TECHNICAL SPECIFICATION
Size:
215 x 205 x 45 mm
Degree of protection:
IP30
Weight:
2.1 kg
Supply Voltage:
230 V ˜ 50 Hz
Rated Insulation Voltage:
440 V AC
Conditional Short Circuit current: I
cf
= 1.5 kA
I
2
t (fuse rating)
300 A
2
s per channel
(Triac rating)
128 A
2
s per channel
Controlled supply:
230 V ˜ 50 Hz
Input Connections (mains):
Terminals for 16 mm
2
copper cable
(control):
3.5 mm pitch terminal blocks
Earthing system:
TT or TN-C-S
Analogue input impedance:
44 k
W
Control voltage:
0 V fully off, +10 V fully on
Maximum load per channel:
10 A or 2.3 kVA @ 230 V AC
(2.3kVA corresponds to a resistive load of 2300 Watts or an
inductive load of approximately 1750 Watts, depending on power
factor.)
Output Connections:
Terminals for 3.5mm copper cable
Maximum total load:
9.2 kVA @ 230V AC
Fuses:
F10A HBC to IEC127
Part code:
F128GD
(HBC means ‘high breaking capacity’ - a HBC fuse has a ceramic
case.)
Triacs:
16 Amp 600 Volt isolated tab.
Type:
BTA16 600BW
Part code:
F950AJ
Page 10