User select 2
ENTER
ENTER
ENTER
ENTER
SELECT
EXTEND
TIME
00:00
FLOW
>4<
TEMP
23°C
TIME
”00:00”
FLOW
”>4<”
TEMP
”23°C”
ENTER
ENTER
SELECT
”EXHAUST”
SELECT
”EXT OFFS”
SELECT
”VENTILAT”
SELECT
”C HOOD”
ENTER
ENTER
ENTER
SELECT
”OFF”
SELECT
”EXTEND”
USER
SELECT 2
ENTER
ENTER
1
2
3
SELECT
”INLET”
5
7
6
4
8
1. TIME 00:00
Required period in which the selected function is to remain operative,
started in hours and minutes. Max. 8 hours.
2. FLOW <4>
Required ventilation level : 1-4. OFF allows the system to be shut
down via an external switch.
3. TEMP 23°C
Required room temperature (5-30°C). Panel sensor T15 is the
controlling sensor.
4. SELECT "INLET" "EXHAUST"
Time and speed must be set in the same way, as described under
SELECT EXTEND.
5. SELECT "EXT OFFS"
The temperature is added or subtracted to/from the set point.
Choose the afterrunning and displacement of the set point for
external room heating. Selected in the same way as shown under
SELECT EXTEND
.
6. SELECT "VENTILAT"
Possibility to run a higher or lower speed. High priority.
7. VALG "C HOOD"
RE7: Close switch for controlling of hood damper motor.
8. SELECT "OFF"
User selection deactivated.
The menu
USER SELECT 2
is used as
USER SELECT
. (only shown when option PCB is fitted)
Combi 302 Polar Top (English)
BY NILAN
13