4. Installation

4. Installation

4.3.6 Electrical connection diagram

.21.

.20.

Figure 4.23 Meter

 

in

 

Grid

1

5 6 7 8

MENU

1600 imp/kWh

220V~10(60)A

T1

T2

T3

DDSD1352

L

N

L

´

N

´

Grid

Load

Communication

Figure 4.21 Guidance for a Simple Installation of an Inverter Solar Energy System

Isolation switch

Solar supply 

main switch

Consumers

mains

(to grid)

Main

switch

MAIN SWITCHBOARD

Circuits not

protected by

RCDs

Circuits Protected

by RCDs

Isolation device

Inverter with

integral grid

Protection device

Solar

(PV)

array

1

1

2

1. The RCD should 

be in parallel

 

connection

 between the consumers mains and the solar supply.

2. More than one RCD may be used. Each RCD can protect one or more circuits.  

Refer to figure 4.21, which is a simple guidance for installing a solar system with PV inverter. 

A DC isolator is required to be installed in the system between PV panels with inverter.

4.3.7 Meter Connection(Only for Australia)

The inverter has intergrated export limitation functionality. 

To use this function a power meter must be installed if use the power meter it should 

be installed in the load side or in the grid side see Figure 4.22 and 4.23. After the inverter 

power on please set the corresponding configuration as sections 6.5.11.1.2 and 6.5.11.1.3.

1

5 6 7 8

MENU

1600 imp/kWh

220V~10(60)A

T1

T2

T3

DDSD1352

L

N

L

´

N

´

Communication

Figure 4.22 Meter

 

in

 

Load

Grid

Load

A B

DRED means demand response enable device. The AS/NZS 4777.2

 required inverter 

:2015

need to support demand response mode(DRM). This function is for inverter that comply with 

AS/NZS 4777.2

 standard. Solis 4G single phase inverter is fully comply with all DRM. 

:2015

A RJ45 terminal is used for DRM connection.

4.3.9 DRED port connections(Only for Australia)

Assignment for inverters capable 
of both charging and discharging

Pin

1

DRM 1/5

2

DRM 2/6

3

DRM 3/7

4

DRM 4/8

5

RefGen

6

7

8

Com/DRM0

V+

V-

Assignment for inverters capable 
of both charging and discharging

Pin

4.3.8 CT connections(optional)

Figure 4.24 Direction of CT

This inverter has integrated export limitation functionality. To use this function, a CT must 

be installed if use the CT please reference below picture. The CT should be fitted around 

the live conductor on the grid side of the main incoming consumer unit. Use the directional 

flow indication arrow on the CT to ensure it is fitted in the correct orientation. The arrow 

should be pointing towards the grid, not the load. when the inverter power on, please set the 

corresponding configuration as sections 6.5.11.1.4.1 and 6.5.11.1.4.2. 

CT 

N

A B

Summary of Contents for Solis 4G Mini

Page 1: ...Industrial Park Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem on the inverter please find out the inverter S N and contact us we...

Page 2: ...6 Operation 24 5 Start Stop 5 1 Start the Inverter 5 2 Stop the Inverter 23 23 23 1 1 Product Description 3 1 2 Packaging 4 4 3 1 Connect PV side of inverter 13 4 3 2 Connect grid side of inverter 16...

Page 3: ...6 4 2 Running Message 28 32 6 5 3 Clear Energy 6 5 4 Reset Password 31 31 6 4 6 Daily Record 6 4 7 Communication Data 29 29 6 5 5 Power Control 6 5 6 Calibrate Energy 31 32 6 5 7 Special Settings 6 5...

Page 4: ...ety Symbols Safety symbols used in this manual which highlight potential safety risks and important safety information are listed as follows WARNING WARNING symbol indicates important safety instructi...

Page 5: ...Main Switch AC must be switched off before the solar panel s DC isolator shall be switched off 6 CAUTION The PV array Solar panels supplies a DC voltage when they are exposed to sunlight CAUTION Risk...

Page 6: ...t indications 8 Figure 4 1 Recommended Installation locations To select a location for the inverter the following criteria should be considered To avoid over heating ambient air temperature must be co...

Page 7: ...nverters are installed in one location a minimum 12inchs clearance should be kept between each inverter or other object The bottom of the inverter should be 20inchs clearance to the ground Visibility...

Page 8: ...0 4G Solis mini 3600 4G Solis mini 1000 4G LV Please don t connect PV array positive or negative pole to the ground it could cause serious damages to the inverter Figure 4 6 DC Connector Figure 4 7 DC...

Page 9: ...nnector cap nut and contact pin Figure 4 8 Disassemble the Connector Cap nut Figure 4 9 Insert the Wire into the Connector Cap nut and contact pin iii Crimp the contact pin to the wire using a proper...

Page 10: ...semble the AC grid terminal connectors are listed as follows a Disassemble the AC connector Strip the AC wires about 6mm Figure 4 15 Stripped AC Wires c Tighten up the cap on the terminal see Figure 4...

Page 11: ...l connector to the inverter Small click will confirm connection Figure 4 18 Connect the AC Connector to the Inverter The inverter can be monitored via Wi Fi or GPRS All Solis communication devices are...

Page 12: ...lease set the corresponding configuration as sections 6 5 11 1 2 and 6 5 11 1 3 1 5 6 7 8 MENU 1600 imp kWh 220V 10 60 A T1 T2 T3 DDSD1352 L N L N Communication Figure 4 22 Meter in Load Grid Load A B...

Page 13: ...Inverter the following steps must be strictly followed 1 Switch the Supply Main Switch AC OFF 2 Wait 30 seconds Switch the DC Switch OFF All the LEDs of the inverter will be off in one minute 5 Start...

Page 14: ...ormation list Inverter SN 00000000000000 Export_P 0000W Export_I 00 0A 10 sec 10 sec Display series number of the inverter Power of ERM Current of EPM 10 sec Work Mode The work mode of inverter DRM Nu...

Page 15: ...word the Main Menu will display a screen and be able to access to the following information 1 Alarm Message 2 Running Message 3 Version 4 Daily Energy 5 Monthly Energy 6 Yearly Energy 7 Daily Record 8...

Page 16: ...reen shows the internal data of the Inverter see Figure 6 14 which is for service technicians only 01 05 01 25 E4 9D AA 06 10 C2 B5 E4 9D 55 Figure 6 14 Communication Data Press DOWN key to move the c...

Page 17: ...OTE This function is for technicians use only Press the UP DOWN keys to select the standard AS4777 02 AS4777 15 VDE4105 VDE0126 UL 240V A UL 208V A UL 240V UL 208V MEX CFE G83 2 for 1 3 6kW models G59...

Page 18: ...u 1 NULL 2 Volt watt 3 Volt var 4 Fixed PF 5 Reac power 6 Power PF There are 5 setting under STD Mode settings 1 Working mode 2 Power Rate limit 3 Freq Derate set 4 10mins OV G V set 5 Initial Setting...

Page 19: ...o default 6 5 10 HMI Update This function is used for update the LCD program This function is applicable by maintenance personnel only wrong operation will prevent the inverter from reaching maximum p...

Page 20: ...ore than 500W Correct means CT has been connected correctly Before pressing the CT Link Test menu please check as follow 1 Load power 500W 2 Inverter should be set Grid Off 3 CT should be connected 4...

Page 21: ...igned in accordance with the most important international grid tied standards and safety and electromagnetic compatibility requirements Before delivering to the customer the inverter has been subjecte...

Page 22: ...staller UN G V01 02 DC INTF DC input overcurrent 1 Restart inverter 2 Identify and remove the string to the fault MPPT 2 Change power board IGFOL F Grid current tracking fail OV G I Over grid current...

Page 23: ...t rated output power 1 5 42 43 50 550 Start up voltage Volts 60 Max short circuit input current Amps 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT numb...

Page 24: ...voltage Volts 60 Max short circuit input current Amps 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid voltage...

Page 25: ...voltage Volts 90 Max short circuit input current Amps 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid voltage...

Page 26: ...Volts 90 Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number M...

Page 27: ......

Reviews: