Page 34
Main Rotor
1. Disconnect the generator field leads from the posi tive and
negative terminals of the rotating rectifier assembly.
2.
Connect the positive and negative leads to one clamp of the
500-volt Megger, and connect the other clamp to the shaft.
3. Apply voltage from the Megger, and measure the resistance
reading after one minute. The reading must be a minimum
of 50 megohm. If it is not, refer to the cleaning or dry out
procedures. (See Table 3.)
4. Ground the field leads to the shaft after disconnecting the
Megger for a minimum of one minute. This will allow the
voltage build up to be properly discharged.
Main Stator
1.
Disconnect power connections and all control appara tus from the
generator terminals.
2. Measure insulation resistance of each phase separately with the
two other phases shorted to the frame.
3. Use a Megger connected between the lead(s) of the phase to
be measured and generator frame. The minimum one-minute
insulation resistance must not be less than 50 megohm. (See
Table 3.)
4. Ground the leads to the frame after the one-minute Megger test.
This will allow the voltage build up to be properly discharged.
Dry Out Procedures
If the insulation resistance readings are below the recommended
minimum values specified previously, use one of the dry out
procedures described below. Select the procedure based on the size and
location of the unit, available equipment, and experience of personnel.
Before drying, remove the voltage regulator, and cover all inlet and
discharge openings. Provide an opening at the top of the machine,
preferably at the fan end, for moisture to evaporate.
Drying with External Heat:
Place heat lamps, space heaters (in
addition to the ones already supplied) or a steam pipe near the
windings. Monitor winding temperatures. Raise winding temperature
gradual ly at a rate of 50° F (28° C) per hour up to 200° F (93° C).
Measure insulation resistance at 1-hour intervals. Typically the
insulation resistance will slowly drop while the temperature is coming
up, and then gradual ly increase and level out.
Drying with AC Current in the Armature:
Short circuit the
generator terminals. Provide DC excitation to the brushless exciter
field winding. Insert a current transformer and an ammeter to read
full load current. Run the generator at rated speed. Apply excitation
to the exciter field until rated current is developed. Monitor winding
temperatures until they stabilize. Continue running until insulation
NOTE: Do not apply heat too rapidly. It
could damage the windings.
Winding
Rated
Voltage
(V)*
Insulation
Resistance Test
Direct Voltage
(V)
<1000
500
1000–2500
500–1000
2501–5000
1000–2500
5001–12000
2500–5000
>12000
5000–10000
* Rated line–line voltage for three-phase
AC machines, and line–ground voltage
for single-phase machines, and rated
direct voltage for DC machines or field
windings.
Table 3 DC Voltage to be Applied
During Insulation Resistance Tests
Summary of Contents for 22765-01
Page 2: ......
Page 3: ......
Page 4: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 163: ...Figure 1 Typical Kato generator equipped with a water to air cooler...
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......