Battery capacity(AH)
Total charging
current (A)
7~20
2
20~40
4
40~60
6
60~80
8
80~100
10
100~150
12
NOTE:
If you connect Battery Pack 2U for
Balder 1500 (PWUP-BP06PBA-AZ01B) to
Balder 1500 you should set maximum charger
current to 4A.
If you connect Battery Pack 2U for Balder 3000
(PWUP-BP12PBA-AZ01B) to Balder 3000 you
should set maximum charger current to 4A.
14:
Charger Boost voltage setting
Cbu 236
Vdc
Parameter 2:
Set up the charger boost
voltage.
2.25-2.40:
setting the charger boost voltage
from 2.25 V/cell to 2.40V/cell. (Default:
2.36V/cell)
15:
Charger Float voltage setting
CFu 228
Vdc
Parameter 2:
Set up the charger float
voltage.
2.20-2.33:
setting the charger float voltage
from 2.20 V/cell to 2.33V/cell. (Default:
2.28V/cell)
NOTE:
Parameters 14 and 15 should be set
based on batteries specifications.
16:
EPO logic setting
EPO AO
Parameter 2:
Set up the EPO function
control logic.
AO:
Active Open (Default). When AO is
selected as EPO logic, it will activate EPO
function with Pin 1 and Pin 2 in open status.
AC:
Active Close. When AC is selected as
EPO logic, it will activate EPO function with
Pin 1 and Pin 2 in close status.
17:
External output isolation transformer connection
dI S
Parameter 2:
Allow or disallow external
output isolation transformer connection.
ENA:
If selected, it’s allowed to connect to
an external output isolation transformer.
DIS:
If selected, it’s not allowed to connect
to external output isolation transformer.
(Default)
18:
Display setting for autonomy time
Vac
Parameter 2:
Set up the display setting for
autonomy time
EAT:
If EAT is selected, it will display the
remaining autonomy time. (Default)
RAT:
If RAT is selected, it will show
accumulated autonomy time so far.
19:
Acceptable input voltage range setting
HLS
INPUT
3 00
Vac
Parameter 2:
Set the acceptable high
voltage point and acceptable low voltage
point for input voltage range by pressing the
Down key or Up key.
HLS:
Input high voltage point
280/290/300: setting the high voltage point
in parameter 2. (Default: 300Vac)
LLS:
Bypass low voltage point
110/120/130/140/150/160: setting the
low voltage point in parameter 2. (Default:
110Vac)
00:
Exit setting
ESC
Exit the setting mode.