1.3.4 - Derating according to the temperature and switching frequency
Ambient temperature ≤ 40°C - altitude ≤ 1000 m.
Rating
Duty
Ico (A)
Flow rate : Minimum (1)
Flow rate : Optimized (1)
2kHz
3kHz
4kHz
5kHz
6kHz
2kHz
3kHz
4kHz
5kHz
6kHz
180T
Heavy duty
260
260
260
255
230
260
260
260
260
255
Normal duty
315
315
305
290
265
315
315
310
305
290
220T
Heavy duty
310
310
310
305
290
310
310
310
310
305
Normal duty
400
400
380
350
330
400
400
385
380
350
270T
Heavy duty
375
375
375
375
370
375
375
375
375
375
Normal duty
470
470
470
440
420
470
470
470
470
440
340T
Heavy duty
470
470
470
470
450
470
470
470
470
470
Normal duty
580
580
580
540
510
580
580
580
580
540
400T
Heavy duty
540
540
540
540
510
540
540
540
540
540
Normal duty
650
650
630
620
580
650
650
640
630
620
470T
Heavy duty
670
670
645
580
-
670
670
660
615
-
Normal duty
800
800
735
660
-
800
800
750
700
-
570T
Heavy duty
750
750
660
-
-
750
750
660
-
-
Normal duty
910
880
750
-
-
940
880
750
-
-
750T
Heavy duty
990
990
990
990
960
990
990
990
990
990
Normal duty
1220
1220
1180
1160
1090
1220
1220
1200
1180
1160
900T
Heavy duty
1225
1225
1215
1090
-
1225
1225
1225
1155
-
Normal duty
1500
1500
1380
1240
-
1500
1500
1410
1310
-
1100T
Heavy duty
1375
1375
1240
-
-
1375
1375
1240
-
-
Normal duty
1710
1650
1410
-
-
1760
1650
1410
-
-
1400T
Heavy duty
1850
1850
1825
1640
-
1850
1850
1850
1735
-
Normal duty
2250
2250
2070
1860
-
2250
2250
2110
1970
1700T
Heavy duty
2065
2065
1860
-
-
2065
2065
1860
-
-
Normal duty
2560
2480
2110
-
-
2650
2480
2110
-
-
For intermediate switching frequencies (3.5 - 4.5 - 5.5 kHz). the available current value will be the average of the upper frequency
and lower frequency currents.
(1) : See § «2.3.3.1 - Flow rate», page 14