8
GENERAL INFORMATION
Powerdrive MD2S Installation guide
4972 en - 2017.08 / d
1.4 - Electrical characteristics
All work relating to installation, commissioning and maintenance must be carried out by experienced, qualified
personnel.
1.4.1 - General characteristics
Characteristics
Level
Power supply voltage
3-phase supply: 400 V -10% to 480 V +10% ("T" ratings) or
525 V -10% to 690 V +5% ("TH" ratings)
Phase voltage imbalance
< 2%
Input frequency
"T" ratings: 50 or 60 Hz ± 5%
"TH" ratings: 50 Hz ± 5%
Maximum number of power-ups per hour (power)
20
Output frequency range
0 to 590 Hz
ROHS conformance
Conforming to standard 2002-95-EC
For operation with a neutral IT point connection, follow the instructions given in section4.4.3
1.4.2 - Electrical characteristics
Ico
: Continuous output current.
Pout
: Output power.
Imax (60s)
: Maximum output current, available for 60 seconds every 600 seconds
Heavy duty
: For heavy duty constant torque machines (presses, grinders, hoisting, etc.) and all applications where significant
inertia has to be accelerated quickly (centrifuges, translation of travelling cranes, etc.).
Normal duty
: For low overload constant torque or centrifugal torque machines (fans, compressors, etc.).
WARNING: In its factory setting, the drive operates with a switching frequency of 3 kHz.
400 V to 460 V 3-phase supply
Switching frequency = 3 kHz - ambient temperature ≤ 40°C (35°C with IP54 option) - altitude ≤ 1,000 m.
Rating
Heavy duty
Normal duty
Imax (60 s)
(A)
Pout at 400 V
(kW)
(1)
Pout at 460 V
(HP)
(1)
Ico
(A)
Pout at 400 V
(kW)
(1)
Pout at 460 V
(HP)
(1)
Ico
(A)
100T
75
100
142
90
125
175
200
120T
90
125
170
110
150
212
240
150T
110
150
220
132
175
250
312
180T
132
175
260
160
200
315
365
220T
160
200
310
200
300
400
435
270T
200
300
375
250
350
470
530
340T
250
350
470
315
450
580
660
400T
315
450
540
355
500
650
760
470T
355
500
670
450
600
800
940
570T
400
600
750
500
650
880
1050
600T
450
650
865
550
700
1090
1210
750T
550
800
990
675
900
1220
1390
900T
675
900
1225
800
1000
1500
1720
1100T
800
1000
1375
900
1250
1650
1930
1400T
900
1250
1850
1200
1500
2250
2590
1700T
1200
1500
2065
1350
1700
2480
2890
(1) Motor winding voltage