2300 W load may be connected to all four channels provided that
the unit is operated so that all four channels are not switched on
together at full power.
•
For a 32 A supply
, the maximum total load is 7360 W which can
be made up of: either: 1840 W watts on each of the four channels
or: different loads on each channel so that the total does not exceed
7360 W (but not more than 2300 W on any one channel) or:
2300 W load may be connected to all four channels provided that
the unit is operated so that all four channels are not switched on
together at full power. For high-inrush loads (Halogen lamps,
motors, transformer operated devices) the outputs should be de-
rated to 1150 W per channel for the most severe inrush loads.
OUTPUTS
Connect the Lives from the loads to the terminal blocks
numbered 1, 2, 3 and 4 and labelled
L.
Connect the Neutrals from the loads to the terminal blocks
numbered 1, 2, 3 and 4 and labelled
N.
Connect the Earths from the loads to the brass terminal block
labelled with the earth symbol.