Heating surface
MODE
”HEATING”
MODE
”OFF”
ENTER
ENTER
ENTER
ENTER
INLET
HEATING
MODE
DEMAND
INLET
MIN 20°C
INLET
MAX 40°C
CURVE
10
OFFSET
CUR 0°C
OFFSET
T15 0°C
DELAY
10 MIN
1
2
3
4
5
6
7
1. MODE "DEMAND"
Select central heating mode "HEATING", "OFF" og "DEMAND"
When the channel heating function is set to HEAT, the regulation is
constantly controlled from the inlet SET point from the curve function.
When the channel heating function is set to DEMAND, the regulation is
controlled by the selected SUPPLY MIN temperature, when there is no
room heating requirement. When there is a room heating requirement,
the curve temperature is used - as in setting HEAT.
2. INLET "MIN 20°C"
Minimum limit for supply air temperature (Channel heater) between 5
and 50 °C.
3. INLET"MAX 40°C"
Maximum limit for supply air temperature (Channel heater) between 5
and 50 °C.
4. CURVE "10"
The weather compensation curve can be set between 1 and 10 (see
illustration).
5. OFFSET CUR"0°C"
Supply air temperature can be changed in the weather compensation
curve (-15 to + 10 °C).
6. OFFSET T15 "0°C"
Rumtemperaturen kan BEHOV forskydes fra rummets setpunkt til et
lavere setpunkt (0 til +2°C).
7. DELAY "10 MIN"
Delayed activation in DEMAND operation from 0-30 min.
Combi 302 Polar Top (English)
BY NILAN