Supply air control
The menu "
Supply air control
" allows you to select the duration for which the compressor has to be off
before it restarts.
ATTENTION
The parameters in the menu “
Supply air control
“ should only be adjusted by persons with
knowledge of control technology.
Service / Supply air control
↳
PI regulation
Settings:
Standard setting:
0
↔
30%/°
7% / °
↳
Integration time
Settings:
Standard setting:
0
↔
600 sec.
120 sec.
↳
Neutral zone
Settings:
Standard setting:
0
↔
10° C
2° C
↳
Temperaturramp.
Settings:
Standard setting:
Off / 0.01
↔
1.0 °C/s
0.10°C / s
↳
Capacityramp.
Settings:
Standard setting:
Off / 0.1
↔
10.0 °C
0.5% / s
↳
Condensor limit
Settings:
Standard setting:
4
↔
70° C / Off
55° C
↳
Hot gas modulation
Settings:
Standard setting:
Auto / Normal / Fast / Very fast
Auto
↳
Restart time
Settings:
Standard setting:
Description:
0
↔
60 minutes
6 minutes
Minimum duration (in minutes) for which the
compressor has to be off before it restarts.
Room temperature control
The menu "
Room temp. control
" makes it possible to set the regulator for controlling the room
temperature.
ATTENTION
The parameters in the menu “
Room temp. control
“ should only be adjusted by persons with
knowledge of control technology.
Service / Room temp. control
↳
Type of response
Settings:
Standard setting:
Description:
Slow / Normal / Fast / User
Normal
Slow: Gain = 4.0 and integral = 12
Normal: Gain = 6.0 and integral = 6
Fast: Gain = 8.0 and integral = 4
User: 6.0 = 6
↳
Neutral zone
Settings:
Standard setting:
Description:
0.0
↔
10 °C
2.0 °C
Set the offset temperature at which the shift between
compressor and after-heating should be activated.
VPL28 (English)
BY NILAN
29