32
PARAMETER-SETTING INTERFACE AND OPTIONS
Installation guide Powerdrive MD Smart Equipment
5704 en - 2021.10 / b
5.1.3 - Interface architecture
To access the interface main menu page, press the Menu
icon in the upper-left corner. Seven menus allow the user to
commission and supervise the drive, as described below.
-
General informations
: gives application type and name
(if previously set), motor details (if previously set) and drive
details.
-
Data display
: Only available if drive output is active. Fully
configurable, allows to display several read values, shown
as curve, bargraph or indicator. By default, gives operator
display (motor speed curve, current magnitude bargraph,
output power indicator) and main control board I/O status.
Additional information can be displayed depending on options
fitted or connected to the drive.
-
Quick application tuning
: menu fully configurable by the
user who can choose up to 20 parameters to be displayed.
Once the drive is commissionned, the operator can access to
this menu to easily read or set main application parameters
without having to search through all interface menus. If initial
start-tup wizard of the drive is used, some parameters can
be automatically stored in this menu, but they still can be
changed by the user if needed.
-
System settings
: provides an access to an easy set-up
function (a wizard for initial start-up of the drive and easy
setup menus for quick setting after first start-up), advanced
menus for experienced users or specific settings, and
password management.
-
Parameter file management
: allows the user to create
several configuration files and to compare them to current
settings, to default settings or to each other.
-
Data monitoring
: allows the user to customize the display
or the parameters and to manage alarms, trips or triggers.
-
Event history
: lists the operating history, trip record and
setting changes.
NOTE
If a menu is locked with a password, the user will see the
locker logo on the left as described below.
: Locker logo which highlights a password protection.
One locker for Level 1 protected,
Two lockers for Level 2 protected.
5.1.4 - Special settings
Refer to commissioning manual (ref. 5641) for further
information on settings parameters for the Powerdrive
MD Smart.
• Clogged filter alarm
The
Powerdrive MD Smart
has an "over temperature" alarm
(# 10.18) which warns the user when the internal temperature
of the product reaches 60°C or when a power module
overheats.
To set a different alarm treshold, you can use the following
settings:
Using comparator 3:
#12.63
=
7.55
(source = control board temperature)
#12.64
=
60
(threshold = 60°C)
#12.65
=
2
°C (hysteresis)
#12.65
=
0
To display information on the HMI of the drive:
#12.67
=
10.54
(User Alarm 1)
To adress information to a digital output (eg. DO1)
# 8.26
=
12.61
(DO1 assigned to comparator 3)
Reminder:
Powerdrive MD Smart
filters are washable and
must be kept clean.