A return well should be a minimum of
80 ft.
from the supply
well for residential applications. The water returned to the well
will not necessarily be pumped into the same aquifer, depend-
ing on underground conditions. The return well must be able to
supply at least the same quantity of water as the amount you
wish to inject into it, preferably much more, since injection ca-
pacity will tend to decrease over time due to clogging. It may be
necessary to place a pressure-tight cap on the well to keep the
return water from flowing out the top of the well. This cap is
commonly required since a certain amount of pressure may be
needed to force the return water back down the well in cases of
limited injectivity.
Water discharged by percolation will generally soak into
the ground within a distance of 50 to 100 ft. If suitable care is
taken to ensure that the drain pipe runs downhill and the end of
the pipe is protected by a bale of hay or spruce bows, the end of
the pipe will not freeze as the pipe will empty out when the heat
pump shuts off and the water valve closes. A screen should be
installed on the end of large discharge pipes, to prevent animals
from building nests inside during extended ’off’ periods and
causing a backflooding risk for open water drains.
When snow comes it will usually cover the entire process
much like a small spring. It is recommended that the pipe be
below the frost line when possible for maximum freeze protec-
tion.
When discharging into a river or stream, or above the sur-
face of a pond, the same guidelines should be followed as de-
scribed in the paragraph above for the percolation method.
When discharging the waste water below the surface of a
pond or lake, the discharge pipe should be placed below the
frost line to prevent the pipe from freezing. As opposed to the
percolation method, water will remain in the end of the pipe. It
is recommended that the surface of the pond be lower than the
installation location of the heat pump. This reduces the back
pressure generated by the weight of the water in the pond.
Water Valve
Water flow through the heat pump is turned on and off by a
water valve, which is controlled by a 24VAC signal from the
heat pump. It should be installed on the OUT pipe of the heat
pump, so that the heat exchanger remains full of water at all
times. There are two types of water valves available from Mari-
time Geothermal.
Most installations use a ‘Taco’ slow closing motorized ball
valve (EBV). This takes ~5 seconds to close, and avoids the
water hammer which can occur with faster acting valves. There
is also a more economical fasting acting ‘Rainbird’ solenoid
valve available, for applications where water hammer is not
expected. Both come with a wiring harness, which plugs into a
connector behind the pipe post of the heat pump. This both
allows the heat pump to properly control the valve, turning the
water flow on and off with the compressor, and also tells the
heat pump to select the higher low pressure safety control for
open loop operation (since there is no antifreeze present).
Water Flow Control
A flow restricting (‘Dole’) valve is highly recommended,
installed downstream of the water valve. This is a passive (non-
electrical) device which automatically varies the size of its rub-
ber orifice in order to restrict flow to its stamped gpm value, re-
gardless of water pressure. This is important in order to provide
some backpressure to the water system, which could otherwise
be too low for the comfort of people taking showers or otherwise
using the domestic water system. It also prevents excessively
Figure 2: Open Loop Accessories & Tools
Gauge adapter
for P/T port
P/T port
P/T adapters for
heat pump
(1” NPT to barb)
Taco EBV
Rainbird Solenoid Valve
Dole Valve
Water
Level
Sounder
Cumulative
Gallon
Meter
Summary of Contents for R-45
Page 11: ...1 Nov 2021 Page 11 001200MAN 09...
Page 15: ...1 Nov 2021 Page 15 001200MAN 09...
Page 16: ...1 Nov 2021 Page 16 001200MAN 09...
Page 18: ...1 Nov 2021 Page 18 001200MAN 09...
Page 19: ...1 Nov 2021 Page 19 001200MAN 09...
Page 21: ...1 Nov 2021 Page 21 001200MAN 09...
Page 25: ...1 Nov 2021 Page 25 001200MAN 09...
Page 26: ...1 Nov 2021 Page 26 001200MAN 09...
Page 27: ...1 Nov 2021 Page 27 001200MAN 09...
Page 28: ...1 Nov 2021 Page 28 001200MAN 09...
Page 29: ...1 Nov 2021 Page 29 001200MAN 09...
Page 33: ...1 Nov 2021 Page 33 001200MAN 09...
Page 34: ...1 Nov 2021 Page 34 001200MAN 09...
Page 35: ...1 Nov 2021 Page 35 001200MAN 09...
Page 63: ...1 Nov 2021 Page 63 001200MAN 09 Wiring Diagram 208 230 1 60...
Page 64: ...1 Nov 2021 Page 64 001200MAN 09 Electrical Box Layout R 45 75 208 230 1 60...
Page 65: ...1 Nov 2021 Page 65 001200MAN 09 Electrical Box Layout R 80 208 230 1 60...
Page 66: ...1 Nov 2021 Page 66 001200MAN 09 Electrical Box Layout RH 45 75 208 230 1 60...
Page 67: ...1 Nov 2021 Page 67 001200MAN 09 Wiring Diagram 208 3 60...
Page 68: ...1 Nov 2021 Page 68 001200MAN 09 Electrical Box Layout R 45 75 208 3 60...
Page 69: ...1 Nov 2021 Page 69 001200MAN 09 Electrical Box Layout R 80 208 3 60...
Page 70: ...1 Nov 2021 Page 70 001200MAN 09 Electrical Box Layout RH 45 75 208 3 60...
Page 71: ...1 Nov 2021 Page 71 001200MAN 09 Wiring Diagram 265 277 1 60...
Page 72: ...1 Nov 2021 Page 72 001200MAN 09 Electrical Box Layout R 45 75 265 277 1 60...
Page 73: ...1 Nov 2021 Page 73 001200MAN 09 Electrical Box Layout R 80 265 277 1 60...
Page 74: ...1 Nov 2021 Page 74 001200MAN 09 Electrical Box Layout RH 45 75 265 277 1 60...
Page 75: ...1 Nov 2021 Page 75 001200MAN 09 Wiring Diagram 460 3 60...
Page 76: ...1 Nov 2021 Page 76 001200MAN 09 Electrical Box Layout R 25 75 460 3 60...
Page 77: ...1 Nov 2021 Page 77 001200MAN 09 Electrical Box Layout R 80 460 3 60...
Page 78: ...1 Nov 2021 Page 78 001200MAN 09 Electrical Box Layout RH 25 75 460 3 60...
Page 79: ...1 Nov 2021 Page 79 001200MAN 09...
Page 80: ...1 Nov 2021 Page 80 001200MAN 09...
Page 81: ...1 Nov 2021 Page 81 001200MAN 09 Dimensions R 45 Left Return...
Page 82: ...1 Nov 2021 Page 82 001200MAN 09 Dimensions R 45 Right Return...
Page 83: ...1 Nov 2021 Page 83 001200MAN 09 Dimensions R 55 65 75 Left Return...
Page 84: ...1 Nov 2021 Page 84 001200MAN 09 Dimensions R 55 65 75 Right Return...
Page 85: ...1 Nov 2021 Page 85 001200MAN 09 Dimensions R 80 Left Return...
Page 86: ...1 Nov 2021 Page 86 001200MAN 09 Dimensions R 80 Right Return...
Page 87: ...1 Nov 2021 Page 87 001200MAN 09 Dimensions RH 45 Left Return...
Page 88: ...1 Nov 2021 Page 88 001200MAN 09 Dimensions RH 45 Right Return...
Page 89: ...1 Nov 2021 Page 89 001200MAN 09 Dimensions RH 55 65 75 Left Return...
Page 90: ...1 Nov 2021 Page 90 001200MAN 09 Dimensions RH 55 65 75 Right Return...