26
CONNECTIONS
Powerdrive MD2SL Installation and maintenance
5077 - 2017.12 / b
en
3.2.3 - Factory configuration of control
terminal blocks
Nota :
For more details on the parameters, please refer to the
commissioning manual ref.4617
+10V ref
AI1+
AI1-
AI2+
AI2-
0V
COM-RL1
RL1
COM-RL2
RL2
AO1
AI3
+24V ref
DO1
STO-1
DI2
DI3
STO-2
DI5
DI4
+24V ref
1
2
3
4
5
6
1
2
3
4
8
7
0V
DI1/CTP
10
9
1
2
3
4
5
6
8
7
9
PX1
PX2
PX3
Status relay (**)
Drive healthy (N/O)
Alarm relay
maximum speed (N/O)
0-10 V
speed reference
4-20 mA
speed reference
4-20 mA current image
Motor PTC (*)
Zero speed
Safe Torque Off/
Drive enable input 1
Reference selection
Reference selection
Safe Torque Off/
Drive enable input 2
Run FWD/Stop
Run REV/Stop
Note:
This configuration has been obtained from a drive with
factory settings (default parameter settings).
The STO-1 and STO-2 inputs must be closed before giving a
run command.
(*) If the motor thermal sensor needs to be connected to DI1/
PTC, set
Mtr.06 (05.70)
= Drive terminal (1).
(**) If the 2 STO inputs are not in the same status, the relay
RL1 opens.
• Modification of the Run/Stop control logic
- For "3-wire" control (jog Run/Stop):
DI4
DI5
+24V ref
7
8
9
Run FWD
Stop
List of parameters to set:
Ctr.06 (06.04)
= Run Latched (1)
I/O.10 (08.25)
=
06.39
Stop (DI5 terminal)
- For Run/Stop control with change of direction:
DI4
DI5
+24V ref
7
9
8
Run/Stop
Change of direction
List of parameters to set:
Ctr.06 (06.04)
= Run Fwd/Rev (2)
I/O.09 (08.24)
=
06.34
Run/Stop (DI4 terminal)
I/O.10 (08.25)
=
06.33
Fwd/Reverse (DI5 terminal)
• Selection of the reference via digital inputs:
DI2
DI3
Selection
0
0
Voltage speed reference (0-10 V) on analog input
AI1+, AI1-
0
1
Current speed reference (4-20 mA) on analog
input AI2+, AI2-
1
0
Preset reference 2
Spd.05 (01.22)
to be set
1
1