Page 22
Foot Deflection
After alignment, check for foot deflection or “soft foot” condition
on each shim location to eliminate distortion of the generator
frame. Do this by loosing one mounting bolt at a time and checking
deflection after retightening. Deflection at the shim location from
shims under compression to a loosened condition must not exceed
0.003" (0.0762 mm).
Doweling
In case the mounting bolts loosen during operation, doweling will
prevent movement of the generator. Dowel as follows:
Check the alignment after the generator has been in operation for at
least 48 hours. If alignment is not satisfactory, realign.
Drill holes through the footpads and into the base in two mounting
pads opposite each other. Drill the holes slightly smaller than the dowel
pin.
Ream the holes to the proper diameter for the pin. Clean out chips, and
install the pins.
Electrical Connections
If the generator was subjected to a rapid change in temperature,
freezing or wet conditions during shipment or storage, measure
the insulation resistance of each winding and dry the generator, if
necessary, as described in the maintenance section below.
Make all electrical connections (main load, temperature monitoring
device, space heater, AVR) in accordance with local regulations and
national/international electrical code requirements. Check the electrical
diagrams provided with the generator or manual. The main terminals
need to be properly spaced for the load connections. Refer to Tables 5
and 6 for the proper torque values for the connections.
On larger generators grounding points are provided for properly
grounding the system to the generator frame. The grounding wire must
be sized to national/international code requirements.
Space Heaters
When the generator has optional space heaters to prevent water
condensation during long periods of downtime, connect the space
heaters so they start when the generator is turned off and stop when
the generator is switched on. Some generators with space heaters have
thermostats. The thermostat should be set above the dew point. Refer
to the electrical diagrams for the space heater characteristics.
CAUTION: The space heaters
are designed to be energized when the
generator is shut down. They are hot
enough to cause skin burns. Terminals for
power at the space heaters are live during
operation. Disconnect power to the space
heaters before removing the generator
covers.
NOTE: Alternator current machines are
intended to for continuous operation
with the neutral or at near ground
potential. Operating with one line at
ground potential should be done only
for infrequent periods of short duration,
for example as required for normal fault
clearance.
Summary of Contents for 22765-01
Page 2: ......
Page 3: ......
Page 4: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 163: ...Figure 1 Typical Kato generator equipped with a water to air cooler...
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......