PLENUM HEATER TROUBLE SHOOTING
Fault
Possible Cause
Verification
Recommended Action
No 24VAC signal
from 1 to ground
at the plenum
heater control
connector
Faulty Plenum Heater
Relay in heat pump
24VAC is present across pin 1 and
pin 3 of the relay, 24VAC is present
from heat pump terminal strip I to
plenum heater ground, but not from
heat pump terminal strip 1 to plenum
heater ground.
Replace relay.
Fan not operating
See Fan/Blower Troubleshooting
section
Correct problem. Reset thermal
overload.
Faulty overload
Reset thermal overload
Replace if faulty.
Plenum heater
thermal overload
is tripped.
DOMESTIC HOT WATER (DESUPERHEATER) TROUBLE SHOOTING
Fault
Possible Cause
Verification
Recommended Action
Insufficient hot
water (tank
problem)
Thermostat on hot water
tank set too low; should
be set at 120°F to 140°F
Visually inspect the setting.
Adjust the setting.
Breaker tripped, or fuse
blown in electrical supply
to hot water tank
Check both line and load sides of
fuses. If switch is open determine
why (possible shorted element).
Correct problem, and replace
blown fuse or reset breaker.
Reset button tripped on
hot water tank
Check voltage at elements with
multimeter.
Push reset button.
DHW switch is turned off
Inspect switch, located on heat
pump cabinet post.
Turn switch on.
Blockage or restriction in
the water line or hot water
heat exchanger
Check water flow and power to
pump. Check water lines for
obstructions.
Remove obstruction in water
lines. Acid treat the domestic hot
water coil.
Faulty DHW cutout (failed
open)
Check contact operation. Should
close at 120°F and open at 140°F.
Replace DHW cutout if faulty.
Heat pump not running
enough hours to make
sufficient hot water
Note the amount of time the heat
pump runs in any given hour.
Temporarily turn up the tank
thermostats until colder weather
creates longer run cycles.
Water is too hot.
Faulty DHW cutout (failed
closed)
Check contact operation. Should
close at 120°F and open at 140°F.
Replace DHW cutout if faulty.
Thermostat on hot water
tank set too high; should
be set at 120°F to 140°F
Visually inspect the setting.
Adjust the setting.
Insufficient hot
water
(heat pump
problem)
Circulator pump seized or
motor failed
Use an amprobe to measure current
draw.
Replace if faulty.
Summary of Contents for R-45
Page 11: ...1 Nov 2021 Page 11 001200MAN 09...
Page 15: ...1 Nov 2021 Page 15 001200MAN 09...
Page 16: ...1 Nov 2021 Page 16 001200MAN 09...
Page 18: ...1 Nov 2021 Page 18 001200MAN 09...
Page 19: ...1 Nov 2021 Page 19 001200MAN 09...
Page 21: ...1 Nov 2021 Page 21 001200MAN 09...
Page 25: ...1 Nov 2021 Page 25 001200MAN 09...
Page 26: ...1 Nov 2021 Page 26 001200MAN 09...
Page 27: ...1 Nov 2021 Page 27 001200MAN 09...
Page 28: ...1 Nov 2021 Page 28 001200MAN 09...
Page 29: ...1 Nov 2021 Page 29 001200MAN 09...
Page 33: ...1 Nov 2021 Page 33 001200MAN 09...
Page 34: ...1 Nov 2021 Page 34 001200MAN 09...
Page 35: ...1 Nov 2021 Page 35 001200MAN 09...
Page 63: ...1 Nov 2021 Page 63 001200MAN 09 Wiring Diagram 208 230 1 60...
Page 64: ...1 Nov 2021 Page 64 001200MAN 09 Electrical Box Layout R 45 75 208 230 1 60...
Page 65: ...1 Nov 2021 Page 65 001200MAN 09 Electrical Box Layout R 80 208 230 1 60...
Page 66: ...1 Nov 2021 Page 66 001200MAN 09 Electrical Box Layout RH 45 75 208 230 1 60...
Page 67: ...1 Nov 2021 Page 67 001200MAN 09 Wiring Diagram 208 3 60...
Page 68: ...1 Nov 2021 Page 68 001200MAN 09 Electrical Box Layout R 45 75 208 3 60...
Page 69: ...1 Nov 2021 Page 69 001200MAN 09 Electrical Box Layout R 80 208 3 60...
Page 70: ...1 Nov 2021 Page 70 001200MAN 09 Electrical Box Layout RH 45 75 208 3 60...
Page 71: ...1 Nov 2021 Page 71 001200MAN 09 Wiring Diagram 265 277 1 60...
Page 72: ...1 Nov 2021 Page 72 001200MAN 09 Electrical Box Layout R 45 75 265 277 1 60...
Page 73: ...1 Nov 2021 Page 73 001200MAN 09 Electrical Box Layout R 80 265 277 1 60...
Page 74: ...1 Nov 2021 Page 74 001200MAN 09 Electrical Box Layout RH 45 75 265 277 1 60...
Page 75: ...1 Nov 2021 Page 75 001200MAN 09 Wiring Diagram 460 3 60...
Page 76: ...1 Nov 2021 Page 76 001200MAN 09 Electrical Box Layout R 25 75 460 3 60...
Page 77: ...1 Nov 2021 Page 77 001200MAN 09 Electrical Box Layout R 80 460 3 60...
Page 78: ...1 Nov 2021 Page 78 001200MAN 09 Electrical Box Layout RH 25 75 460 3 60...
Page 79: ...1 Nov 2021 Page 79 001200MAN 09...
Page 80: ...1 Nov 2021 Page 80 001200MAN 09...
Page 81: ...1 Nov 2021 Page 81 001200MAN 09 Dimensions R 45 Left Return...
Page 82: ...1 Nov 2021 Page 82 001200MAN 09 Dimensions R 45 Right Return...
Page 83: ...1 Nov 2021 Page 83 001200MAN 09 Dimensions R 55 65 75 Left Return...
Page 84: ...1 Nov 2021 Page 84 001200MAN 09 Dimensions R 55 65 75 Right Return...
Page 85: ...1 Nov 2021 Page 85 001200MAN 09 Dimensions R 80 Left Return...
Page 86: ...1 Nov 2021 Page 86 001200MAN 09 Dimensions R 80 Right Return...
Page 87: ...1 Nov 2021 Page 87 001200MAN 09 Dimensions RH 45 Left Return...
Page 88: ...1 Nov 2021 Page 88 001200MAN 09 Dimensions RH 45 Right Return...
Page 89: ...1 Nov 2021 Page 89 001200MAN 09 Dimensions RH 55 65 75 Left Return...
Page 90: ...1 Nov 2021 Page 90 001200MAN 09 Dimensions RH 55 65 75 Right Return...