Figure 4.14 AC Grid Terminal Connector
Figure 4.13 AC Grid Terminal Connector Inside
4. Installation
Each Solis Mini Single Phase Inverter is supplied with an AC grid terminal connector.
There are symbols marked inside the connector , the Line
wire of grid must be connected to
“
L
”
terminal; the Neutral wireof grid must
be connected to
“
N
”
terminal; the Earth of grid must be connected
to
“
”
(see Figure 4.13).
4. Installation
Cable type
2.5~6.0mm
²
Cross section
Range
Industry generic
grid cable
Recommended
value
6mm
²
Table 4.2 Grid cable size
.17.
.16.
WARNING:
The steps to assemble the AC grid terminal connectors are listed as follows:
a) Disassemble the AC connector. Strip the AC wires about 6mm.
Figure 4.15 Stripped AC Wires
c) Tighten up the cap on the terminal (see Figure 4.17).
Figure 4.17 Tighten up the Cap on the Terminal
b) Fix the green and yellow wire to the ground terminal. Fix the red(or brown) wire to L
(line) terminal. Fix the blue wire to N(Neutral). Tight the screws on the connector.
Please try to pull out the wire to make sure the it’s well connected.
Figure 4.16 Connect Wires to the Terminal
For all AC connections, 2.5- 6mm 105
℃
cable is required to be used. Please make sure
2
the resistance of cable is lower than 1 ohm. If the wire is longer than 20m, it's recommended
to use 6mm cable.
2
4.3.2 Connect grid side of inverter