28 pmg511en21p01
Temperature
Alarm temperature
Without Preset Delay:
Alarm Output
With Preset Delay:
Alarm Output
Alarm off
Hysteresis
Time
Parameter
Description
A1ON
Alarm Output 1 on Delay: In the event of an alarm event, it is on standby for a preset period of time,
checks the conditions for activating the alarm, and turns on the alarm output if the conditions persist.
A1OF
Alarm Output 1 Off Delay: After the alarm output is turned off, it is ready for a preset period, checks
the alarm trigger conditions, and turns off the alarm output if the deactivation conditions continue.
5.7.7 Loop Break Alarm (LBA)
[PAR4 → AL-1/ → LBA]
Diagnose the control loop by monitoring the temperature change in the control circuit and send alarms if necessary.
– Heating control: If the
MV
control output is 100% or the upper limit
[H-
MV
]
and the
PV
does not exceed
the LBA detection band
[LBaB]
during the LBA monitoring time
[LBaT]
, or if the control output
MV
is 0%
or lower limit
[L-
MV
]
and
PV
do not fall below the LBA detection band
[LBaB]
during the LBA monitoring
time
[LBaT]
, the alarm output will turn on.
– Cooling control: If the
MV
control output is 0% or lower limit
[L-
MV
]
and the
PV
does not increase at
the LBA detection band
[LBaB]
during the LBA monitoring time
[LBaT]
, or if the control output
MV
is
100% or upper limit
[H-
MV
]
and
PV
do not fall below the LBA detection band
[LBaB]
during the LBA
monitoring time
[LBaT]
, the alarm output will turn on.
Common reasons triggering the LBA output:
– Sensor fault
(disconnection, short circuit)
– External control fault
(magnet, auxiliary relay, etc.)
– External load fault
(heating, cooling, etc.)
– Incorrect connection and disconnection of the
external network.
During auto-tuning / manual control / STOP / Ramp function, the loop break alarm does not work except for the
sensor fault indication
(HHHH / LLLL)
.
Type
LBA Monitoring
period
Alarm output
Standard alarm
Alarm latch
Initializing Alarm, changing control output operation
mode, setting LBA monitoring time/band as 0
Initializing
OFF
Changing input correction value, set value
Maintains the present alarm
Changing
MV
, stopping control, running auto-tuning
Initializing
OFF
Maintains the
present alarm
Occurring sensor break alarm, HHHH, LLLL
ON
ON