18. Motor module
3
The switching circuits you wish to connect can now be connected to the outputs.
4
Group all neutral conductors and connect these to one N screw terminal.
5
Connect the motor module to the module before it. Slide the sliding contact of this module to the right until it clicks
into the motor module. This will ensure that the bus and the power supply voltage are connected.
A 230 Vac or 24 Vdc motor is used for the operation of venetian blinds or vertical blinds.
Error codes
When the module is functioning properly, the STATUS LED will light up in TEST mode only. If one or several errors occur,
the LED will blink to indicate the error code of the error with the highest priority. The table below provides an overview of
all error codes.
Technical data
• switching delay: 0,5 s
• maximum number of motors permitted: 3
• maximum 6 A per output
• dimensions: DIN 4U
• sliding contact
• connection terminals for 3 x 1,5 mm² or 2 x 2,5 mm² or 1 x 4 mm²
• CE marking
• ambient temperature: 0 to 45°C (without derating)
Keep in mind the following when installing the motor module:
• Venetian blinds are operated with a 230 Vac motor in the same way as roll-down shutters.
• To operate venetian blinds using a 24 Vdc motor, you will need two switching contacts (not a Niko product)
per venetian blind or vertical blind.
LED
ACTION
ERROR
POSSIBLE SOLUTIONS
STATUS LED
Blinks – one pulse per two
seconds.
Software error
Wrong software version.*
*Download the latest software version
from the Niko website to upgrade the
module.