EV-Mini IP2 Installation instructions
IIS-EV-Mini IP2 Issue 4 18/01/2019
RoHS Compliance Statement
This product complies with the European Union RoHS (Restriction of Hazardous Substances)
directive 2011/65/EU which restricts the use of the following six hazardous materials in the
manufacture of electronic and electrical equipment.
• Lead (Pb)
• Hexavalent Chromium
• Mercury (Hg)
• Cadmium (Cd)
• Polybrominated biphenyls (PBB’s)
• Polybrominated diphenyl ethers (PBDE’s)
NOTE:
Please read these instructions carefully and keep for future reference. The
information in this document is subject to change without notice. For updates please refer
to our website.
NOTE:
Follow the requirements for the installation of the product in accordance with the
Specifications. Otherwise it may cause malfunction
NOTE:
Do not install the product in any location where oil, dust, iron powder, chemicals, or
hydrogen sulphide may occur or affect the product. It may cause malfunction.
This package contains the following items
:
Main unit:
x 1
EOL resistor:
10k ohm x 1
Alarm Resistor:
680 ohm x 1
Manual:
(this document) x 1
General Description
The EV-Mini IP2 Mini Input Module is a compact size addressable input module with short
circuit isolator. The module provides the function to monitor an input from manual call
points, aspirating smoke detectors, beam detectors, ventilation control and fire door
control systems, etc.
The EV-Mini IP2 provides one input circuit (Class B) that can be connected to input
devices with a normally open dry contact. The EV-Mini IP2 monitors the dry contact input
through a 10k EOL resistor. The monitoring state (normal, input, open, or short) of the
device is transmitted to the control panel.
The module is equipped with a constant current output (2.5mA typ.) for a remote
indicator, which allows the remote indicator STA-R1 to be connected.
EV-Mini IP2 – Mini Input Module
with Isolator
EN 54-17: 2005 / AC: 2007 – Short Circuit Isolators
EN 54-18: 2005 / AC: 2007 – Input / Output Devices
19
0359
For use with Nittan Evolution Protocol Only.
Loop Voltage: 20 to 38 Vdc
Quiescent Current: 690µA
Alarm Current: 3.3mA (Inc. LED)
Loop resistance
:
:
:
:
< 50 ohm/ km
Input line resistance
::::
< 50 ohm/ km
EOL resistor: 10k ohm
Input resistance: 470 ohm or 680 ohm
Input threshold level: ON
:
:
:
:
< 680 ohm,
Short
:
:
:
:
<50 ohm,
Open
:
:
:
:
> 20k ohm
Min sw open voltage (Vso min): 11 Vdc
Max sw open voltage (Vso max): 14 Vdc
Min sw close voltage (Vsc min): 3 Vdc
Max sw close voltage (Vsc max): 10 Vdc
Max line current (Ic max): 500 mA
Max switching current (Is max): 1500 mA
Max leakage current (Il max): 15 mA
Max switch resistance (Zc max): 150 m
Ω
Wire size: Min. 0.75mm
2
Max. 2.5mm
2
Operating temperature: -10
°
C to 55
°
C
Storage temperature: -40
°
C to 80
°
C
Max. relative humidity: 95%RH, non-condensing
Mass: 40g
Technical Data Sheet: TD-EV-Mini IP2
DoP Number: 00641
Figure 1
SCI LED (Yellow)
Address Setting Port
Page 1