36 pmg511en21p01
Note: Ignores the MV of the ON / OFF control or the PID control and sends a control value based on the defined MV.
5.10.4.2 Stopping the Alarm Output
[PAR5 → StAL]
Enable or disable the alarm output when the control stopped. Default setting: CONT.
Setting
Description
OFF
The alarm stops under all conditions.
(However, returning to ‘Normal’ mode will reset the alarm output to the previous state after
the alarm latch or alarm latch and standby stop.)
CONT
The alarm output continues regardless of the control.
5.10.5 Multi SV
The Multi
SV
feature allows users to configure multiple SVs and save all settings from SV0 to SV1. Users can
change the SV-N or select the desired
SV
using the external digital input terminal
(digital input, DI-1)
function.
This feature supports up to four SVs that can be configured independently.
5.10.5.1 The Number of Multi SVs
[PAR5 → MtSV]
This parameter sets the number of Multi SVs
(1 = SV–0/2 = SV–0, SV–1)
. Default: 1.
Note: This feature is not available for all models. If the digital input (DI-1) function is set to Multi SV [MtSV], the Multi SV
number will not change by pressing the button or communicating.
5.10.5.2 Selecting the Multi SV Number
[PAR1 → SV-N]
Select the
SV
to control. Default setting: SV-0.
Note: The number range (SV number) assigned to each SV varies depending on the setting of Multi SVs [MtSV].
5.10.5.3 Multi SV Settings
[PAR1 → SV-0/ SV-1]
Select the value of each
SV
for the Multi SV. Default value: 0. The unit is °C / °F.
5.10.6 Digital Input
5.10.6.1 Digital Input Terminal Settings
[PAR5 → DI-1]
If an external signal source is connected to a digital input terminal, one of the following functions can be set.
Default setting: OFF.
Setting
Description
OFF
Not in use
STOP
Run / Stop
AlRE
Deactivate alarm output
MAN
Select automatic / manual control
MtSV
Multi SV selection
If the DI-1 is set to Multi
SV
[MtSV]
, SV-0 is selected as
SV
when the terminal’s external contact is off and SV-1
is selected when the signal is switched on.
Note: When turned on, the digital input always checks the terminal input settings. The PGM–500 series has a limited
number of terminals. Therefore, the digital input terminal1 (DI-1) is available. The Multi SV parameter is only activated
if the Multi SV is at least 2. The digital input terminal function works independently of the lock and password settings
[PAR5 → PWD].