NOARK Ex9EMS 1P 2M - 19
6008
L2 Total active energy*
03
2
kWh
Float ABCD
600A
L3 Total active energy*
03
2
kWh
Float ABCD
600C
Forward active energy
03
2
kWh
Float ABCD
600E
T1 Forward active energy
03
2
kWh
Float ABCD
6010
T2 Forward active energy
03
2
kWh
Float ABCD
6012
L1 Forward active energy*
03
2
kWh
Float ABCD
6014
L2 Forward active energy*
03
2
kWh
Float ABCD
6016
L3 Forward active energy*
03
2
kWh
Float ABCD
6018
Reverse active energy
03
2
kWh
Float ABCD
601A
T1 Reverse active energy
03
2
kWh
Float ABCD
601C
T2 Reverse Active Energy
03
2
kWh
Float ABCD
601E
L1 Reverse active energy*
03
2
kWh
Float ABCD
6020
L2 Reverse active energy*
03
2
kWh
Float ABCD
6022
L3 Reverse active energy*
03
2
kWh
Float ABCD
6024
Total reactive energy
03
2
kvarh
Float ABCD
6026
T1 Total reactive energy
03
2
kvarh
Float ABCD
6028
T2 Total reactive energy
03
2
kvarh
Float ABCD
602A
L1 Total reactive energy*
03
2
kvarh
Float ABCD
602C
L2 Total reactive energy*
03
2
kvarh
Float ABCD
602E
L3 Total reactive energy*
03
2
kvarh
Float ABCD
6030
Forward reactive energy
03
2
kvarh
Float ABCD
6032
T1 Forward reactive energy
03
2
kvarh
Float ABCD
6034
T2 Forward reactive energy
03
2
kvarh
Float ABCD
6036
L1 Forward reactive energy*
03
2
kvarh
Float ABCD
6038
L2 Forward reactive energy*
03
2
kvarh
Float ABCD
603A
L3 Forward reactive energy*
03
2
kvarh
Float ABCD
603C
Reverse reactive energy
03
2
kvarh
Float ABCD
603E
T1 Reverse reactive energy
03
2
kvarh
Float ABCD
6040
T2 Reverse reactive energy
03
2
kvarh
Float ABCD
6042
L1 Reverse reactive energy*
03
2
kvarh
Float ABCD
6044
L2 Reverse reactive energy*
03
2
kvarh
Float ABCD
6046
L3 Reverse reactive energy*
03
2
kvarh
Float ABCD
6048
Tariff
03
1
-
Signed
6049
Resettable day counter
03
2
kWh
Float ABCD
Write
Reg. address Content
Function code Register length Unit
Data type
4003
Modbus ID
06
1
-
Signed
Command:
4004
Baud rate
06
1
-
Signed
Command:
400D
S0 output rate
10
2
imp/kWh Float ABCD
Command:
400F
Combination code
06
1
-
Signed
Command:
4010
LCD cycle time
06
1
sec.
HEX
Command:
4011
Parity setting
06
1
-
Signed
Command:
4016
Power down counter
06
1
-
Signed
Command:
6048
Tariff
06
1
-
Signed
Command:
6049
Resettable day counter
06
1
kWh
Float ABCD
Command:
*
Ex9EMS 3P 4
M only
01 10 6049 0002 04 0000 0000
Reset to 0
01 06 4010 0025 (new time: 25 sec.)
01~30
01: even - 02: none - 03: odd
01 06 4016 0000
Reset to 0
01 06 6048 0002 (new tariff: 2)
01: T1 - 02: T2 - 11: T1 not saved -
12: T2 not saved
01 06 4011 0002 (new parity: none)
01 06 400F 000A (new code: 10 F-R)
01, 04, 05, 06, 09, 10,
11*
01 10 400D 0002 04 41 20 00 00 (new S0: 10)
01 06 4003 000A (new ID: 10)
01~247 - 01 default - 00 broadcast
01 06 4004 25 80 (new Baudrate: 9600)
10.000 - 2.000 - 1.000 - 100 - 10 - 1 - 0,1
- 0,01
300* - 600*
- 1200 - 4800 - 9600