18

NIBE PB 10

Installation

Troubleshooting

The unit has stopped:

When the unit has stopped, before cutting the current, 
check what LD1, LD2 or LD3 indicates, this is of great help 
when troubleshooting.

 

Q

Check that there are pellets in the container/storage 
area.

 

Q

Check that the external screw works (feeds in pellets).

 

Q

Clean the grate.

 

Q

Restart.

The unit does not start:

 

Q

Check the door frame switch.

 

Q

Check the boiler thermostat.

 

Q

Check that the unit is powered. Also check the separa-
ble contact. 

 

Q

Check the fuses in the fuse box.

 

Q

Cut the current and press in the reset button on the 
overheating protection. Reinstall the protection and 
switch on the current to the unit.

Fan and ignition ok, but pellets not fed in:

 

Q

The thermal screw motor protection may have de-
ployed. Cut the current and wait 10 minutes.

Cut the current and check the glass fuses (20 x 5 mm), 
and, if necessary, replace them (see control electronics 
board).

 

Q

Ignition/glow coil 

6.3A slow.

 

Q

Fan  

 

800 mA quick.

 

Q

Supply screw    

1.0A quick.

Troubleshooting

Fuel is supplied, but ignition does not occur: 

Checks

Corrective 
action

- fuse (6.3 A) on circuit board blown

- replace

- glow coil does not become hot

- replace

- glow coil electrical connections damaged - repair

Pellets feed in and ignite, but fan does not start:

Checks Corrective 

action

- blown fan motor fuse on circuit board

- replace

- fan motor faulty

- replace

Pellets feed in, ignite and fan starts, but the screw 
does not restart:

Checks

Corrective 
action

- photocell dirty

- clean

- photo cell faulty

- replace

Unit stops, but works after restart:

The photo cell has been affected due to incorrect combus-
tion 

Checks

Corrective action

- sensitivity on P5

- check LD1 
when firing

(LD1 must come 
on when the 
burner is lit)

Work behind screwed covers may only 

be carried out under the supervision of a 

qualified electrician.

Note!

Summary of Contents for PB 10

Page 1: ...MOS GB 0951 2 PB 10 511891 INSTALLATION AND MAINTENANCE INSTRUCTIONS NIBE PB 10 LEK...

Page 2: ......

Page 3: ...________________ 8 Adjusting control electronics ________________________ 9 Adjusting the burner ____________________________ 10 Trimming tips __________________________________ 11 Check points after...

Page 4: ...even draft in the boiler and prevent back burn ing accidents The vacuum in the boiler hearth must be a minimum of 5 6 Pa 0 5 0 6 mm VP Q The pellets must be stored in a dry and well ventilated place...

Page 5: ...3 NIBE PB 10 User guide General System diagram M...

Page 6: ...of the boiler s water jacket The burner has an extended cover that directs the ame for ward For installation in boilers without a spacer connector the extended cover can be cut to direct the ame upwar...

Page 7: ...installed the entire length of the chimney Adjustment with the instrument should also be carried if the pellet size or quality is changed There must not be any overpressure in the replace at any time...

Page 8: ...burner and any from the boiler Q Remove any cinders from the ignition pod plate 107 and clean the grate Note The at part of the grate must be slid in as far as possible under the ignition pod plate P...

Page 9: ...e 9 At thermostat cut off the fan continues to run until the photocell no longer registers re The extinguish ing time is activated in this mode which corresponds to 150 seconds 10 After extinguishing...

Page 10: ...Continuous yellow and green light at the same time on LD2 and LD3 Fault on screw supply Flashing yellow light on LD2 Photocell fault Flashing red light on LD1 Fan fault Changing times and fan damper...

Page 11: ...l has lost light in the burner P4 Overrun time at 25 supply 45 450 Time between igni tion and normal operation P5 The sensitivity of the photocell 0 9 9 max re light intensity 0 min re light intensity...

Page 12: ...burner using a flue gas analysis instrument for optimal combustion Note P1 P2 P3 P4 P5 Supply time Firing supply Extinguishing time Overrun time Photocell 0 Flashes 30 seconds 1 5 seconds 30 seconds...

Page 13: ...s temp 170 240 C If the ue gas temp is too high the amount of surplus air is too great In the event of low temperatures check the boiler s turbulators if the boiler is equipped with them These can be...

Page 14: ...the connection pipe senses heat 90 C the supplier screw stops If the overheating protection deploys it must be reset This is carried out by rst cutting the main power and then unscrewing the cover on...

Page 15: ...spond to a certain value The most important value to you as an installer is the ring supply P2 It controls the supplied output in the burner the higher the output the more ashes the lower the output t...

Page 16: ...iagram Wiring diagram Network zero Network phase Photocell Protective earth Thermostat phase Glow coil phase Glow coil zero Fan phase Fan zero Supply screw phase Supply screw zero Photocell Glow coil...

Page 17: ...ction PELLUX 200 Connect the burner cable s black wire to plinth 11 terminal 3 Connect the blue wire to plinth 11 terminal 2 Connect the brown wire to plinth 11 terminal 1 Take the switch supplied wit...

Page 18: ...16 NIBE PB 10 Installation Electrical connection of PB 10 to PELLUX...

Page 19: ...17 NIBE PB 10 Installation Electrical connection of PB 10 to PELLUX...

Page 20: ...es Cut the current and check the glass fuses 20 x 5 mm and if necessary replace them see control electronics board Q Ignition glow coil 6 3A slow Q Fan 800 mA quick Q Supply screw 1 0A quick Troublesh...

Page 21: ...29 103 36 9 LEK 104 105 List of components 5 Doorframe switch 6 Overheat protection 9 Connection supply 11 Connection pellet screw 29 Relay card 36 Fan 103 Serial number plate 104 Feed pipe 107 Igniti...

Page 22: ...20 NIBE PB 10 Miscellaneous Dimensions Dimensions Leave approximately 750 mm free area around the burner to facilitate service and maintenance...

Page 23: ...Electrical connections 230V 10 A Installation Electrical Authorisation Fuel volume External container 250 litres accessory Dimensions Length 570 mm Height 470 mm incl ller pipe Width 200 mm fan cover...

Page 24: ...door for VEDEX 1000 3300 Part no 089 878 LEK Pellet burner door with spacer conector for CITY ATTACK COMBI VX before 2005 Part No 420 088 Part No 420 089 Pellet burner door for VEDEX 3000 Part no 089...

Page 25: ...ling the draft limiter for chimneys The draft limiter has a newly developed design that makes installation on the ue pipe possible in all positions Vertical angled as well as horizontal The draft limi...

Page 26: ...screw angle and hose length The hose should have gently sloping bends to prevent ne particles from collecting inside it The outlet section of the screw must be slightly recessed in relation to the in...

Page 27: ...e drive section s outlet 5 Use the supplied drill to make a hole straight through the joint sleeve and joint pipe and tighten using the supplied screw 6 Connect to a 220 230 V power source and test ru...

Page 28: ...26 NIBE PB 10...

Page 29: ...27 NIBE PB 10...

Page 30: ...28 NIBE PB 10...

Page 31: ......

Page 32: ...l 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk www volundvt dk NIBE Systemtechnik GmbH Am Reiherpfahl 3 29223 Celle Tel 05141 7546 0 Fax 05141 7546 99 E mail info nibe de www nibe de CH NIBE W...

Reviews: