14/36
BKI16ATEX0010X
cbr2052a0600p_05
5.1.
P
ROGRAMMING WITHOUT DISPLAY MODULE
P
ROGRAMMING FEATURES
4 mA output current (direct) assignment to the minimum (0%) level
20 mA output current (direct) assignment to the maximum (100%) level
4 mA output current (indirect) assignment to the minimum (0%) level by means of an
intermediate level
20 mA output current (indirect) assignment to the maximum (100%) level by means of an
intermediate level
Fault indication by the current output: 3.8 mA; or 22 mA
Damping (3 sec, 10 sec, 60 sec)
Reset to the Factory Default
Remark: current output can be programmed for inverse operation: 4 mA = 100% (full), 20 mA = 0% (empty)
Procedure of programming:
press programming keys in the proper sequence and watch state of the LEDs. See interpretation of the LEDs below
= LED “Off”, = LED Blinking, = LED “On” lit, = LEDs blinking alternatively = Do not care
“Direct” assignment of 4 mA to the minimum level, 0%
(or maximum level for inverse operation)
Fill the tank to the minimum (maximum) level
Programming steps
LED State After Programming step
1) Press key
and keep it pressed
= NIVOCAP in programming mode
2) Press additionally key
and keep it pressed
= Assignment of 4 mA to the level in the tank
3) Release both keys
= Programming completed
“Direct” assignment of 20 mA to the maximum level, 100%,
(or minimum level for inverse operation)
Fill the tank to the maximum (minimum) level
Programming steps
LED State After Programming step
1) Press key and keep it pressed
= NIVOCAP in programming mode
2) Press additionally key
and keep it pressed
= Assignment of 20 mA to the level in the tank
3) Release both keys
= Programming completed