11
GENERAL INFORMATION
Installation guide Powerdrive MD Smart Equipment
5704 en - 2021.10 / b
Rating
Ambient
temperature
INVERTER
RECTIFIER 690V
Isp output current
(A)
Power supply current
Normal duty
Heavy duty
Imax 3s
(A)
Imax
60s
(A)
Input
current
(A)
Imax
60s
(A)
Idc
(A)
3kHz 4kHz 6kHz 8kHz 3kHz 4kHz 6kHz 8kHz
150TH
40°C
143
119
91
72
115
96
73
57
195
175
136
210
166
50°C
130
108
82
65
104
87
66
52
123
150
180TH
40°C
172
143
110
86
143
119
92
72
230
211
170
263
208
50°C
156
130
99
78
130
108
83
65
154
189
220TH
40°C
248
203
153
153
195
159
120
96
315
286
222
343
271
50°C
225
184
138
138
176
144
109
87
201
246
340TH
40°C
375
341
256
201
295
268
202
158
475
432
334
518
409
50°C
340
309
232
182
267
243
183
143
303
371
430TH
40°C
456
415
310
244
359
327
244
192
580
526
407
630
498
50°C
413
376
281
221
325
296
221
174
368
451
570TH
40°C
516
439
329
260
406
397
298
235
648
594
497
770
608
50°C
467
398
298
235
368
360
270
213
450
551
680TH
40°C
728
661
497
389
572
521
391
306
922
838
699
1083
856
50°C
659
599
450
352
519
472
354
277
633
775
860TH
40°C
886
806
602
472
697
634
474
372
1125
1020
850
1317
1041
50°C
802
730
545
428
631
574
430
337
770
943
1140TH
40°C
1000
852
639
504
787
771
578
456
1257
1152
960
1487
1175
50°C
906
772
579
456
713
698
524
413
869
1065
1290TH
40°C
1315
1196
894
701
1034
941
704
553
1670
1515
1262
1955
1545
50°C
1191
1084
810
635
937
852
638
501
1143
1399
1710TH
40°C
1485
1265
949
748
1169
1144
858
677
1866
1711
1425
2208
1745
50°C
1345
1146
859
678
1059
1036
777
613
1291
1581
2280TH
40°C
1960
1669
1252
987
1542
1510
1132
893
2462
2257
1880
2914
2303
50°C
1775
1512
1134
894
1397
1367
1026
809
1703
2086
2850TH
40°C
2450
2087
1565
1234
1928
1887
1415
1116
3110
2851
2350
3642
2878
50°C
2219
1890
1418
1118
1746
1709
1282
1011
2129
2607