Service settings
Password
Password for service settings: 2
User selection 1
You can set the user selection program using special settings that override the operating mode in the
main menu. The user selection program is activated via an external signal.
The user selection program can be used, for instance, to create imbalance in supply air and extract air
ventilation.
When user selection 1 is active, an icon is displayed on the main screen
Service / User selection
↳
Select program
Settings:
Standard setting:
Description:
No / Expanded / Supply air / Extract air / Ventilate
Expanded
Here you select the program you wish to run.
↳
Expanded
Description:
If you select expanded.
↳
Duration
Settings:
Standard setting:
Description:
Off / 15
↔
480 minutes
Off
Time runs with 15 minute intervals. Select for how long
the program is to continue after the external signal has
ceased.
↳
Fan speed level
Settings:
Standard setting:
Description:
Level 1 / Level 2 / Level 3 / Level 4 / Off
Level 4
Select the desired fan speed level.
↳
Room temperature
Settings:
Standard setting:
Description:
5
↔
30 °C
23 °C
Set the desired room temperature.
↳
Supply air
Description:
If you select supply air.
↳
Duration
Settings:
Standard setting:
Description:
Off / 15
↔
480 minutes
Off
Time runs with 15 minute intervals. Select for how long
the program is to continue after the external signal has
ceased.
↳
Fan speed level
Settings:
Standard setting:
Description:
Level 1 / Level 2 / Level 3 / Level 4 / Off
Level 4
Select the desired fan speed level.
↳
Extract air
Description:
If you select extract air.
↳
Duration
Settings:
Standard setting:
Description:
Off / 15
↔
480 minutes
Off
Time runs with 15 minute intervals. Select for how long
the program is to continue after the external signal has
ceased.
↳
Fan speed level
Settings:
Standard setting:
Description:
Level 1 / Level 2 / Level 3 / Level 4 / Off
Level 4
Select the desired fan speed level.
↳
Ventilate
Description:
If you select ventilate.