1. TIME 00:00
Required period in which the selected function is to remain operative,
stated in hours and minutes. Max. 8 hours.
2. FLOW <4>
Required ventilation level: 1-4. OFF allows the system to be shut
down via an external switch.
3. TEMP 23°C
Required room temperature (5-30°C). T15 is the controlling sensor.
4. SELECT "INLET" "EXHAUST"
Time and speed must be set in the same way as described under
SELECT EXTEND.
5. SELECT "EKS OFFS"
The temperature is added or subtracted to/from the set point.
Choose the afterrunning and displacement of the set point for
external room heating. Selected in the same way as shown under
SELECT EXTEND
.
6. SELECT "VENTILAT"
Possibility to run a higher or lower speed. High priority.
7. SELECT "OFF"
User selection deactivated.
The menu
USER SELECT
overrides the operating mode of the main menu by activating an external
switch.
12