EN nv
Niko
sa Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel. +32 3 778 90 00 — fax +32 3 777 71 20 — e-mail: [email protected] — www.niko.eu
PMXXX-7802XR14325
XXX-7802X
4.4. Manual operation
The flush-mounting motion detector has two modes. Besides the automatic or PIR mode (see section 4.3.), you
can also switch the lighting on and off manually.
Step
Action
Result
1
Press the button on the top
of the sensor briefly (< 5 s):
- The lighting remains switched on for four hours.
- During this time, the red LED behind the sensor lens is also
illuminated.
- After four hours, the sensor resumes its normal operation
(automatic mode).
- The red LED switches off.
2
Press this button again.
- The lighting is switched off.
- The sensor detects no movement for a period of ten seconds.
- After ten seconds, the sensor resumes its normal operation.
To block the shift to the manual mode, connect the voltage (the same phase as the power supply voltage) to the
external input terminal 1 (E1) of the actuator.
4.5. Staircase function
By briefly interrupting the voltage at the external input terminal 1 (E1) of the actuator via a push button (NO or
NC), the lighting is switched on for the duration of the preset switch-off delay
if
at that moment the daylight is
less intense than the preset lux value.
4.6. Parallel connection
In installations with several motion detectors that are connected in parallel, the lamps may not be illuminated
in the detection area of different motion detectors, because, for example, when the first sensor switches off the
lighting, the second sensor registers the lowering temperature and switches the lighting on again. The minimum
load required remains 40 W.
4.7. External push button
If you press the external push button, the lighting is switched on, just like when the sensor is activated. The
lighting is only switched on if the photo cell in the sensor registers that it is sufficiently dark in the room (the
daylight level falls below the preset lux value).
5. TROUBLESHOOTING
Problem
Cause
Action
The flush-mounting motion
detector does not switch on.
The reaction threshold is set to
twilight in a brightly illuminated
room.
Correctly set the light intensity
(lux value).
The lens is covered or dirty.
Uncover or clean the lens.
The electronic control gear or the
fuse is defective.
Replace the defective electronic
control gear or the defective
fuse.
The wiring is faulty.
Check the wiring.
The lighting does not work.
The lamp is defective.
Replace the lamp.
The flush-mounting motion
detector has been mounted at
the incorrect height.
Respect the recommended
mounting height (0.8 – 1.2 m).
The lighting remains illuminated.
The manual mode is activated.
Deactivate the manual mode.
You have switched on the lighting
using a switch.
Switch off the lighting with the
switch.
There is constant movement in
the detection area.
- Remove the heat source from
the detection area.
- Set the switch-off delay to the
shortest possible time.
- Wait until the switch-off delay
elapses (max. 30 minutes).
- Cover the lens to check this
setting.
The manual mode cannot be put
into operation.
The manual mode is blocked.
Deactivate the block (see section
4.4.).
The manual mode is activated.
Activate the automatic mode
and then the manual mode (see
section 4.4.).
The lighting is constantly
switching on and off.
The distance to the switched
lamp is too small.
Increase the distance to the
lamp.
Automatic and unwanted
switching
The flush-mounting motion
detector switches on after
the mains voltage has been
interrupted.
The lighting is illuminated
for 90 seconds before the
interruption. After that, the device
is in automatic mode.
Sunlight falls on the lens or in
the detection area.
Set the lux value to twilight.
Heat/cold penetrates through to
the detection area by way of an
open door or window.
Close the door or window or
move the device.
6. TECHNICAL DATA
power supply voltage
230 Vac, 50 Hz
mounting
flush-mounting box with flush-mounting depth of
min. 40 mm
connection terminals
6 (maximum capacity per connection terminal:
2 x 1.5 mm² or 1 x 2.5 mm²)
ambient temperature during operation
0 – 40°C
ambient temperature during storage and transport
-25 – 70°C
switch-off delay
± 5 s – 30 min
light sensitivity
± 2 – 1000 lux
flush-mounting height
0.8 – 1.2 m
extra functionality
staircase function
detection angle
horizontal: 180° – vertical: 60° (see illustrations
below)
detection range
8 m (horizontal) (see illustrations below)
0
1
2
3
4
5
6
7
8 m
7
6
5
4
3
2
1
8 m
10°
0°
35°
50°
0
1
2
3
4
5
6
7
8 m
7
6
5
4
3
2
1
8 m
10°
0°
35°
50°
7. WARNINGS REGARDING INSTALLATION
- The installation should be carried out by a registered installer and in compliance with the statutory
regulations.
- This manual should be presented to the user. It should be included in the electrical installation file, and it
should be passed on to any new owners. Additional copies are available on the Niko website or via the Niko
support service. The latest manual for this product is available on the Niko website at any time.
- During installation, the following should be taken into account (non-exhaustive list):
- the statutory laws, standards and regulations.
- the technology currently available at the time of installation.
- this manual, which only states general regulations and should therefore be read within the scope of each
specific installation.
- the rules of proper workmanship.
This product complies with all of the relevant European guidelines and regulations. If applicable, you can find
the EC declaration of conformity regarding this product at www.niko.eu.
8. NIKO SUPPORT
In case of doubt or for the specific exchange procedure in case of a possible defect, contact the Niko support
service in Belgium at +32 3 778 90 80 or your wholesaler/installer. Contact details and more information can
be found at www.niko.eu under the “Help and advice” section.
9. GUARANTEE PROVISIONS
- The period of guarantee is four years from the date of delivery. The delivery date is the invoice date of
purchase of the product by the consumer. If there is no invoice, the date of production applies.
- The consumer is obliged to inform Niko in writing about the non-conformity, within two months after stating
the defect.
- In case of a non-conformity, the consumer only has the right to a product repair or replacement free of
charge, which shall be decided by Niko.
- Niko shall not be held liable for a defect or damage resulting from incorrect installation, improper or
careless use, incorrect operation, transformation of the product, maintenance that does not adhere to the
maintenance instructions or an external cause, such as damage due to moisture or overvoltage.
- The compulsory regulations of the national legislation concerning the sale of consumer goods and the
protection of the consumer in the countries where Niko sells, directly or via sister companies, subsidiaries,
chain stores, distributors, agents or permanent sales representatives, take priority over the above-mentioned
rules and regulations.
8