390 

Heat Pump Sizing 

 

The following table is a rough guideline as to the size of 

space each heat pump size can handle for 

ground loop (closed 

loop) 

installations.   

The following table is a rough guideline as to the size of 

home each heat pump size can handle for 

ground water (open 

loop) 

installations.   

THE TABLES ABOVE ARE FOR ESTIMATION ONLY. 

THEY SHOULD NOT BE USED TO SELECT A FINAL UNIT 

SIZE.  

They simply show what size unit is required for a 

northern home with typical construction: R20 walls, R40 ceiling, 

and average size and number of windows.  The heated area is 

the area of the above grade main level; the tables account for a 

basement the same size as the heated area. 

 

MARITME GEOTHERMAL LTD. HIGHLY RECOM-

MENDS THAT A PROPER HEAT LOSS/GAIN ANALYSIS BE 

PERFORMED BY A PROFESSIONAL WITH APPROVED CSA 

F-280 SOFTWARE BEFORE SELECTING THE HEAT PUMP 

SIZE.  For heating dominant climates, we recommend sizing 

the unit to 100% of the heating design load for maximum 

long term efficiency with minimal supplementary heat.  The 

unit should be installed as per CSA standard 448.2-02.  For 

ground loop applications, the ground loop should be de-

signed using suitable software with a multi-year analysis. 

 

The analysis will result in a heat load for the coldest day, 

which is influenced by, for example, the number of levels, the 

size of the windows, the orientation of the home, attached gar-

age, bonus rooms, walk-in basement, and coldest outdoor tem-

perature for the region.    

 

A heat pump model size can then be selected by compar-

ing the calculated heat load to the heat pump capacity at the 

standard indoor air temperature, which can be found in the per-

formance tables in the 

Model Specific Information 

section.  For 

R-series, the 

Standard Capacity Ratings

 rather than detailed 

performance tables can be used for simplicity.  For 100% heat 

pump sizing, choose a heat pump with a standard capacity rat-

ing that matches or just slightly exceeds the calculated heat 

load. 

Some background on 

Standard Capacity Ratings

: closed 

ground loops are normally designed to reach a minimum tem-

perature of just below freezing at the end of the heating season, 

in order to take advantage of the latent heat of groundwater (at 

least in northern climates). Hence, the Standard Capacity Rat-

ings for Ground Loop Heating should apply in all northern cli-

mates.  Conversely,

 

the Standard Capacity Ratings for Ground 

Water (open loop) heat pumps assume a well water temperature 

of 50°F (10° C). In more southerly climates, the groundwater or 

ground loop will probably be at a warmer minimum temperature, 

and it will be necessary to consult the more detailed perfor-

mance tables for heat pump output at a different ELT. 

 

 

In cooling dominant climates, the heat pump should be 

similarly sized using the Ground Loop Cooling or Ground Water 

Cooling Standard Capacity Ratings.  

Even in northern heating 

dominant climates, it should be ensured that 100% of the 

cooling load will be covered when sizing the heat pump, 

since there is normally no auxiliary or backup cooling avail-

able. 

 

Plenum Heater Sizing 

 

The plenum heater is available as an accessory in 5, 7, 10, 

15 and 20kW sizes.  If full backup is desired, choose a size that 

covers 

100% of the coldest day heat load

, according to the heat 

loss analysis mentioned in the last section.  If that is not availa-

ble, use the following recommendation:

 

Two styles of plenum heater are available; the first is for R-

series internal installation (inside the indoor unit).  Note limit for 

size 45 in above table.   

 

The second has a wider element profile for installation 

outside the unit, in the ductwork.  For RH series or for R series 

when field-installing the fan in the convertible side discharge 

position, this type of plenum heater should be used.

 

TABLE 3 - Plenum Heater Sizing 

Model 

Plenum Heater Size (kW) 

Full Backup 

Possible

 

Not Possible

 

R/RH-45 

10  

5, 7, 10 

15, 20* 

R/RH-55 

10  

5, 7, 10, 15, 20 

 

R/RH-65 

15 

5, 7, 10, 15, 20 

 

R/RH-75  

20 

5, 7, 10, 15, 20 

 

R-80 

20 

5, 7, 10, 15, 20 

 

* Although these plenum heaters will not fit inside heat pump, 

there are versions available for external mounting. 

TABLE 1 - Heat Pump Size vs. Heated Area 

                  for a Ground Loop System 

Model

 

ft

2

 

m

2

 

R/RH-45 

1400 

130 

R/RH-55 

2000 

185 

R/RH-65 

2600 

240 

R/RH-75 

3100 

290 

R-80 

3500 

325 

Summary of Contents for R-45

Page 1: ...l Ltd P O Box 2555 170 Plantation Road Petitcodiac NB E4Z 6H4 506 756 8135 R RH Series Liquid to Air Geothermal Heat Pumps Two Stage R410a Model Sizes 45 80 info nordicghp com www nordicghp com 001200...

Page 2: ...is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be employed whenever repairs require removal of refrigerant from the heat pump Series R Rev...

Page 3: ...C Y Z SDELF SDERF 12 13 14 15 2 T 4 T 6 S 7 T R 80 HACW P 1 2 3 4 7 S C Y Z SDELF SDERF 10 11 RH 45 HACW P 1 2 3 4 6 7 T C Y Z SDELF SDERF 08 RH 55 HACW P 1 2 3 4 6 7 T C Y Z SDELF SDERF 08 RH 65 HACW...

Page 4: ...31 Water Flow Control 31 Submersible Pump Selection 32 Table of Contents Stage 1 vs 2 on Open Loop 32 Plumbing the Heat Pump 32 Pipe Insulation 32 000907CDG Typical Open Loop Installation 33 001822CDG...

Page 5: ...onfiguration 25 000609INF Typical Vertical Ground Loop Configuration 26 000906CDG Geo Flo Circulator Pump Module Installation 27 001823CDG Dual Flow Circulator Pump Module Installation for 2 Stage Hea...

Page 6: ...ns A single thermo static expansion valve TXV regulates superheat The cabinet is constructed from powder coated galvanized sheet metal 1 Heating Mode In heating mode the heat pump heats warm air in a...

Page 7: ...slightly exceeds the calculated heat load Some background on Standard Capacity Ratings closed ground loops are normally designed to reach a minimum tem perature of just below freezing at the end of t...

Page 8: ...RCHASED Sample Bill of Materials Open Loop Installations FROM MARITIME GEOTHERMAL R RH SERIES HEAT PUMP L OR R RETURN PLENUM HEATER __kW THERMOSTAT WIFI OR STD P T PORTS AND HOSE ADAPTERS 2 DOLE VALVE...

Page 9: ...at step 2 for the access panel with the blower mounted in it Set the assembly on the floor 5 Disconnect the plenum heater extension from the blower housing and from the access panel 6 Mount the blower...

Page 10: ...is mounted inside heat pump cabinet See diagram on following page Remove the screws from the cover plate remove the cover plate and place the plenum heater in the cutout Slide it up and secure the bot...

Page 11: ...1 Nov 2021 Page 11 001200MAN 09...

Page 12: ...at pump has provisions for connecting the circulator pump module so that the pumps will be turned on whenever the compressor operates Connect the circulator pump module to the appropriate two terminal...

Page 13: ...Cooling Mode reversing valve Y2 Heat Pump Stage 2 not used for single stage units AR1 Airflow Reduction AR2 Airflow Reduction CP I Plenum Heater dry contact Connect to C or I in plenum heater 1 Plenum...

Page 14: ...flow sensor located in the drip tray and the voltage of the 24vac transformer A fault will occur if a conden sate overflow is detected or a low voltage condition electricity grid brownout is detected...

Page 15: ...1 Nov 2021 Page 15 001200MAN 09...

Page 16: ...1 Nov 2021 Page 16 001200MAN 09...

Page 17: ...es the possibility of reverse heating of the refrigerant gas under low condensing temperature operating conditions WARNING USE ONLY COPPER LINES TO CONNECT THE DESUPERHEATER TEMPERA TURES CAN BE 200 F...

Page 18: ...1 Nov 2021 Page 18 001200MAN 09...

Page 19: ...1 Nov 2021 Page 19 001200MAN 09...

Page 20: ...e heater elements If desired the first 5 10 feet of the main supply trunks can be insulated internally with acoustical duct insulation to further inhibit any noise from the unit from travelling down t...

Page 21: ...1 Nov 2021 Page 21 001200MAN 09...

Page 22: ...17 16 5 x 16 5 22 944 2250 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 22 1062 2600 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 24 1227 2900 22 12 x 36 14 x 30 16 x 26 18 x 23 2...

Page 23: ...pump module that can deliver the flow required for the unit at the calculated total pressure drop should be selected Refer to the Model Specific Information section for unit flow re quirements Loop pr...

Page 24: ...k closed cell pipe insulation to prevent condensa tion and dripping onto floors or walls Although many different antifreeze solutions have been employed in geothermal systems the alcohols such as meth...

Page 25: ...1 Nov 2021 Page 25 001200MAN 09...

Page 26: ...1 Nov 2021 Page 26 001200MAN 09...

Page 27: ...1 Nov 2021 Page 27 001200MAN 09...

Page 28: ...1 Nov 2021 Page 28 001200MAN 09...

Page 29: ...1 Nov 2021 Page 29 001200MAN 09...

Page 30: ...or significant Ammonia 0 5 ppm or H2S 0 2 ppm is present the use of an open loop system should be reconsidered Water Discharge Methods Water disposal methods vary from area to area However some consi...

Page 31: ...the pipe from freezing As opposed to the percolation method water will remain in the end of the pipe It is recommended that the surface of the pond be lower than the installation location of the heat...

Page 32: ...ble pump will proba bly negate the COP benefit of running the heat pump on stage 1 In this case it is recommended to jumper Y1 and Y2 together at the heat pump terminal strip in order to satisfy the h...

Page 33: ...1 Nov 2021 Page 33 001200MAN 09...

Page 34: ...1 Nov 2021 Page 34 001200MAN 09...

Page 35: ...1 Nov 2021 Page 35 001200MAN 09...

Page 36: ...freeze and the mixture value on the startup sheet circle Vol or Weight 4 Record the static loop pressure on the startup sheet Outdoor Loop Open Loop 1 Verify there are no leaks in the connections to t...

Page 37: ...unit Connect the brown wire with the blue insulated terminal to the compressor contactor as shown in the electrical box diagram Turn the DHW Switch in the unit post on Turn the power to the unit on 6...

Page 38: ...orrect and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct a...

Page 39: ...warm water open loop systems unusual Coaxial Heat Exchanger Flushing Procedure Open Loop 1 Isolate the heat exchanger by closing the valves in the IN and OUT ports to the heat exchanger 2 Blow out the...

Page 40: ...urs 3 hours recommended 5 Disconnect the purge cart and dispose of the solution RYDLYME is non toxic and biodegradable and as such can be poured down a drain Clean the purge cart thoroughly 6 Connect...

Page 41: ...urn the power off wait 10 seconds and turn the power back on Set the thermostat to call for heating or cooling depending on the season STEP 3 If a 24VAC signal does not appear across Y1 and C of the t...

Page 42: ...th compressor on See Low Discharge Pressure in Heating Mode Cooling Mode Troubleshooting section Faulty low pressure con trol failed open very unlikely For this test there must be a signal present on...

Page 43: ...re compressor overload has had a chance to reset If compressor is hot this may take several hours Replace the compressor Burned out motor shorted windings Remove wires from compressor Resistance betwe...

Page 44: ...of the flow restriction and correct it Verify pumps are working and sized correctly for ground loop systems Verify well pump and water valve is working for ground water sys tems Entering liquid temper...

Page 45: ...osits Backflush the coaxial exchanger with a calcium removing cleaning solution OPERATION TROUBLESHOOTING HEATING MODE Fault Possible Cause Verification Recommended Action High Suction Pressure may ap...

Page 46: ...Low Suction Pressure Low airflow See Fan Troubleshooting section Note low airflow will cause the air coil to ice up once the suction drops below 90PSIG Correct the problem TXV stuck almost closed or...

Page 47: ...the following at the fan con trol signal harness insert probes in connector where wire is inserted do not unplug the connector Recirculation grey pin 15 Stage 1 yellow pin 6 Stage 2 yellow black pin1...

Page 48: ...heck the thermostat manual Faulty thermostat Thermostat doesn t indicate a call for auxiliary or emergency when it should Or thermostat indicates aux iliary or emergency but no 24VAC signal present ac...

Page 49: ...why possible shorted element Correct problem and replace blown fuse or reset breaker Reset button tripped on hot water tank Check voltage at elements with multimeter Push reset button DHW switch is t...

Page 50: ...rocedures to prevent soot buildup inside the pipes It is recommended to replace the liquid line filter dryer any time the refrigeration system has been exposed to the atmosphere Place a wet rag around...

Page 51: ...soot buildup inside the pipes 4 Vacuum the unit as per above procedure 5 If there was a compressor burnout a Charge the unit with new refrigerant and operate it for continuously for 2 hours Pump down...

Page 52: ...Adequate antifreeze concentration required Heating Maximum ELT 80 27 Reduce flow above this temperature Cooling Minimum ELT 41 5 Flow reduction may be required Cooling Maximum ELT 110 43 INDOOR air d...

Page 53: ...6 16 1 01 Stage 1 1660 783 2 305 54 300 15 9 7 2 24 4 Stage 2 2100 991 3 710 69 800 20 5 5 7 19 4 R 80 6 17 1 07 Stage 1 2400 1133 4 130 86 500 25 4 5 8 19 6 Table 19 Standard Capacity Ratings Ground...

Page 54: ...4 3 30 4 6 32 5 5 38 7 2 50 12 0 76 5 2 36 5 5 38 6 6 45 8 7 60 13 0 82 5 9 41 6 2 43 7 4 51 9 7 67 R RH 45 14 0 88 6 7 46 7 0 48 8 6 59 11 3 78 15 0 95 8 0 55 8 2 57 9 5 65 12 5 86 6 0 38 1 1 7 6 1 2...

Page 55: ...1 0 6 9 1 3 9 0 8 0 50 1 2 8 3 1 3 9 0 1 3 9 0 1 7 12 9 0 57 1 5 10 1 6 11 1 6 11 2 1 14 10 0 63 1 8 12 1 9 13 2 1 14 2 8 19 11 0 69 2 1 14 2 3 16 2 4 17 3 2 22 12 0 76 2 4 17 2 6 18 2 9 20 3 8 26 13...

Page 56: ...7 50 10 60 7 0 34 965 11 1 2 770 116 1 200 103 38 0 44 185 4 67 Fan W 179 179 179 179 179 179 179 179 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat...

Page 57: ...0 12 59 8 6 51 663 14 1 3 247 112 1 500 108 40 4 62 471 5 64 Fan W 185 185 185 185 185 185 185 185 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej...

Page 58: ...14 58 8 7 61 001 18 3 4 353 113 1 900 107 38 6 75 456 5 08 Fan W 300 300 300 300 300 300 300 300 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej...

Page 59: ...5 69 50 16 60 8 9 71 411 21 1 4 951 113 2 100 109 40 6 87 893 5 20 Fan W 410 410 410 410 410 410 410 410 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C He...

Page 60: ...00 106 4 38 4 87 458 4 64 66 0 50 16 8 57 0 9 0 75 450 26 1 5 594 113 2 400 109 3 41 3 94 236 4 94 Fan W 661 661 661 661 661 661 661 661 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond...

Page 61: ...230 581 1000 472 850 401 75 1974 932 1678 792 1560 736 1326 626 1105 522 940 443 80 2256 1065 1918 905 N A N A N A N A 1263 596 1074 507 Table 25 HIGH Airflow 6 Model STAGE 2 STAGE 1 FAN ONLY Recircul...

Page 62: ...required if connecting 115VAC circulators to the unit R RH 55 1 208 230 1 60 187 253 20 4 122 4 0 5 0 30 2 35 3 50 8 2 2 208 3 60 187 229 14 0 83 4 0 5 0 23 8 27 3 40 8 3 3 265 277 1 60 226 304 16 0 1...

Page 63: ...1 Nov 2021 Page 63 001200MAN 09 Wiring Diagram 208 230 1 60...

Page 64: ...1 Nov 2021 Page 64 001200MAN 09 Electrical Box Layout R 45 75 208 230 1 60...

Page 65: ...1 Nov 2021 Page 65 001200MAN 09 Electrical Box Layout R 80 208 230 1 60...

Page 66: ...1 Nov 2021 Page 66 001200MAN 09 Electrical Box Layout RH 45 75 208 230 1 60...

Page 67: ...1 Nov 2021 Page 67 001200MAN 09 Wiring Diagram 208 3 60...

Page 68: ...1 Nov 2021 Page 68 001200MAN 09 Electrical Box Layout R 45 75 208 3 60...

Page 69: ...1 Nov 2021 Page 69 001200MAN 09 Electrical Box Layout R 80 208 3 60...

Page 70: ...1 Nov 2021 Page 70 001200MAN 09 Electrical Box Layout RH 45 75 208 3 60...

Page 71: ...1 Nov 2021 Page 71 001200MAN 09 Wiring Diagram 265 277 1 60...

Page 72: ...1 Nov 2021 Page 72 001200MAN 09 Electrical Box Layout R 45 75 265 277 1 60...

Page 73: ...1 Nov 2021 Page 73 001200MAN 09 Electrical Box Layout R 80 265 277 1 60...

Page 74: ...1 Nov 2021 Page 74 001200MAN 09 Electrical Box Layout RH 45 75 265 277 1 60...

Page 75: ...1 Nov 2021 Page 75 001200MAN 09 Wiring Diagram 460 3 60...

Page 76: ...1 Nov 2021 Page 76 001200MAN 09 Electrical Box Layout R 25 75 460 3 60...

Page 77: ...1 Nov 2021 Page 77 001200MAN 09 Electrical Box Layout R 80 460 3 60...

Page 78: ...1 Nov 2021 Page 78 001200MAN 09 Electrical Box Layout RH 25 75 460 3 60...

Page 79: ...1 Nov 2021 Page 79 001200MAN 09...

Page 80: ...1 Nov 2021 Page 80 001200MAN 09...

Page 81: ...1 Nov 2021 Page 81 001200MAN 09 Dimensions R 45 Left Return...

Page 82: ...1 Nov 2021 Page 82 001200MAN 09 Dimensions R 45 Right Return...

Page 83: ...1 Nov 2021 Page 83 001200MAN 09 Dimensions R 55 65 75 Left Return...

Page 84: ...1 Nov 2021 Page 84 001200MAN 09 Dimensions R 55 65 75 Right Return...

Page 85: ...1 Nov 2021 Page 85 001200MAN 09 Dimensions R 80 Left Return...

Page 86: ...1 Nov 2021 Page 86 001200MAN 09 Dimensions R 80 Right Return...

Page 87: ...1 Nov 2021 Page 87 001200MAN 09 Dimensions RH 45 Left Return...

Page 88: ...1 Nov 2021 Page 88 001200MAN 09 Dimensions RH 45 Right Return...

Page 89: ...1 Nov 2021 Page 89 001200MAN 09 Dimensions RH 55 65 75 Left Return...

Page 90: ...1 Nov 2021 Page 90 001200MAN 09 Dimensions RH 55 65 75 Right Return...

Page 91: ...iring or voltage conditions 7 Products subjected to accident misuse negligence abuse fire flood lightning unauthorized alteration misapplication contaminated or corrosive liquid or air supply operatio...

Reviews: