12 - ACCESSORY INPUTS AND OUTPUTS 

GATE OPERATOR ACCESSORY INPUTS:
Auxiliary Inputs 1 (16) and 2 (18):

 These digital inputs may be connected 

to the digital outputs of accessories and programmed to activate or control 

the gate operator in a number of different modes. Shorting the pins through a 

dry contact activates the programmed settings for these inputs. These inputs 

are programmed in the “FUNCTION Auxiliary I/O” menu. 

SAFETY LOOP Input:

 (22) Dry contact input that can be programmed for an 

inductive safety loop or photo-eye detector. Shorting pin 22 to GND reverses 

a closing gate to the full open position. The opened gate is held opened for 

as long as the LOOP input is active. 

SHADOW (LOOP 1) Input:

 (24) Dry contact input that can be programmed 

for an inductive safety loop or photo-eye detector. Shorting the LOOP 1 input 

(24) to GND maintains an OPEN gate fully open and a CLOSED gate fully 

closed until deactivated. 
Setting the LOOP1 input to “Photo Mode” causes the moving gate to stop, 

then reopens the gate when the LOOP1 input is deactivated. 

ENTRAPMENT (LOOP 2) Input:

 (26) Dry contact input that can be 

programmed for an inductive safety loop or photo-eye detector. Shorting the 

LOOP2 input (26) to GND while the gate is opening cause the gate to close 

to the fully closed position. This loop input is intended for use with safety 

sensors to prevent entrapment between the opening gate and an adjacent 

wall or structure. 

Edge Input:

 (28) This input may be configured as “DIGITAL” or “ANALOG” 

as required by the sensor type. When configured as “DIGITAL”, this is a dry 

contact input; otherwise when configured as “ANALOG”, the input must 

measure 8200ohms. When the input is activated it stops the gate regardless 

of direction of travel, momentarily reverses it then stops. 

Exit Input:

 (30) Dry contact input for a vehicle exit sensor. Shorting this 

input to GND opens gate from the closed position and holds gate open with 

maintained input or reverses gate if closing. 

Fire Input:

 (32) Dry contact input for a fire department control switch. Opens 

the gate and holds the gate open until the control switch is deactivated. This 

input is “hold to run”. Auto-close is disabled when this input is activated. Also 

clears hard shutdown. 

GUARD STATION
Guard Station Open:

 (34) Dry contact input for a guard station open switch. 

Momentarily shorting the digital input to GND opens the gate to the full open 

position with the subsequent auto-close feature enabled. 

Guard Station Stop:

 (35) Dry contact input (Normally Closed) for a guard 

station stop switch. Momentarily opening this input stops the opening gate at 

its current position. While this input is activated, all other inputs are disabled 

and are not functional. 

Guard Station Close:

 (36) Dry contact input for a guard station close 

switch. Momentarily shorting the digital input to GND closes the gate (master 

and slave). 

RADIO
Radio Open:

 (39) Dry contact input for an accessory radio open switch. 

Momentarily shorting the digital input to GND opens the gate to the full open 

position with the subsequent auto-close feature enabled. 

Radio Close:

 (40) Dry contact input for an accessory radio close switch. 

Momentarily shorting the digital input to GND closes the gate. 

Radio Input:

 Open/Close: (39 and 40) If you tie open and close together the 

unit will operate as a Step by Step command each time the input is shorted 

to GND, it will either OPEN, STOP or CLOSE.

12.1 - Outputs 

Figure - BOARD OUTPUTS 

GATE OPERATOR ACCESSORY OUTPUTS:
OUT1 and OUT2:

 Individual, isolated relays provide COMMON, NORMALLY 

OPEN, and NORMALLY CLOSED dry contacts for switching accessories 

based on programming of the “Auxiliary IO” function. These outputs are 

programmed in the “FUNCTION Auxiliary I/O” menu. 

Magnetic Lock:

 Provides fused power (1.85A max) and isolated relay 

COMMON, NORMALLY OPEN, and NORMALLY CLOSED dry contacts for 

electrically powered and maintained magnetic locks. The output time for 

magnetic lock activation/deactivation may be adjusted from 0 to 5 seconds. 

Lamp:

 Provides fused power (1.85A max) to drive a flashing warning lamp 

to indicate gate operation. This output is active when the gate is operating 

(Opening and Closing). Lamp Delay sets the amount of time the lamp 

accessory output is activated prior to gate movement. Settings from 0 to 5 

seconds with a step of 0.5 seconds. 

Alarm:

 Provides fused power (0.5A @ 12VDC) to drive an alarm siren 

to signal the occurrence of a hard shutdown, caused by 2 consecutive 

entrapment events (signals). This alarm output is reset by pressing the “Reset 

Hard Shutdown” button on the front panel or activating the “FIRE” input. 

12.2 - Inputs 

Figure - INPUTS 

Summary of Contents for CBOX1K

Page 1: ...Nice Apollo Control Box Vehicular Gate Operator Control Revision 1 0 0 0_6 2014 CBOX1K...

Page 2: ......

Page 3: ...ion 18 9 3 Push to open installation 19 9 4 Actuator mounting 19 9 5 Actuator wiring 20 9 6 Gate bracket mounting 20 9 7 Limit motor connection to the board 21 9 8 Limit switch adjustment 21 9 9 Setti...

Page 4: ...ction Dry contact inputs are provided for loop probe and photoelectric detectors as well as edge sensors guard station and fire department control of gate opening and closing Voltage outputs 12VDC and...

Page 5: ...he moving gate system No entry into the gate is ever authorized and should be prevented by whatever measures are required for that specific installation Care should always be used during installation...

Page 6: ...nal gate types 4 3 15 Any existing manual gate latches shall be removed or disabled when an automatic gate system is installed Use only mag locks controlled by the system 3 3 Gate system safety device...

Page 7: ...nt any device that operates the gate opener where the user can reach around over or through the gate to operate the controls Controls should be mounted at minimum 8 feet away from any moving part of t...

Page 8: ...ontrol board for STANDBY operation See section 16 for information on STANDBY mode Battery Connect wires to the battery terminal block The positive wire of the battery connects to the left terminal mar...

Page 9: ...included The CBOX1K control box is used for many different model operators The following pages show installation guides for these models Refer to the correct model operator section for instructions on...

Page 10: ...IDENTIFICATION Control Box 11111B T5 Actuator NT TO5012 T7 Actuator NT TO7012 Operator QTY QTY QTY QTY QTY QTY T5ETL 1K 1 1 1 1 0 1 T7ETL 1K 1 0 1 1 1 1 8 NT T51K NT T71K INSTALLATION NT T51K NT T71K...

Page 11: ...the rear pivot bracket using the T5 or T7 graph provided on the next pages The graphs serve to establish the dimensions A and B and the value of the maximum opening degree of the gate Important The va...

Page 12: ...5 16 6 11 16 7 1 16 7 1 2 7 7 8 8 1 4 8 11 16 9 1 16 9 7 16 9 13 16 10 1 4 10 5 8 11 7 16 11 3 15 16 4 5 16 4 3 4 5 1 8 5 1 2 11 13 16 12 3 16 12 5 8 13 13 3 8 Recommended installation line NOT RECOM...

Page 13: ...1 7 16 11 13 16 5 5 16 6 5 16 6 11 16 7 1 16 7 1 2 7 7 8 8 1 4 8 11 16 9 1 16 9 7 16 9 13 16 10 1 4 10 5 8 11 7 16 11 NOT RECOMMENDED VALUES AREA Recommended installation line C 4 1 2 3 1 2 5 1 8 6 6...

Page 14: ...of the T5 T7 to the attachment bracket using the supplied bolt and washer with a 13mm metric socket as shown Be careful not to over tighten the bolt 2 3 1 Unlock the strain relief bushing located on t...

Page 15: ...2 into the connection labeled Motor 2 Note Motor 1 Make sure motor lead connector is plugged in below the limit 5 pin terminal connector T5 and T7 Limit and Encoder wiring T5 and T7 Motor wiring green...

Page 16: ...e RED and BLACK motor leads Using the OPEN button on the front of the Control board hold the button down until the gate reaches the fully intended open position Adjust the Open Limit Switch until the...

Page 17: ...x 11111B 816 Actuator with 8 harness 816X Actuator with 38 harness Supplied with 16501K Pivot Arm 1116 2 with 16501K Gate attach bracket 10025215 2 with 16501K Bolt kit 2 with 16501K 9 15501K 16501K I...

Page 18: ...rate of speed of the gate it is critical that the measurements below are followed The pivot arm may need to be cut to achieve the correct placement of the actuator mounting hole Measurements are take...

Page 19: ...g hole Measurements are taken from the center of pivot of the gate hinge Vertical position of pivot arm DIRECTION OF OPENING GATES CLOSED HINGE POST HINGE POST LEFT HAND SWING RIGHT HAND SWING TOP VIE...

Page 20: ...n below These connections enable the Apollo 816 limit switch and smart sensor inputs into the gate controller 816 limit switch and smart sensor wiring Connect the Apollo 816 actuator cable to the 5 pi...

Page 21: ...pin connector for motor 1 into the connection labeled Motor 1 on the controller as shown For a dual gate installation install the 5 and 3 pin and connector for motor 2 into the connection labeled Mot...

Page 22: ...te limit wires CLOSE LIMIT Red CLOSE LED 3 Using the CLOSE button on the front of the Control Board hold the button down until the gate reaches the fully intended closed position 4 Adjust the Closed L...

Page 23: ...23 10 1 PARTS IDENTIFICATION Control Box CBOX1K Chassis CHBOX350 Arm Assembly ABOX350 10 35001K 36001K INSTALLATION 35001K 36001K INSTALLATION...

Page 24: ...istances are from the hinges square to the center of the mounting post Longer gates should operate at slower speeds E C B D A OPTIMUM SETTING SHOWN IN GREEN A Open Degrees B Inches C Inches D Inches E...

Page 25: ...the gate in the closed position and level for proper operation 3 Conduit should be considered at this time for cable routing from the control box to the chassis assembly Welding mounting bracket Weld...

Page 26: ...to the primary arm using a 1 2 x 2 1 4 hex bolt brass washers and lock nut The stop tab should be positioned away from the gate Install the aluminum adjustable arm to the secondary arm using the 1 2...

Page 27: ...te attach bracket to the gate Note Permanent welds or bolt attachment should be completed once limits are set Make sure that the primary arm is locked into the stop tab on the secondary arm Located in...

Page 28: ...wiring White Close limit Orange Open Limit Green Limit Common Green Orange White 1 2 3 4 5 3500 3600 Limit Wiring White Close limit Orange Open Limit Green Limit Common Green Orange White 1 2 3 3500...

Page 29: ...N limit switch is now set Note if red LED illuminates reverse orange and white limit wires CLOSE LIMIT Red CLOSE LED 3 Using the CLOSE button on the front of the Control Board hold the button down unt...

Page 30: ...irection MUST be set prior to learning the board 2 Press and hold the Open or Close button on the gate controller until the gate is 50 open 3 Press ENTER to allow the control board to scan for attache...

Page 31: ...ars hard shutdown GUARD STATION Guard Station Open 34 Dry contact input for a guard station open switch Momentarily shorting the digital input to GND opens the gate to the full open position with the...

Page 32: ...cting other assigned remote controls This procedure needs to be performed at the Nice Plug In Receiver with the affected Nice remote control 1 Press and hold the button on the side of the Nice receive...

Page 33: ...for the operator connection The wire table is based on stranded copper wire Wire run calculations are based on a 110 VAC power source with a 3 voltage drop on the power line plus an additional 10 red...

Page 34: ...g edge of the closing gate The EXIT sensor input is provided to activate to open the gate or re open a closing gate upon sensing an exiting vehicle Figure FIRE DEPT INPUT 15 2 Magnetic lock connection...

Page 35: ...ty equipment and connections Clean equipment and connections 16 6 Improper broken inadequately supported equipment wiring and conduit loose connections of terminals and loose ferrules 16 7 Poor mechan...

Page 36: ...lls Figure LAYOUT FOR IN GROUND LOOPS Entrapment Protection Inputs Typical Installation Diagram Utilizing Photocells Figure LAYOUT FOR PHOTOCELLS Loop Safety Loop Safety Loop Shadow Loop Exit 4 Min fr...

Page 37: ...at the control panel before making any electric service power connection Be aware of all moving parts and avoid close proximity to any pinch points Know how to operate the manual release Adjust the un...

Page 38: ...Stop gate movement Close the gate Figure GENERAL BOARD OVERVIEW THE PROGRAMMING BUTTONS INDICATED IN THE ABOVE REFERENCE SHOULD BE USED ONLY AFTER UNDERSTANDING THE MANUAL AND ITS RELATION TO THE PROG...

Page 39: ...itivity of sudden impact force to the moving gate on a scale of 1 to 10 1 being most sensitive ESC Exit the FORCE menu 20 2 Speed Max Sets the limit of maximum allowed gate speed on a scale of 20 to 1...

Page 40: ...dvance Settings The following settings are available for customizing the gate operator as required by the customer s installation requirements Set Language English Spanish French Set clock 12H 24H Set...

Page 41: ...perator or system intended for use in a commercial location or building such as a multi family housing unit five or more single family units hotels garages retail store or other building servicing the...

Page 42: ...Table 3 SYMPTOM S POSSIBLE SOLUTION Check that power to the circuit board is turned ON Check terminal block wiring for loose or broken wires If voltage measures OK check the terminal block Check the...

Page 43: ...43 1 1 2 2 A A B B COMPANY NICE APOLLO NAME CONTROL BOX GENERAL OVERVIEW 18 22 18 18 8 32...

Page 44: ...LE POLE 1115 1 4 SWITCH PUSH BUTTON CNTRL BOX 1119 1 5 1050 CIRCUIT BOARD 1050 1 6 1050 BOARD MOUNT KIT 10055090 1 7 NICE RECEIVER 318NPI 1 8 1 1 2 2 A A B B TITLE Company 2 6 8 3 7 4 5 1 Note Control...