background image

EN

English – 

7

TABLE 5 - Programming procedure (first level functions)

01.

  Press and hold down the “

Set

” key for approx. 3 seconds;

02.

  Release the key when LED 

L1

 starts flashing;

03.

  Press keys “

s

” or “

t

” to move from the flashing led to the led associated with the function to be modified;

04.

  Press “

Set

” to change the status of the function:

 

(short flash = OFF; long flash = ON)

05.

  Wait 10 seconds (maximum time) to exit the programming mode.

Note 

– During this procedure, points 03 and 04 need to be repeated when programming other functions to “ON” or “OFF” during the phase itself .

SET

SET

SET

L1

or

3 s

10 s

The control unit has 3 keys 

OPEN

 (

s

), 

STOP

 (

Set

), 

CLOSE

 (

t

) (

Fig. 49

) that 

can be used both for controlling the unit during testing and for programming 

the available functions .

The programmable functions available are divided into 2 levels and their relative 

operating status is displayed by means of the 8 LEDs (

L1

L8

) on the control 

unit (LED lit = function active; LED off = function not active).

Programming keys:
OPEN

 (

s

): the “OPEN” key enables control of pole opening or can be used, 

during programming, to move the programming point up .

STOP

 (

Set

): the “STOP” key enables the user to stop the manoeuvre; if pressed 

for more than 5 seconds, it enables entry to programming mode .

CLOSE

 (

t

): the “CLOSE” key enables control of pole closing or can be used, 

during programming, to move the programming point down .

CAUTION! – During a manoeuvre (Open or Close) all three keys have 

the STOP function: all manoeuvres in progress are stopped.

6.1 - Level one programming (ON-OFF functions)

All level 1 functions are set by default to “

OFF

” and may be modified at any 

time as explained in 

Table 5

 . To check the value corresponding to each LED 

see 

Table 6

 .

IMPORTANT 

– The programming procedure has a maximum interval of 10 

seconds admissible between the activation of one key and the next. When this 

time interval elapses, the procedure quits automatically, saving the changes 

made up until that time .

CONTROL UNIT PROGRAMMING

6

each size, in reflective material (e.g. mirror or white gloss paint) and three 

sides in opaque material (e .g . black matt paint) . To test the photocells posi-

tioned at 50 cm from the ground, the parallelepiped must be placed on the 

ground or raised at 50 cm in the case of photocells placed at 1 m from the 

ground .

 

When testing one pair of photocells, the test specimen must be positioned 

exactly at the centre of the pole with the 20 cm sides facing the photocells 

and moved along the entire length of the pole (

Fig. 46

) .

 

When testing two pairs of photocells, the test must first be performed 

individually for each pair of photocells, using one test specimen, and then 

repeated using two test specimens .

 

Each test specimen must be positioned laterally with respect to the centre 

of the pole, at a distance of 15 cm sides and then moved along the entire 

length of the pole (

Fig. 47

) .

 

During these tests, the test specimen must be read by the photocells in any 

position along the entire length of the pole .

Ensure there is no interference between the photocells and other devices, 

by intercepting the optic axis joining the two photocells by means of a cyl-

inder (diameter 5 cm, length 30 cm, 

Fig. 48

): pass the cylinder first close to 

the TX photocell, then close to the RX and lastly at the centre between the 

two .

 

Ensure that in all cases the device engages, changing from the active 

status to alarm status and vice versa, and that the envisaged action is gen-

erated in the control unit (for example movement inversion in the Closing 

manoeuvre) .

8  Check protection against the risk of lifting:

 on automations with verti-

cal movement, it must be ensured that there is no risk of lifting . This test can 

be performed as follows: hang a weight of 20 kg mid-way along the pole 

(for example, a sack of gravel), activate an Opening manoeuvre and ensure 

that during operation the pole does not exceed the height of 50 cm from 

the closing position. If the pole exceeds this height, reduce the motor force 

(see chapter 6 - Table 7) .

If hazardous situations generated by the moving poles are protected by 

means of impact force limitation, measure the force as specified in the 

standard EN 12445. If motor force control is used as auxiliary function with 

the system for reduction of impact force, test and identify the setting that 

obtains the best results .

10  Check efficiency of the release system: 

place the pole in the Closing 

position and manually release the gearmotor (see paragraph 3 .6) ensuring 

that there is no difficulty with this procedure. Ensure that the manual force 

required to move the pole on opening is no greater than 200 N (approx. 20 

kg); the force is measured perpendicular to the pole and at 1 m from the 

rotation axis. Lastly, ensure that the key required for manual release is avail-

able in the vicinity of the automation .

11  Power supply disconnection system check:

 by using the power dis-

connect device, and disconnecting any buffer batteries, ensure that all leds 

on the control unit are off and that the pole remains stationary when any 

commands are sent. Check efficiency of the locking device to prevent inad-

vertent and/or unauthorised reconnection .

5.2 - Commissioning

Commissioning can only be performed after positive results of all test 

phases. Partial or “makeshift” commissioning is strictly prohibited.

Compile and provide the automation owner with the “

CE Declaration of 

conformity - Appendix I

”, at the end of this manual, in the removable sec-

tion .

Compile and provide the automation owner with the form “

Operation 

Manual

” at the end of this manual, in the removable section .

Compile the form “

Maintenance schedule

” containing all maintenance 

instructions for all devices in the automation and forward it to the owner . 

In the case of X-Bar, this form is present at the end of this manual, in the 

removable section .

Before commissioning the automation, ensure that the owner is adequately 

informed of all associated risks and hazards .

Permanently affix on the pole the label in the pack regarding the gearmotor 

manual release and locking operations .

ONLY for installations NOT IN CONFORMITY with the criteria stated in 

chapter 1.3.1 of this manual: produce the technical documentation of 

the automation, which must include the following documents: an overall 

drawing of the automation, the wiring diagram of all connections made, an 

assessment of all risks present and relative solutions adopted (see forms to 

be compiled on the website 

www.niceforyou.com

), declarations of con-

formity of manufacturer of all devices used (for X-Bar see appendix II) and 

the declaration of conformity compiled by the installer .

 

Affix a dataplate on the barrier, specifying at least the following data: type of 

automation, name and address of manufacturer (responsible for commis-

sioning), serial number, year of construction and CE mark .

Summary of Contents for X-Bar

Page 1: ...ione e l uso FR Instructions et avertissements pour l installation et l utilisation ES Instrucciones y advertencias para la instalaci n y el uso DE Installierungs und Gebrauchsanleitungen und Hinweise...

Page 2: ......

Page 3: ...I 1 A B D C D B 3 2 179 5 mm 300 mm 1146 mm 826 mm 3000 mm b a l d e c i g f h...

Page 4: ...II 5 A B C 4...

Page 5: ...III 9 10 90 6 A C B 7 8 B A...

Page 6: ...IV 14 A B 15 A B 11 A B 12 13 A B...

Page 7: ...V 18 17 16 A B...

Page 8: ...VI 20 21 OK O O 19 A B C D...

Page 9: ...VII 22 A 2cm 1cm 23 A B C D...

Page 10: ...VIII 24 26 27 180 25 C C A B...

Page 11: ...L N 28 29 NC NC NO NO C C FLASH MOTB OPEN CLOSE TX RX BLUEBUS STOP OPEN CLOSE P P 31 Op en Sto p Se t Clo se Fuse 1AT L1 L2 L3 L4 L5 L6 L7 L8 32 Op en Sto p Se t Clo se Fuse 1AT L1 L2 L3 L4 L5 L6 L7...

Page 12: ...X Op en St op Se t Cl os e Fuse 1AT L1 L2 L3 L4 L5 L6 L7 L8 34 35 36 A A B...

Page 13: ...XI STOP 37 A B 38 A B C D...

Page 14: ...XII 51 O p e n L 1 L 2 L 3 L 4 L 5 L 6 L 7 L 8 S t o p S e t C lo s e Fuse 1AT Open Stop Set Close 49 F2 F1 50 48 O pe n L1 L2 L3 L4 L5 L6 L7 L8 St op Se t Cl os e Fuse 1AT 52...

Page 15: ...ation disconnected from the power mains If the power disconnect device is not visible from the location of the automation before starting work ing a suitable notice must be affixed on the power discon...

Page 16: ...es The product does not contain and or release hazardous substances in con formity with the provisions of the standard EN 13241 1 point 4 2 9 and ac cording to the list of substances stated in the web...

Page 17: ...talled is in a sheltered location and pro tected against the risk of accidental impact 3 2 Product application limit Before installing the product ensure that all values specified in the chapter Techn...

Page 18: ...ll parts 09 Position the pole plug Fig 23 A the upper impact protection must be inserted by at least 2 cm the lower impact protection must protrude by 1 cm B Insert the pole plug C Secure the plug usi...

Page 19: ...chanical stop is moved IMPORTANT The deceleration points are calculated automatically by the control unit after the position search phase at least 2 or 3 complete manoeu vres must be performed before...

Page 20: ...t Fig 44 04 Disconnect the mains power and fit the connector as shown in Fig 45 4 9 3 Solemyo System photovoltaic supply X Bar is designed to be powered with the Solemyo SYKCE photovoltaic system To c...

Page 21: ...the device engages changing from the active status to alarm status and vice versa and that the envisaged action is gen erated in the control unit for example movement inversion in the Closing manoeuv...

Page 22: ...tion both in Opening and Closing If the function is deactivated deceleration is short L6 Pre flash This function activates a pause of 3 seconds between activation of the flashing light and the start o...

Reviews: