19
U
W
V
PE
PE
PE
CONNECTIONS
Installation guide Powerdrive MD Smart Equipment
5704 en - 2021.10 / b
Rating
POWERDRIVE
AC supply
Motor
500-690V - 50Hz
I
L
(A)
Fuses
gG type
(1)
Cable cross-section
(mm²) (2) (4)
Overload
Ico (A)
Cable cross-section
(mm²) (3) (4)
150TH
136
160
3x120 + PE
Heavy
115
3x120 + PE
Normal
143
3x120 + PE
180TH
170
200
3x120 + PE
Heavy
104
3x120 + PE
Normal
172
3x120 + PE
220TH
222
250
3x150 + PE
Heavy
195
3x150 + PE
Normal
248
3x150 + PE
340TH
334
400
2x(3x95) + PE
Heavy
295
2x(3x95) + PE
Normal
375
2x(3x95) + PE
430TH
407
500
2x(3x150) + PE
Heavy
359
2x(3x150) + PE
Normal
456
2x(3x150) + PE
570TH
497
500
2x(3x185) + PE
Heavy
406
2x(3x185) + PE
Normal
516
2x(3x185) + PE
680TH
699
Heavy
572
Normal
728
4x(3x240) + PE
860TH
850
Heavy
697
Normal
886
4x(3x150) + PE
1140TH
960
Heavy
787
Normal
1000
4x(3x240) + PE
1290TH
1262
Heavy
1034
Normal
1315
1710TH
1425
Heavy
1169
Normal
1485
2280TH
1880
Heavy
1542
Normal
1960
2850TH
2350
Heavy
1928
Normal
2450
Note: The line current value
I
L
is a typical value which depends on the source impedance.
(1)
The aR semi-conductor fuses included as standard do not protect the drive power supply line. They must be combined with an
overload protection device (gG fuses, C type circuit-breaker, etc.) suitable for the installation configuration and located at the start
of the line.
(2)
The recommended AC supply cable cross-sections have been determined for single-core cable with a maximum length of 20 m.
For longer cables, take line drops due to the length into account.
(3)
The motor cable cross-sections are given for information only for a current corresponding to the value of the
Ico current at 3 kHz in normal duty, a maximum length of 50 m, output frequency less than 100 Hz and an ambient
temperature of 40°C.
The recommended motor cables are shielded multicore type
. The values supplied are
typical values.
Example: Cable cross-section of 2 x [3 x 150 + PE] corresponds to 2 cables each consisting of 3 phase conductors
(cross-section 150 mm²) + earth conductors (see below).
(4)
The earth (PE) conductor cross-section cannot be less than half the cross-section of a live conductor, with the same material
used. Example: The earth conductor cross-section for a live conductor 2x 240 mm² must be:
- 2 x 120 mm²
- 2 x (3 x 40 mm²) when the earth conductor is divided by 3 (see above figure)
(5)
For Powerdrive MD Smart equipment 680TN-H / 860TN-H / 1140TN-H / 1290TN-H / 1410TN / 1710TN-H / 2280TN-H / 2850TN-H:
• The cables for each of the motor U/V/W phases must be distributed symmetrically over the U/V/W connection plates in each
drive cabinet.
• In -B versions, the incoming line cables must be distributed symmetrically over the L1/L2/L3 connection plates in each drive
cabinet.