Nibe FIGHTER 310P Installation And Maintenance  Instruction Download Page 17

Electrical connections

15

For the Installer

FIGHTER 310P

All electrical equipment except for the outdoor sensor 
has been connected at the factory.
Disconnect the heat pump before insulation testing the 
house wiring.

FIGHTER 310P does not include an isolator switch on 
the  incoming  electrical  supply.  The  installation  must 
therefore be preceded by a circuit-breaker with at least 
a 3 mm breaking gap according to applicable norms.
The heat pump must be installed via an isolator switch. 
The  supply  to  the  heat  pump  is  connected  to  termi-
nal (9) via a strain relief. Connection must not be car-
ried out without the permission of the electricity sup-
plier  and  under  the  supervision  of  a  qualified  electri-
cian. The cable entry conduit is dimensioned for cable 
with a max Ø 19 mm.
The power is controlled via a contactor which is oper-
ated by a microprocessor.
The temperature limiter (6) cuts off the supply to the 
immersion heater if the temperature rises to 88 °C; it 
can be manually reset by pressing the button on the 
temperature limiter.
The temperature limiter (169) for the compressor cuts 
off  the  supply  to  the    compressor  if  the  temperature 
rises to 88 °C; it can be manually reset by pressing the 
button on the temperature limiter.

As standard the output power of the immersion heater 
is 8.0 kW. 
The supplied output is 6.0 kW.
Switching between different power outputs is done by 
opening the front panel (see under “Service” — “Open-
ing  the  front  panel”),  and  moving  certain  cables  as 
described  under  “Electrical  diagram”,  “Changing  the 
output”.

Connection

Power rating as set at the 

factory

Max current

NOTE!

Reset the temperature limiter,  

it may have tripped during transport.

NOTE! 

The switch  (8) must not be moved 

from  “0” until the boiler has been 

filled with water. The temperature 

limiter, thermostat, compressor and 

the immersion heater can otherwise  

be damaged.

The  automatic  heating  control  system,  circulation 
pump (16) and its cabling, are internally fuse protected 
with a miniature circuit breaker (7).

The temperature limiters are accessible behind the top 
front cover and are positioned to the right of the pan-
el.
The temperature limiters are reset by firmly pressing 
in its buttons.
Resetting  the  temperature  limiter  may  only  be  carried 
out  by  a  qualified  installation  engineer  after  checking 
the electrical equipment.

Resetting  

the temperature limiter

NOTE! 

The electrical installation, wiring and 

any service work must be done in strict   

conformity to current regulations 

under the supervision of a qualified 

electrician.

  Immersion heater output  Max current 

Breaker 

 

(kW) 

(A) 

(A)

 

  6,0 

30,3 

32 

 

  8,0 

39,0 

40

FIGHTER 310P is delivered with an 8 kW immersion 
heater (1). It is started and stopped via the microproes-
sor card (34). If a failure occurs there is a temperature 
limiter (6) (thermal cut-out) that is stopping the immer-
sion heater. An immersion heater without a  tempera-
ture limiter is not allowed to be mounted.

Immersion heater

Art.nr.  611603

2

1

bar

3

0

4

2

1

bar

3

0

4

2

1

bar

3

0

4

Transparent, blåfärgad film (ej hål).

18,6

98,1             

26,3

4,2

86,3

92,7

126,8

129,8

132,8

145,2

272,5

336

41

19,2

83

90.5

111

98,6

523

10,5

Ø 52,8

53,5

135,3

130,7

15

70,5

135,3

261,5

r=4,5

37

23

9

2 st Ø 4,5, transparent, ofärgad film (ej hål).

OBS! Endast halv cirkel (radie=11)

Slits på baksidan

De 8 grårastrerade ytorna (Ø22)
skall ej förses med häftämne.

49,5

84,4

85,7

186,3

196,8

42,5

67,5

57,25

52

 161

Ø 13

Ø 18,5

Ø 62

Hål 16 x 31

Hål 16 x 16

313,2

 2 st urstansninga , bredd=5 och r=2,5

Immersion 
heater

Compressor

Summary of Contents for FIGHTER 310P

Page 1: ...INSTALLATION AND MAINTENANCE INSTRUCTION FIGHTER 310P 230V MOS GB 0850 4 FIGHTER 310P 511350 L E K Fighter 310P Fighter 310P...

Page 2: ...LEK LEK 1 2 LEK LEK 3 4 5...

Page 3: ...ve offset 0 20 Heating curve offset 2 20 Setting using diagrams 20 Dealing with malfunctions Low temperature or a lack of hot water 21 Low or a lack of ventilation 21 Low room temperature 21 High room...

Page 4: ...40 285 21 MARKARYD SWEDEN Maxiumum water supply pressure 16 bar Immersion heater R50 8000W 230 V Operating pressure tap water 6 bar Expansion vessel tap water charge pressure 3 5 bar Expansion vessel...

Page 5: ...o that its temperature drops and the refrigerant changes state from gas to liquid The refrigerant then goes via filters to the expansion valve where the pressure and temperature are further reduced Th...

Page 6: ...4 Upper visible part of the front panel Display screen Art nr 611603 2 1 bar 3 0 4 2 1 bar 3 0 4 2 1 bar 3 0 4 41 83 90 5 111 98 6 523 70 5 135 3 261 5 Switch Pressure gauge Indicator lamps Extra hot...

Page 7: ...e Dealing with malfunctions Indications on the numerical display NOTE When switching from Standby mode to normal mode 1 the numerical display can remain dimmed for a brief period This can also occur a...

Page 8: ...r hidden part of the front panel Art nr 611603 2 1 bar 3 0 4 2 1 bar 3 0 4 2 1 bar 3 0 4 111 98 6 523 Indicator lamps Heating curve selection Operating mode Channel selection I H J G L Miniature circu...

Page 9: ...ions G Art nr 611822 Operating mode When the heat pump is started all functions immersion heater circulation pump and auto matic heating control system are running Pressing the Operating mode button o...

Page 10: ...adjustment of basic settings Cold weather conditions If the room temperature is low increase the heating curve selection setting by one step If the room temperature is high reduce the heating curve se...

Page 11: ...wners LEK The heat pump and its ventilation ducting require some regular maintenance when the following points should be checked The numbers in brackets refer to the section Compo nent locations Clean...

Page 12: ...ion vessel normally 0 5 bar and 2 5 bar 25 mvp See Commissioning and adjusting Pressure gauge Extract air temperature Checking the safety valves L E K 2 1 bar 3 0 4 2 1 bar 3 0 4 FIGHTER 310P has thre...

Page 13: ...between about 50 and 60 C The Extra hot water knob 18 on the front panel is used to increase the hot water capacity Temperatures in FIGHTER 310P NOTE Thetransport guard around the compressor mustberem...

Page 14: ...es in the boiler section The pressure vessel in the FIGHTER 310P is approved for max 9 0 bar 0 9 MPa in the water heater and 2 5 bar 0 25 MPa in the double shell section Overflow water from the evapor...

Page 15: ...o building regulation approval notify the Local Authority of intention to install Warning to the installer Use only manufacturer s recommended replacement parts Tap water connection Hot and cold water...

Page 16: ...xhaust air devices it may be a good idea to install a silencer in the duct This is especially important if there are exhaust air devices in bedrooms Because the heat pump contains a flammable refriger...

Page 17: ...front panel see under Service Open ing the front panel and moving certain cables as described under Electrical diagram Changing the output Connection Power rating as set at the factory Max current NO...

Page 18: ...in defrosting mode In addition the flow temperature is limited to maxi mum 60 C Art nr 611 1 2 3 4 5 6 1 2 3 4 5 6 1 1 2 3 4 5 6 1 2 3 4 5 6 Immersion heater operation connec tion on delivery Limited...

Page 19: ...V SKYDDSKLENSP NNING SELV B 1 2 3 4 5 6 7 8 B R R A B RUMSGIVARE RUNDSTYRNING UTEGIVARE B A Rundstyrning eller effektvakt 14 Rundstyrning RS och effektvakt EV Brytande kontaktfunktion RS EV EV RS SKYD...

Page 20: ...ter screw to A Set the dimensioned capacity 35 on the circula tion pump 16 See the section Pipe connections Pump and pressure drop diagram Make sure that the switch is not in an intermediate position...

Page 21: ...heating control system and Front panel The heating water can be drained off through drain valve 51 using an R15 1 2 hose coupling Remove the cover 80 from the valve Now screw on the hose coupling and...

Page 22: ...2 V RMEKURVA 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 30 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1514 13 12 11 10 8 7 6 5 4 3 2 1 40 C UTETEMPERATUR 10 0 10 5 5 30 40 50 60 7...

Page 23: ...witch 8 set to 0 MCB 7 tripped See the section Dealing with mal functions Resetting the miniature circuit break ers Tripped temperature limiter 6 Contact service Closed or throttled filler valve 46 on...

Page 24: ...the fault code must be cleared from the display by switch ing the heat pump off and on again Middle lamp lit Defrosting When there is too much ice on the evaporator defrost ing takes place After this...

Page 25: ...ault in the refrigerant circuit or its controller Request a service When the compressor is not operational the extract air temperature lies at about the same level as the room temperature High extract...

Page 26: ...ide temperature Actual value 04 Evaporation temperature Actual value 05 Extract air temperature Actual value 06 Curve slope Heating curve selection 07 Offset Heating curve offset 08 Temperature compre...

Page 27: ...ge 0 27 26 28 15 14 5 13 41 40 39 38 37 36 35 Re 1 Re 2 Re 3 Re 4 Re 5 Re 6 Re 7 29 230 V 12 V B1 C1 34 Brun Bl Svart VR1 C2 C3 F3 F1 F2 C4 L2 L1 5 2 1 3 4 P3 P1 P2 1 2 3 4 5 6 7 8 6 0 kW 1 Noll bleck...

Page 28: ...31 32 94 1 88 86 30 37 Fram ledning radiatorer 11 9 59 16 17 44 70 19 44 89 78 27 36 33 58 95 52 96 97 8 62 48 63 87 65 99 14 82 ter ledning radiatorer k v v v 41 103 51 80 71 50 66 151 149 74 73 84 9...

Page 29: ...atic heating control system and compressor 8 Switch positions 0 1 9 Terminal block power supply 10 Contactor step 1 11 Terminal block docking 13 Terminal block 14 Terminal block 15 Outdoor sensor 16 C...

Page 30: ...d in front of the heat pump for servicing Measuring principle Kl mring Klemmring Cu r r Kupferrohr A B och Undvik r rdragning inom streckmarkerat omr de f r att underl tta service Skyddsklensp nning 1...

Page 31: ...r Max pressure in double jacket volume 0 25 MPa 2 5 bar Breaking value high pressure pressostat 2 45 MPa 24 5 bar Breaking value low pressure pressostat 0 15 MPa 1 5 bar Design pressure in double jack...

Page 32: ...cabinet 385 535 mm Part no 089 428 ROOM SENSOR RG 10 In some cases a room sensor can be used as a sup plement to the ordinary automatic control system LEK 2 1 3 4 5 6 7 8 9 Accessories LEK Heightening...

Page 33: ...31 FIGHTER 310P...

Page 34: ...FIGHTER 310P 32...

Page 35: ......

Page 36: ...Tel 97 17 20 33 Fax 97 17 29 33 E mail info volundvt dk www volundvt dk NIBE Systemtechnik GmbH Am Reiherpfahl 3 29223 Celle Tel 05141 7546 0 Fax 05141 7546 99 E mail info nibe de www nibe de CH NIBE...

Reviews: