Electric Power Generation

Installation and maintenance

R221

A.V.R.

5035 en -

3.3 - Electrical faults

Fault

Action

Effect

Check/Cause

No voltage at 

no load on 

start-up

Connect a new battery 

of 4 to 12 volts to 

terminals E- and E+, 

respecting the polarity, 

for 2 to 3 seconds

The alternator builds up and its 

voltage is still correct when the 

battery is removed.

- Lack of residual magnetism

The alternator builds up but its 

voltage does not reach the rated 

value when the battery is 

removed.

- Check the connection of the voltage 

reference to the AVR

- Faulty diodes

- Armature short-circuit

The alternator builds up but its 

voltage disappears when the 

battery is removed

- Faulty AVR

- Field windings disconnected

- Main field winding open circuit - check the 

resistance

Voltage too 

low

Check the drive speed

Correct speed

Check the AVR connections (AVR may be 

faulty)

- Field windings short-circuited

- Rotating diodes burnt out

- Main field winding short-circuited - Check 

the resistance

   

Speed too low

Increase the drive speed 

(Do not touch the AVR voltage pot. (P2) 

before running at the correct speed) 

Voltage too 

high

Adjust AVR voltage 

potentiometer

Adjustment ineffective

Faulty AVR

Voltage 

oscillations

Adjust AVR stability 

potentiometer

- Check the speed : possibility of cyclic 

irregularity 

- Loose connections

- Faulty AVR

- Speed too low when on load (or U/F bend 

set too high)

Voltage 

correct at no 

load and too 

low when on 

load (*)

Run at no load and 

check the voltage 

between E+ and E- on 

the AVR

- Check the speed (or U/F bend set too 

high)
- Faulty rotating diodes

- Short-circuit in the main field. Check the 

resistance

- Faulty exciter armature.

(*) Caution :

 For single-phase operation, check that the sensing wires coming from the AVR are correctly connected to the 

operating terminals
Voltage 

disappears 

during 

operation

Check the AVR, the 

surge suppressor, the 

rotating diodes, and 

replace any defective 

components

The voltage does not return to the 

rated value.

- Exciter winding open circuit

- Faulty exciter armature

- Faulty AVR

- Main field open circuit or short-circuited

Warning : after operational testing, replace all access panels or covers.

Summary of Contents for LEROY-SOMER R221

Page 1: ...E E 0V 110 R221 VOLT OPEN FOR 60 Hz STAB POT 1K R221 A V R Installation and maintenance...

Page 2: ...ing symbol for electrical danger to personnel All servicing or repair operations performed on the AVR should be undertaken by personnel trained in the commissioning servicing and main tenance of elect...

Page 3: ...al and recycling instructions WARNING The AVR R221 is dedicated for the alternators LSA40 and LSA423 single phase 50Hz 60Hz It is particularly recommended for applications in which the alternator s vo...

Page 4: ...39 V 50 60 Hz Rapid response time 500 ms for a transient voltage variation amplitude of 20 Voltage setting P1 Stability setting P2 Power supply protected by 8 A fuse slow blow action tolerates 10 A fo...

Page 5: ...voltage adjustment fully anti clockwise Remotevoltageadjustmentpotentiometer centre position Run the alternator at its rated speed If the voltage does not increase the magnetic circuit should be rema...

Page 6: ...heck the resistance Speed too low Increase the drive speed Do not touch the AVR voltage pot P2 before running at the correct speed Voltage too high Adjust AVR voltage potentiometer Adjustment ineffect...

Page 7: ...tion you may require For all spare parts orders or technical support requests send your request to service epg leroy somer com or your closest contact whom you will find at www lrsm co support indicat...

Page 8: ...ur technical support depar tment can provide detailed directions on products dismounting upon request Waste hazardous materials The following components and materials need a special treatment and need...

Page 9: ...9 2017 12 e Electric Power Generation Installation and maintenance R221 A V R 5035 en...

Page 10: ...10 2017 12 e Electric Power Generation Installation and maintenance R221 A V R 5035 en...

Page 11: ...nd efficient repair support and maintenance services Trust your alternator maintenance and support to electric power generation experts Our field personnel are 100 qualified and fully trained to opera...

Page 12: ...www emersonindustrial com 2017 12 e www leroy somer com epg 5035 en Linkedin com company Leroy Somer Twitter com Leroy_Somer_en Facebook com LeroySomer Nidec en YouTube com LeroySomerOfficiel...

Reviews: