General
Connect KVR 10 to the heat pump's condensation water
trough using the supplied hose clamp.
■
Pipe installation must be carried out in accordance
with current norms and directives.
■
We recommend three ways of leading off condensa-
tion water; to an indoor drain (subject to local rules
and regulations), stone caisson, gutter drainage or
other frost free collection point.
■
When casting the base, the holes for KVR 10 must have
an internal diameter of 110 mm.
■
Route the pipe downward from the air/water heat
pump.
■
The insulation of KVR 10 must seal against the bottom
of the product's condensation water trough.
■
The drain from KVR 10 must be positioned at frost free
depth or indoors (subject to local rules and regula-
tions).
■
The drain from KVR 10 must be able to receive up to
100 litres of condensation water per day.
■
The installation must be equipped with a water seal
where air circulation can occur in the condensation
water pipe.
Drain indoors
Water seal
Joint
The condensation water is lead to an indoor drain (sub-
ject to local rules and regulations).
Route the pipe downward from the air/water heat pump.
The condensation water pipe must have a water seal to
prevent air circulation in the pipe.
KVR 10 spliced as illustrated. Pipe routing inside house
not included.
Condensation water pipe KVR 10
Chapter 2 |
Pipe connections
6