background image

 

 

 

 

 

 

Technical data 

nominal voltage:

           24V DC (21 - 30V DC) 

power consumption:

       0,4 W 

PIR- sensors:

 

   3 Pyro detectors 

sensitivity:

 

   adjustable via ETS in 10 steps 

light measuring:

             brightness sensor with linear output 

lux value: 

   value readable (5 - 2000lux, 2 Byte) 

switiching criteria:

          motion and brightness 

detection range:             

360°, ceiling mounted 

r

 

ange 

height= 3m/ 

RA 16m

:   

Ø6m presence, Ø14m motion 

range 

height= 3m/ 

RA 30m

:

   Ø7m presence, Ø26m motion 

recom. mounting height

:

  

2m – 6m (25032

, 25034

 

2m – 8m (25036) 

ceiling or false- ceiling mounting   

AP/UP- housing, IP55 -housing    

IP 20, indoor mounting, class II 

- 20°C bis +40 °C

mounting:

available accessory

:

    

protection rating:

      

temperature range:  

dimensions:       

RA

  16  m:  Ø105  x  44  mm

RA

 30 m: Ø105 x 

51mm

RA

 16 m 

EB

: Ø105 x 51 mm

PM

35032_35034_35036

R2150

3

_EN

Warnings regarding installation

The installation of products that will permanently be part of the electrical installation and which 
include dangerous voltages, should be carried out by a qualified installer and in accordance 
with the applicable regulations. This user manual must be presented to the user. It should 
be included in the electrical installation file and it should be passed on to any new owners. 
Additional copies are available on the Niko website or via Niko customer services. 

CE marking

This product complies with all of the relevant European guidelines and regulations. For radio 
equipment Niko llc declares that the radio equipment in this manual conforms with the 2014/53/
EU directive. The full text of the EU declaration of conformity is available at www.niko.eu under 
the product reference, if applicable.

Environment

This product and/or the batteries provided cannot be disposed of in non-recyclable waste. Take 
your discarded product to a recognised collection point. Just like producers and importers, 
you too play an important role in the promotion of sorting, recycling and reuse of discarded 
electrical and electronic equipment. To finance the rubbish collection and waste treatment, the 
government levies recycling charges in certain cases (included in the price of this product).

Summary of Contents for SG360KNX/KLR RA 16 m

Page 1: ... SG360KNX KLR RA 16 m 3505100250326 351 25034 SG360KNX KLR RA 16 m EB 3505100250340 351 25036 SG360KNX KLR RA 30 m 3505100250364 nv Niko sa Industriepark West 40 9100 Sint Niklaas Belgium www niko eu 32 3 778 90 80 support niko eu Edition 12 2021 Art Nr 351 25032 351 25034 351 25036 ...

Page 2: ...ght output for switching dimming or scenery selection Standby light If the light channel is set to dimming absolute an emergency standby light can be programmed using the standby value and standby duration min h Two value pairs can be read out from the KNX bus 1 HVAC channel controls heating ventilation and air conditioning This output can be used for presence detection Additionally alarm systems ...

Page 3: ... connected light If no motion is detected again the light will automatically switch off after a delay time configured in ETS In case of activated standby the light will stay on at reduced intensity during the set time period mode dimming complete constant light control Installation Connect the presence detector as follows red wire to be connected to red terminal black wire to be connected to grey ...

Page 4: ...SG360P KNX KLR RA 16m 351 25032 frontal view rear view 4 bus terminal grey bus terminal red rating plate ...

Page 5: ...e above numbering scheme After KNX EIB bus connection the detector takes approx 1 min to reach a stable working condition 5 lux sensor LED green Flashes with each detection programming button LED red programming glows upon pressing the programming button PIR sensors numbering 3 2 1 ...

Page 6: ...unting height as well as the angle of approach high sensitivity when crossing a switching segment Since the device registers the temperature differences between the source of heat and the ambient temperature the detection range may vary depending on site conditions floor heating etc SG360P KNX KLR RA 30m 30m lenses SG360P KNX KLR RA 16m 16m lenses 6 ...

Page 7: ... or potential causes of false light never turns OFF triggering animals heating etc may all doing faulty switching check distances to lamps heat reflection or direct light influence detector is to sensitive reduce the detection range sensitivity 1 10 via ETS Turns the ON during day twilight adjustment set to high time set to a lower value via ETS menu light execution RA 16m round execution RA 16m E...

Page 8: ...e carried out by a qualified installer and in accordance with the applicable regulations This user manual must be presented to the user It should be included in the electrical installation file and it should be passed on to any new owners Additional copies are available on the Niko website or via Niko customer services CE marking This product complies with all of the relevant European guidelines a...