background image

EN

8

 – English

IMPORTANT

 – In the programming procedure, the maximum time interval 

that can elapse between activation of one key and the next is 10 seconds. 

When this time elapses, the procedure terminates automatically, memorising 

the modifications made up until then.

6.2 - Level two programming (adjustable parameters)

All level 2 parameters are set by default as highlighted in grey in 

Table 7

, and 

may be modified at any time as explained in 

Table 8

 .

The parameters can be set on a scale from 1 to 8 . To check the value corre-
sponding to each LED see 

Table 7

 .

TABLE 6 - First level functions

LED Description 

Example

L1

 

Automatic closure

 

This function performs automatic closure of the pole after the programmed pause time. Factory setting:    

 

 

30 seconds . Value programmable from 5 to 200 seconds .

L2

 

Reclose after photo 

 

This function enables the pole to remain in Opening position for the time required for transit . When the function is  

 

 

active, operation depends on the parameter set in the function “Automatic closure”:

 

 

• with “Automatic closure” active, the Opening manoeuvre stops immediately after the photocells are  

 

 

 

disengaged and the Closure manoeuvre starts after 5 seconds .

 

 

• with “Automatic closure” not active, the pole always reaches the maximum Opening position (even if the  

 

 

photocells are disengaged beforehand) and Closure starts after 5 seconds .

L3

 

Always close

 

This function is useful in the event of a power failure, even brief . In fact if this function is active(ON), when power  

  

is 

restored, the control unit detects the pole as open and starts Closure . For reasons of safety the Closure   

  

manoeuvre is preceded by a 3-second pre-flashing interval.

L4

 

Stand by

 

The Stand-by function allows consumptions to be reduced . If active, 1 minute after the end of the manoeuvre, the  

 

 

control unit turns off the “Bluebus” output (connected devices) and all the LEDs apart from the Bluebus LED which  

 

 

will flash more slowly. When the control unit receives a command normal operation is restored. When using X-Bar  

 

 

with the Solemyo system, a longer Stand By mode must be set . This operation is performed using the Oview  

  

programmer .

L5

 

Deceleration long

 

This function enables the user to double the space for starting deceleration, both in Opening and Closing . If the  

 

 

function is deactivated, deceleration is short .

L6

 

Pre-flash

 

This function activates a pause of 3 seconds between activation of the flashing light and the start of a manoeuvre.

L7

 

Sensitivity 

When this function is set to “ON” the level of control unit sensitivity in obstacle detection can be increased  

 

 

considerably . If used as a means to read the “impact force” of the motor, the values “speed” and “motor force”  

 

 

must be set accordingly in the level 2 menu .

L8

 

Direction of motor rotation

 

This parameter enables inversion of the direction of motor rotation to enable barrier installation  on the right; the  

 

 

factory setting is “OFF” (standard motor rotation – pole closure on left) . 

 

 

 

 

  

Important

 – If the function is activated, the Opening and Closing positions must be memorised again (Paragraph 4 .5) .

TABLE 7 - Second level functions

  Input LED 

Parameter 

LED (level) 

Value 

Description

L2

L1
L2
L3
L4
L5
L6
L7
L8

Open – stop – close - stop
Open – stop – close - open 
Open – close – open - close
Apartment block (more than 2 sec . generates Stop)
Apartment block 2 (less than 2 sec . generates partial opening) .
Step by step 2 
Hold-to-run
Opening in semi-automatic mode, closing in dead man mode

Sets the sequence of commands as-

sociated with the input or the radio 

control: “Step by step”.

Function

Step by 

step

L1

L1
L2
L3
L4
L5
L6
L7
L8

5 seconds
10 seconds
20 seconds
40 seconds
60 seconds
80 seconds
120 seconds
200 seconds

Sets the pause time, i .e . the time that 

passes between the end of an ope-

ning manoeuvre and the start of an 

automatic closing manoeuvre

This parameter is only effective if the 

“automatic Closure” is active .

Time

Pause

L3

L1
L2
L3
L4
L5
L6
L7
L8

Speed 1 (30% - slow)
Speed 2 (47%)
Speed 3 (65%)
Speed 4 (82%)
Speed 5 (100%) - fast
Open V3, Close V2
Open V4, Close V3
Open V5, Close V4

Sets the motor speed during normal 

travel .

Speed

Motor

L4

L1
L2
L3
L4
L5
L6
L7
L8

Pole Open Indicator Function (24 V - 10 W)
Active if pole closed (24 V - 10 W)
Active if pole open(24 V - 10 W)
Flashing light(12 V - 21 W)
Flashing light for pole lights (24 V - 10 W)
Electric lock(24 V - 10 W)
Suction cup(24 V - 10 W)
Maintenance indicator (24 V - 10 W)

Selects the type of device connected 

to the FLASH output .

Important!

 – If the programmed set-

ting is modified, check the type of vol-

tage of the new device connected to 

the FLASH terminal and ensure that it 

corresponds to the type of voltage of 

the selected programming level .

Output

FLASH

Summary of Contents for X-Bar

Page 1: ...ione e l uso FR Instructions et avertissements pour l installation et l utilisation ES Instrucciones y advertencias para la instalaci n y el uso DE Installierungs und Gebrauchsanleitungen und Hinweise...

Page 2: ......

Page 3: ...I 1 A B D C D B 3 2 179 5 mm 300 mm 1146 mm 826 mm 3000 mm b a l d e c i g f h...

Page 4: ...II 5 A B C 4...

Page 5: ...III 9 10 90 6 A C B 7 8 B A...

Page 6: ...IV 14 A B 15 A B 11 A B 12 13 A B...

Page 7: ...V 18 17 16 A B...

Page 8: ...VI 20 21 OK O O 19 A B C D...

Page 9: ...VII 22 A 2cm 1cm 23 A B C D...

Page 10: ...VIII 24 26 27 180 25 C C A B...

Page 11: ...L N 28 29 NC NC NO NO C C FLASH MOTB OPEN CLOSE TX RX BLUEBUS STOP OPEN CLOSE P P 31 Op en Sto p Se t Clo se Fuse 1AT L1 L2 L3 L4 L5 L6 L7 L8 32 Op en Sto p Se t Clo se Fuse 1AT L1 L2 L3 L4 L5 L6 L7...

Page 12: ...X Op en St op Se t Cl os e Fuse 1AT L1 L2 L3 L4 L5 L6 L7 L8 34 35 36 A A B...

Page 13: ...XI STOP 37 A B 38 A B C D...

Page 14: ...XII 51 O p e n L 1 L 2 L 3 L 4 L 5 L 6 L 7 L 8 S t o p S e t C lo s e Fuse 1AT Open Stop Set Close 49 F2 F1 50 48 O pe n L1 L2 L3 L4 L5 L6 L7 L8 St op Se t Cl os e Fuse 1AT 52...

Page 15: ...ation disconnected from the power mains If the power disconnect device is not visible from the location of the automation before starting work ing a suitable notice must be affixed on the power discon...

Page 16: ...es The product does not contain and or release hazardous substances in con formity with the provisions of the standard EN 13241 1 point 4 2 9 and ac cording to the list of substances stated in the web...

Page 17: ...talled is in a sheltered location and pro tected against the risk of accidental impact 3 2 Product application limit Before installing the product ensure that all values specified in the chapter Techn...

Page 18: ...ll parts 09 Position the pole plug Fig 23 A the upper impact protection must be inserted by at least 2 cm the lower impact protection must protrude by 1 cm B Insert the pole plug C Secure the plug usi...

Page 19: ...chanical stop is moved IMPORTANT The deceleration points are calculated automatically by the control unit after the position search phase at least 2 or 3 complete manoeu vres must be performed before...

Page 20: ...t Fig 44 04 Disconnect the mains power and fit the connector as shown in Fig 45 4 9 3 Solemyo System photovoltaic supply X Bar is designed to be powered with the Solemyo SYKCE photovoltaic system To c...

Page 21: ...the device engages changing from the active status to alarm status and vice versa and that the envisaged action is gen erated in the control unit for example movement inversion in the Closing manoeuv...

Page 22: ...tion both in Opening and Closing If the function is deactivated deceleration is short L6 Pre flash This function activates a pause of 3 seconds between activation of the flashing light and the start o...