Nordic R-45 Installation And Service Manual Download Page 20

1-Nov-2021 

Page   20 

001200MAN-09 

 

Ductwork 

Zoning

 

Zoning can be done with heat pumps that have 2-stage 

compressors, but only to a limited extent.  It is recommended 

that no zone be less than 1/3 the total area, to avoid problems of 

high airflow and noise through one zone or safety control trips 

due to capacity mismatch between heat pump and zones.  

 

The airflow can be reduced by 15% by making a dry con-

tact across 

AR1

 and 

AR2

 on the thermostat terminal strip in the 

heat pump’s electrical box, as show in 

Wiring 

chapter.   

 

When only one zone of 50% or less is calling for heating or 

cooling, the compressor should be limited to 

stage 1 

operation 

by the zone controller by sending only a 

Y1 

(without Y2) control 

signal.  Stage 1 corresponds to ~67%  compressor capacity and 

~80% airflow. 

 

Refer to airflow tables in the 

Model Specific Information

 

chapter for airflows with the various reductions. 

 

Duct Systems - General 

 

Ductwork layout for a heat pump will differ from traditional 

hot air furnace design in the number of leads and size of main 

trunks required. Air temperature leaving the heat pump is 

normally 

95º -105ºF (35-40ºC)

, much cooler than that of a 

conventional fossil fuel furnace. To compensate for this, larger 

volumes of lower temperature air must be moved and 

consequently duct sizing must be able to accommodate the 

greater airflow without creating a high static pressure or high 

velocity at the floor diffusers.  

 

A duct system capable of supplying the required airflow is 

of utmost importance.  Maritime Geothermal Ltd. recommends 

that the external static pressure from the duct system be kept 

below 0.2 inches of water total.  In some instances the number 

of floor diffusers will actually double when compared to the 

number that would be used for a hot air oil-fired furnace.  Refer 

to following tables. 

 

 

1.  Generally allow 

100 cfm 

for each floor grill. 

2.  All leads to the grills should be 6'' in diameter (28sq.in. each). 

3.  The main hot air trunks should be at least 75% of the square      

     surface area of leads being fed at any given point. 

4.  Return air grills should have a minimum of the same total   

     square surface area as the total of the supply grills.  

5.  The square surface area of the return trunks should equal   

     the square surface area of the grills being handled at any   

     given point along the trunk. 

 

It is 

VERY IMPORTANT

 

that all turns in both the supply 

trunks and the return trunks be made with 

TURNING RADII

. Air 

act like a fluid and, just like water, pressure drop is increased 

when air is forced to change direction rapidly around a sharp or 

irregular corner. 

 

It is recommended that flexible collars be used to connect 

the main trunks to the heat pump.  This helps prevent any vibra-

tions from travelling down the ductwork.  If a plenum heater is 

installed, the collar should be at least 12” away from the heater 

elements. 

 

If desired, the first 5-10 feet of the main supply trunks can  

be insulated internally with acoustical duct insulation to further 

inhibit any noise from the unit from travelling down the ductwork.  

If a plenum heater is installed, insulation should not be placed 

within 12” of the heater elements. 

Duct Systems - Grill Layout 

    

 

Most forced air heating systems in homes have the floor 

grills placed around the perimeter of the room.   Supply grills 

should be placed under a window when possible to help prevent 

condensation on the window.  As mentioned in the previous sub

-section, supply grill leads should be 6'' in diameter (28 square 

inches each) to allow 

100 cfm

 of airflow. 

 

In a typical new construction, there should be one supply 

grill for every 100 square feet of area in the room.  When rooms 

require more than one grill, they should be placed in a manner 

that promotes even heat distribution, such as one at each end of  

the room.  It is always a good idea to place a damper in each 

grill supply or place adjustable grills so that any imbalances in 

the heat distribution can be corrected. 

 

The total number of supply grills available is based on the 

heat pump nominal airflow.  The table

 

shows the number of 

grills recommended per heat pump size. 

Return grills should be mounted on the floor.  At minimum 

they should be the same size as the supply grill, 

it is highly rec-

ommended that they be 25% to 50% larger than the total 

supply.

 They should be placed opposite the supply grills 

when possible to ensure distribution across the room.  For 

rooms requiring more than one supply grill, it may be possible to 

use one larger return grill if it can be centrally positioned oppo-

site of the supply grills, however it is preferred to have one re-

turn for each supply to optimize heat distribution across the 

room. 

 

Thermostat Location 

 

Most homes are a single ducted air zone with one thermo-

stat.  The thermostat should be centrally located within the 

home, typically on the main floor.  It should be placed away from 

any supply grills, and should not be positioned directly above a 

return grill.  Most installations have the thermostat located in a 

hallway, or on the inner wall of the living room.  It should be not-

ed that most  homes do not have any supply ducts in the hall-

way.  This can lead to a temperature lag at the thermostat if 

there is very little air movement in the hallway, causing the 

home to be warmer than indicated by the thermostat. 

 

Plenum Heater

 

The plenum heater will be usually installed inside the heat 

pump, as described in the 

Installation Basics 

section.  If the 

blower is installed in the side discharge position, the plenum 

heater will be installed in the discharge ductwork outside the 

unit, at least 12” away from any flexible duct collars.  There is an 

accessory plenum heater with a wider cage profile available that 

is more suitable for duct installation.   

TABLE 10 - Heat Pump Size vs.  Hot Air Grills 

Model

 

Size (tons) 

# of Grills (@100 cfm)

 

45 

12 

55 

15 

65 

19 

75 

21 

80 

6.5 

23 

Summary of Contents for R-45

Page 1: ...l Ltd P O Box 2555 170 Plantation Road Petitcodiac NB E4Z 6H4 506 756 8135 R RH Series Liquid to Air Geothermal Heat Pumps Two Stage R410a Model Sizes 45 80 info nordicghp com www nordicghp com 001200...

Page 2: ...is performed CAUTION Venting refrigerant to atmosphere is illegal A proper refrigerant recovery system must be employed whenever repairs require removal of refrigerant from the heat pump Series R Rev...

Page 3: ...C Y Z SDELF SDERF 12 13 14 15 2 T 4 T 6 S 7 T R 80 HACW P 1 2 3 4 7 S C Y Z SDELF SDERF 10 11 RH 45 HACW P 1 2 3 4 6 7 T C Y Z SDELF SDERF 08 RH 55 HACW P 1 2 3 4 6 7 T C Y Z SDELF SDERF 08 RH 65 HACW...

Page 4: ...31 Water Flow Control 31 Submersible Pump Selection 32 Table of Contents Stage 1 vs 2 on Open Loop 32 Plumbing the Heat Pump 32 Pipe Insulation 32 000907CDG Typical Open Loop Installation 33 001822CDG...

Page 5: ...onfiguration 25 000609INF Typical Vertical Ground Loop Configuration 26 000906CDG Geo Flo Circulator Pump Module Installation 27 001823CDG Dual Flow Circulator Pump Module Installation for 2 Stage Hea...

Page 6: ...ns A single thermo static expansion valve TXV regulates superheat The cabinet is constructed from powder coated galvanized sheet metal 1 Heating Mode In heating mode the heat pump heats warm air in a...

Page 7: ...slightly exceeds the calculated heat load Some background on Standard Capacity Ratings closed ground loops are normally designed to reach a minimum tem perature of just below freezing at the end of t...

Page 8: ...RCHASED Sample Bill of Materials Open Loop Installations FROM MARITIME GEOTHERMAL R RH SERIES HEAT PUMP L OR R RETURN PLENUM HEATER __kW THERMOSTAT WIFI OR STD P T PORTS AND HOSE ADAPTERS 2 DOLE VALVE...

Page 9: ...at step 2 for the access panel with the blower mounted in it Set the assembly on the floor 5 Disconnect the plenum heater extension from the blower housing and from the access panel 6 Mount the blower...

Page 10: ...is mounted inside heat pump cabinet See diagram on following page Remove the screws from the cover plate remove the cover plate and place the plenum heater in the cutout Slide it up and secure the bot...

Page 11: ...1 Nov 2021 Page 11 001200MAN 09...

Page 12: ...at pump has provisions for connecting the circulator pump module so that the pumps will be turned on whenever the compressor operates Connect the circulator pump module to the appropriate two terminal...

Page 13: ...Cooling Mode reversing valve Y2 Heat Pump Stage 2 not used for single stage units AR1 Airflow Reduction AR2 Airflow Reduction CP I Plenum Heater dry contact Connect to C or I in plenum heater 1 Plenum...

Page 14: ...flow sensor located in the drip tray and the voltage of the 24vac transformer A fault will occur if a conden sate overflow is detected or a low voltage condition electricity grid brownout is detected...

Page 15: ...1 Nov 2021 Page 15 001200MAN 09...

Page 16: ...1 Nov 2021 Page 16 001200MAN 09...

Page 17: ...es the possibility of reverse heating of the refrigerant gas under low condensing temperature operating conditions WARNING USE ONLY COPPER LINES TO CONNECT THE DESUPERHEATER TEMPERA TURES CAN BE 200 F...

Page 18: ...1 Nov 2021 Page 18 001200MAN 09...

Page 19: ...1 Nov 2021 Page 19 001200MAN 09...

Page 20: ...e heater elements If desired the first 5 10 feet of the main supply trunks can be insulated internally with acoustical duct insulation to further inhibit any noise from the unit from travelling down t...

Page 21: ...1 Nov 2021 Page 21 001200MAN 09...

Page 22: ...17 16 5 x 16 5 22 944 2250 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 22 1062 2600 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 24 1227 2900 22 12 x 36 14 x 30 16 x 26 18 x 23 2...

Page 23: ...pump module that can deliver the flow required for the unit at the calculated total pressure drop should be selected Refer to the Model Specific Information section for unit flow re quirements Loop pr...

Page 24: ...k closed cell pipe insulation to prevent condensa tion and dripping onto floors or walls Although many different antifreeze solutions have been employed in geothermal systems the alcohols such as meth...

Page 25: ...1 Nov 2021 Page 25 001200MAN 09...

Page 26: ...1 Nov 2021 Page 26 001200MAN 09...

Page 27: ...1 Nov 2021 Page 27 001200MAN 09...

Page 28: ...1 Nov 2021 Page 28 001200MAN 09...

Page 29: ...1 Nov 2021 Page 29 001200MAN 09...

Page 30: ...or significant Ammonia 0 5 ppm or H2S 0 2 ppm is present the use of an open loop system should be reconsidered Water Discharge Methods Water disposal methods vary from area to area However some consi...

Page 31: ...the pipe from freezing As opposed to the percolation method water will remain in the end of the pipe It is recommended that the surface of the pond be lower than the installation location of the heat...

Page 32: ...ble pump will proba bly negate the COP benefit of running the heat pump on stage 1 In this case it is recommended to jumper Y1 and Y2 together at the heat pump terminal strip in order to satisfy the h...

Page 33: ...1 Nov 2021 Page 33 001200MAN 09...

Page 34: ...1 Nov 2021 Page 34 001200MAN 09...

Page 35: ...1 Nov 2021 Page 35 001200MAN 09...

Page 36: ...freeze and the mixture value on the startup sheet circle Vol or Weight 4 Record the static loop pressure on the startup sheet Outdoor Loop Open Loop 1 Verify there are no leaks in the connections to t...

Page 37: ...unit Connect the brown wire with the blue insulated terminal to the compressor contactor as shown in the electrical box diagram Turn the DHW Switch in the unit post on Turn the power to the unit on 6...

Page 38: ...orrect and securely fastened Circuit breaker or fuse size and wire gauge for Heat Pump A Ga Circuit breaker or fuse size wire gauge and Plenum Heater size A Ga kW Low voltage connections are correct a...

Page 39: ...warm water open loop systems unusual Coaxial Heat Exchanger Flushing Procedure Open Loop 1 Isolate the heat exchanger by closing the valves in the IN and OUT ports to the heat exchanger 2 Blow out the...

Page 40: ...urs 3 hours recommended 5 Disconnect the purge cart and dispose of the solution RYDLYME is non toxic and biodegradable and as such can be poured down a drain Clean the purge cart thoroughly 6 Connect...

Page 41: ...urn the power off wait 10 seconds and turn the power back on Set the thermostat to call for heating or cooling depending on the season STEP 3 If a 24VAC signal does not appear across Y1 and C of the t...

Page 42: ...th compressor on See Low Discharge Pressure in Heating Mode Cooling Mode Troubleshooting section Faulty low pressure con trol failed open very unlikely For this test there must be a signal present on...

Page 43: ...re compressor overload has had a chance to reset If compressor is hot this may take several hours Replace the compressor Burned out motor shorted windings Remove wires from compressor Resistance betwe...

Page 44: ...of the flow restriction and correct it Verify pumps are working and sized correctly for ground loop systems Verify well pump and water valve is working for ground water sys tems Entering liquid temper...

Page 45: ...osits Backflush the coaxial exchanger with a calcium removing cleaning solution OPERATION TROUBLESHOOTING HEATING MODE Fault Possible Cause Verification Recommended Action High Suction Pressure may ap...

Page 46: ...Low Suction Pressure Low airflow See Fan Troubleshooting section Note low airflow will cause the air coil to ice up once the suction drops below 90PSIG Correct the problem TXV stuck almost closed or...

Page 47: ...the following at the fan con trol signal harness insert probes in connector where wire is inserted do not unplug the connector Recirculation grey pin 15 Stage 1 yellow pin 6 Stage 2 yellow black pin1...

Page 48: ...heck the thermostat manual Faulty thermostat Thermostat doesn t indicate a call for auxiliary or emergency when it should Or thermostat indicates aux iliary or emergency but no 24VAC signal present ac...

Page 49: ...why possible shorted element Correct problem and replace blown fuse or reset breaker Reset button tripped on hot water tank Check voltage at elements with multimeter Push reset button DHW switch is t...

Page 50: ...rocedures to prevent soot buildup inside the pipes It is recommended to replace the liquid line filter dryer any time the refrigeration system has been exposed to the atmosphere Place a wet rag around...

Page 51: ...soot buildup inside the pipes 4 Vacuum the unit as per above procedure 5 If there was a compressor burnout a Charge the unit with new refrigerant and operate it for continuously for 2 hours Pump down...

Page 52: ...Adequate antifreeze concentration required Heating Maximum ELT 80 27 Reduce flow above this temperature Cooling Minimum ELT 41 5 Flow reduction may be required Cooling Maximum ELT 110 43 INDOOR air d...

Page 53: ...6 16 1 01 Stage 1 1660 783 2 305 54 300 15 9 7 2 24 4 Stage 2 2100 991 3 710 69 800 20 5 5 7 19 4 R 80 6 17 1 07 Stage 1 2400 1133 4 130 86 500 25 4 5 8 19 6 Table 19 Standard Capacity Ratings Ground...

Page 54: ...4 3 30 4 6 32 5 5 38 7 2 50 12 0 76 5 2 36 5 5 38 6 6 45 8 7 60 13 0 82 5 9 41 6 2 43 7 4 51 9 7 67 R RH 45 14 0 88 6 7 46 7 0 48 8 6 59 11 3 78 15 0 95 8 0 55 8 2 57 9 5 65 12 5 86 6 0 38 1 1 7 6 1 2...

Page 55: ...1 0 6 9 1 3 9 0 8 0 50 1 2 8 3 1 3 9 0 1 3 9 0 1 7 12 9 0 57 1 5 10 1 6 11 1 6 11 2 1 14 10 0 63 1 8 12 1 9 13 2 1 14 2 8 19 11 0 69 2 1 14 2 3 16 2 4 17 3 2 22 12 0 76 2 4 17 2 6 18 2 9 20 3 8 26 13...

Page 56: ...7 50 10 60 7 0 34 965 11 1 2 770 116 1 200 103 38 0 44 185 4 67 Fan W 179 179 179 179 179 179 179 179 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat...

Page 57: ...0 12 59 8 6 51 663 14 1 3 247 112 1 500 108 40 4 62 471 5 64 Fan W 185 185 185 185 185 185 185 185 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej...

Page 58: ...14 58 8 7 61 001 18 3 4 353 113 1 900 107 38 6 75 456 5 08 Fan W 300 300 300 300 300 300 300 300 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C Heat Rej...

Page 59: ...5 69 50 16 60 8 9 71 411 21 1 4 951 113 2 100 109 40 6 87 893 5 20 Fan W 410 410 410 410 410 410 410 410 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond Temp Flow L s LLT C Delta T C He...

Page 60: ...00 106 4 38 4 87 458 4 64 66 0 50 16 8 57 0 9 0 75 450 26 1 5 594 113 2 400 109 3 41 3 94 236 4 94 Fan W 661 661 661 661 661 661 661 661 HEATING COOLING OUTDOOR LOOP 15 Methanol ELECTRICAL ELT C Cond...

Page 61: ...230 581 1000 472 850 401 75 1974 932 1678 792 1560 736 1326 626 1105 522 940 443 80 2256 1065 1918 905 N A N A N A N A 1263 596 1074 507 Table 25 HIGH Airflow 6 Model STAGE 2 STAGE 1 FAN ONLY Recircul...

Page 62: ...required if connecting 115VAC circulators to the unit R RH 55 1 208 230 1 60 187 253 20 4 122 4 0 5 0 30 2 35 3 50 8 2 2 208 3 60 187 229 14 0 83 4 0 5 0 23 8 27 3 40 8 3 3 265 277 1 60 226 304 16 0 1...

Page 63: ...1 Nov 2021 Page 63 001200MAN 09 Wiring Diagram 208 230 1 60...

Page 64: ...1 Nov 2021 Page 64 001200MAN 09 Electrical Box Layout R 45 75 208 230 1 60...

Page 65: ...1 Nov 2021 Page 65 001200MAN 09 Electrical Box Layout R 80 208 230 1 60...

Page 66: ...1 Nov 2021 Page 66 001200MAN 09 Electrical Box Layout RH 45 75 208 230 1 60...

Page 67: ...1 Nov 2021 Page 67 001200MAN 09 Wiring Diagram 208 3 60...

Page 68: ...1 Nov 2021 Page 68 001200MAN 09 Electrical Box Layout R 45 75 208 3 60...

Page 69: ...1 Nov 2021 Page 69 001200MAN 09 Electrical Box Layout R 80 208 3 60...

Page 70: ...1 Nov 2021 Page 70 001200MAN 09 Electrical Box Layout RH 45 75 208 3 60...

Page 71: ...1 Nov 2021 Page 71 001200MAN 09 Wiring Diagram 265 277 1 60...

Page 72: ...1 Nov 2021 Page 72 001200MAN 09 Electrical Box Layout R 45 75 265 277 1 60...

Page 73: ...1 Nov 2021 Page 73 001200MAN 09 Electrical Box Layout R 80 265 277 1 60...

Page 74: ...1 Nov 2021 Page 74 001200MAN 09 Electrical Box Layout RH 45 75 265 277 1 60...

Page 75: ...1 Nov 2021 Page 75 001200MAN 09 Wiring Diagram 460 3 60...

Page 76: ...1 Nov 2021 Page 76 001200MAN 09 Electrical Box Layout R 25 75 460 3 60...

Page 77: ...1 Nov 2021 Page 77 001200MAN 09 Electrical Box Layout R 80 460 3 60...

Page 78: ...1 Nov 2021 Page 78 001200MAN 09 Electrical Box Layout RH 25 75 460 3 60...

Page 79: ...1 Nov 2021 Page 79 001200MAN 09...

Page 80: ...1 Nov 2021 Page 80 001200MAN 09...

Page 81: ...1 Nov 2021 Page 81 001200MAN 09 Dimensions R 45 Left Return...

Page 82: ...1 Nov 2021 Page 82 001200MAN 09 Dimensions R 45 Right Return...

Page 83: ...1 Nov 2021 Page 83 001200MAN 09 Dimensions R 55 65 75 Left Return...

Page 84: ...1 Nov 2021 Page 84 001200MAN 09 Dimensions R 55 65 75 Right Return...

Page 85: ...1 Nov 2021 Page 85 001200MAN 09 Dimensions R 80 Left Return...

Page 86: ...1 Nov 2021 Page 86 001200MAN 09 Dimensions R 80 Right Return...

Page 87: ...1 Nov 2021 Page 87 001200MAN 09 Dimensions RH 45 Left Return...

Page 88: ...1 Nov 2021 Page 88 001200MAN 09 Dimensions RH 45 Right Return...

Page 89: ...1 Nov 2021 Page 89 001200MAN 09 Dimensions RH 55 65 75 Left Return...

Page 90: ...1 Nov 2021 Page 90 001200MAN 09 Dimensions RH 55 65 75 Right Return...

Page 91: ...iring or voltage conditions 7 Products subjected to accident misuse negligence abuse fire flood lightning unauthorized alteration misapplication contaminated or corrosive liquid or air supply operatio...

Reviews: