Bypass enable/disable when UPS is off
Enable or disable Bypass function.
You may choose the following two
options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
08:
Bypass voltage range setting
Set the acceptable high voltage point
and acceptable low voltage point for
Bypass mode by pressing the Down
key or Up key.
HS:
Bypass high voltage point
For 200/208/220/230/240 VAC
models:
230-264: setting the high voltage
point in parameter 3 from 230Vac to
264Vac. (Default: 264Vac)
LS:
Bypass low voltage point
For 200/208/220/230/240 VAC
models:
170-220: setting the low voltage
point in parameter 3 from 170Vac to
220Vac (Default: 170Vac)
09:
Bypass frequency range setting
Set the acceptable high frequency
point and acceptable low frequency
point for Bypass mode by pressing the
Down key or Up key.
HS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high
loss point from 51Hz to 55HZ (De
-
fault: 53.0Hz)
LS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low
loss point from 45Hz to 49HZ (De
-
fault: 47.0Hz)
10:
Programmable outlets enable/disable
Enable or disable the Programmable
outlets function. You may choose the
following two options:
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable
(Default)
d 1 5
0 7
LOAD
BATTERY
INPUT
INPUT
INPUT
Hz
Hz
Hz
H S
5 3 0
4 7 0
0 9
H S
L S
LOAD
LOAD
LOAD
BATTERY
BATTERY
BATTERY
d 1 5
1 0
LOAD
BATTERY
INPUT
V
H S
0 8
LOAD
BATTERY
INPUT
V
2 6 4
H 5
LOAD
BATTERY
INPUT
V
1 7 0
L 5
LOAD
BATTERY