5.8 Backlight
The meter is equipped with a blue backlight. The backlight can be set to always on, off or button mode.
5.8.1 Change the backlight setting
•
Scroll with the buttons to Program mode 2.
•
Hold the right button for 3 seconds to enter the menu.
•
Scroll to LCD page Backlight setting (bACK xx).
•
Hold the right button for 5 seconds to enter program mode.
•
The value starts blinking: select button/on/off.
•
Confirm the new setting by holding both buttons for 3 seconds.
•
The LCD will show OK when the setting is confirmed.
5.9 Resettable day counter
The meter is equipped with a day counter for consumed energy. This is the energy forward calculated and can be reset to zero
by the user.
5.9.1 How to reset the day counter back to 0
•
Scroll to register Resettable kWh in the main menu.
•
Hold the right button for 3 seconds to enter the menu.
•
The value starts blinking: hold the right button for 5 seconds to reset.
•
The LCD will show OK when the value is reset.
5.10 S0 output rate
The energy meter is equipped with two pulse outputs (forward and reverse) which are optically isolated from the
inside circuit. It generates pulses in proportion to the measured consumption for purpose of remote reading or accuracy tes-
ting. The pulse output is a polarity dependent, open-collector transistor output requiring an external voltage source for correct
operation. For this external voltage source, the voltage (Ui) should be lower than 27V DC. The maximum switching current
(Imax) is 100mA. To connect the impulse output, connect 5-27V DC to connector 18/20 (collector), and the signal wire (S) to
connector 19/21 (emitter).
5.10.1 How to change the S0 output rate
•
Scroll with the buttons to Program mode 3.
•
Hold the right button for 3 seconds to enter the menu.
•
Enter the 4 digit password: scroll with the buttons and select each digit 0-9, hold the right button for 3 seconds to
confirm each digit.
•
Scroll to LCD page S0 output (S0 xxxxxx).
•
Hold the right button for 5 seconds to enter program mode.
•
The value starts blinking: select 10.000/2.000/1.000/100/10/1/0,1/0,01.
•
Confirm the new setting by holding both buttons for 3 seconds.
•
The LCD will show OK when the setting is confirmed.
NOARK Ex9EMS 1P 2M - 9