34 pmg511en21p01
Interface:
Type
Description
Communication protocol
Modbus RTU
Connection type
RS485
Application standard
EIA RS485 compliant
Maximum number of connections
31 unit (address: 01…99)
Synchronization method
Asynchronous
Communication method
2-wire, half-duplex
Communication distance
Max. 800 m
Communication speed
2400, 4800, 9600, 19200, 38400 bps
Communication response time
5…99 ms
Start bit
1-bit (fix)
Data bit
8-bit (fix)
Parity bit
None, odd, even
Stop bit
1-bit, 2-bit
5.9.1 Unit Address Settings
[PAR4 → ADRS]
Unique addresses can be assigned to units from 1 to 99. Default setting: 1.
5.9.2 BPS (Bits Per Second) Settings
[PAR4 → BPS]
Set the data transfer rate.
Parameter
Description / Range
Default
BPS
24
(2400 bps)
/
48
(4800 bps)
/
96
(9600 bps)
/
192
(19200 bps)
/
384
(38400 bps)
96 bps
5.9.3 Communication Parity Bit
[PAR4 → PRTY]
This parameter enables or disables the parity bit setting. The parity bit is a data communication method that adds
an additional bit to the transmitted data packet as an indicator for checking for data loss and damage. Default
setting: NONE.
Setting
Description
NONE
Disables parity bit.
EVEN
Parity is even if the number of bits of value 1 in the data packet is even
ODD
The parity is odd if the number of bits of value 1 in the data packet is odd
5.9.4 Communication Stop Bit Settings
[PAR4 → STP]
The number of bits can be set to indicate the end of the transmitted data series. The number of bits can be 1 or
2 bits. Default setting: 2 bits.
5.9.5 Response Timeout Settings
[PAR4→ RSwT]
Set a timeout to reduce communication errors when communicating with a slow master device
(PC, PLC, etc.)
.
After setting the waiting time, the controller responds after the specified waiting time. Default setting: 20 ms.
Note: Shorter latencies may cause communication errors in the master device.