INSTALLATION AND MAINTENANCE INSTRUCTIONS

FIGHTER 1220

MOS GB 0429-1

011676

FIGHTER 1220

LE

K

Fighter 1220

R

Summary of Contents for FIGHTER 1220

Page 1: ...INSTALLATION AND MAINTENANCE INSTRUCTIONS FIGHTER 1220 MOS GB 0429 1 011676 FIGHTER 1220 LEK Fighter 1220 R...

Page 2: ......

Page 3: ...fset 2 21 Heating curve offset 0 21 Heating curve offset 2 21 Control General 22 Changing parameters 23 Key lock 23 Quick movement 23 Menu tree 24 Main menus 27 Hot water temperature 28 Supply tempera...

Page 4: ...d with all correspondence with NIBE 689_ _ _ _ _ _ _ _ _ _ FIGHTER 1220 _ _ kW Installation engineers Anti corrosion Enamel Stainless steel Copper The type of brine Mixing proportion freezing point Ac...

Page 5: ...sor The refrigerant the temperature of which has now been raised is passed to the condenser where it gives off its energy to the heating medium cir cuit and if necessary to the water heater After the...

Page 6: ...Indicates when immersion heater is con nected The line indicates which power step steps are currently connected I 2 kW additional power is connected II 4 kW additional power is connected I II 6 kW add...

Page 7: ...g this button The change does not need to be confirmed with the enter button A Means that the hot water temperature is increased to 60 C adjustable The temperature then returns to the normal value Whe...

Page 8: ...r first see the sec tion Room temperature Basic setting The basic heating is set using menu 2 1 and with the Offset heating curve knob If you do not know the correct settings use the basic data from t...

Page 9: ...concrete floor structure Markaryd Area 10 5 Select curve 5 on the dis play and 1 on the Increase reduce heat knob 3 House with floor heating installed in a timber floor structure Markaryd Area 10 5 Se...

Page 10: ...the tempera ture to about 70 C for 3 24 hours press the Extra hot water button once When the electrical module is connected for extra hot water the compressor stops The value is adjustable between 50...

Page 11: ...lly follows the operation of the heat pump There is a special operating mode for continuous operation for 10 days followed by return to normal mode this may be used before stable circu lation has been...

Page 12: ...mediate frost protected circuit must be provided because of the risk of dirt and freezing in the evaporator This requires an additional heat exchanger Pipe installation must be carried out in accordan...

Page 13: ...the connection of ambient cold possible To avoid condensation all pipes and other cold sur faces must be insulated with diffusion proof material Where the cooling demand is high fan convectors with dr...

Page 14: ...kPa 250 500 750 0 l h 1000 2 4 8 20 80 40 Tryckfall Fl de 1250 1500 1750 60 6 2500 2250 2000 FIGHTER 1215 7 FIGHTER 1215 10 0 0 mvp kPa 250 500 750 0 l h 1000 2 4 8 20 80 40 Tryckfall Fl de 1250 1500...

Page 15: ...perature limiter thermostat compressor or the immersion heater can be damaged The automatic heating control system circulation pumps and their wiring are internally fuse protected with a miniature cir...

Page 16: ...e contactor Remove the 2 orange straps on terminal block 9 and connect the control voltage to the outermost terminals marked L and N on the wiring diagram LEK PE L2 L3 N L1 PE L1 L2 L3 PE L2 L3 N L L1...

Page 17: ...mmersion heater out kW Knob position Max phase A 5 kW Max phase A 7 kW Max phase A 8 5 kW Max phase A 10 kW 6 4 C 14 3 16 2 17 4 18 6 9 3 B 9 9 11 8 13 0 14 2 9 9 D 18 6 20 5 21 7 22 9 Max hot water t...

Page 18: ...one of the phases the immersion heater will step down the output until it can be connected again The control system must be set for the installation s main fuse so that the load monitor can work corr...

Page 19: ...onitor is required for the collector installation this can be connected to positions 16 17 on terminal block 14 In order for this to be active you must change menu 9 2 11 brine pressostat to On The co...

Page 20: ...ure limiter TB has tripped Indicated as a TB alarm The motor cut out MS has tripped indicated by an MS alarm Pressure level monitor brine accessory indicated as pressure level brine Brine temp low ind...

Page 21: ...menu 9 2 12 The heat pump cannot start because EP electric boil er mode only is selected The brine pump is now operational together with the filling pump The fluid can circulate via the mixing vessel...

Page 22: ...ine pump 10 days from menu 9 2 12 to run the brine pump continuously for 10 days After 10 days the brine pump automatically returns to normal operation Ensure the brine and heating medium pumps are ve...

Page 23: ...b is then set A suitable value for floor heating is 1 and for radiator systems 2 Offset heating curve 2 Setting using diagrams 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 30...

Page 24: ...ting mode button followed by enter quick movement to return to menu 1 0 Information is presented on the display about the status of the heat pump and the electric boiler Menu 1 0 is nor mally shown on...

Page 25: ...1 2 Time period 1 3 MAX time HW period 1 4 HW temp Starttemp HW 1 5 HW temp Stoptemp HW 1 6 Stop Temp XHW 1 7 Stop compressor XHW 1 8 Interval XHW 1 9 Next XHW action 1 10 HW running time 1 11 0 Pool...

Page 26: ...1 11 1 Pooltemperatur inst 1 11 2 Diff pool min temp 1 11 3 Poolperiod 1 11 4 Poolpause 1 11 5 Sensor typ 1 11 6 Return to 1 11 0 Hotwatertemperature 1 0 4 1 Outdoor avg temp 4 2 Return to 4 0 Outdoor...

Page 27: ...3 3 7 3 9 Set time Monday Sunday 7 3 10 Return to 7 3 0 8 1 1 Operation mode types 8 1 2 Language 8 1 3 Contrast 8 1 4 Light intensity 8 1 5 Return to 8 1 0 8 2 1 Summer mode temp 8 2 2 Winter mode t...

Page 28: ...tep 9 1 3 Add heat run time 9 1 4 Return to 9 1 0 Service menues 9 0 9 2 1 Max HW temp 9 2 2 Flow diff HP 9 2 3 Diff HP Add 9 2 4 Electric boiler 9 2 5 System 2 Present 9 2 6 Room disp Present 9 2 7 C...

Page 29: ...bmenus to this menu Menu 9 0 Service menues This menu and its submenus are only shown on the display screen when access has been selected in menu 8 1 1 Values can be read and various settings can be m...

Page 30: ...u 1 10 HW running time How long hot water heating has been in progress is shown here accumulated 2 0 6 0 m i n P e r i o d t i m e H W T o t a l 1 1 1 4 d ay s I n t e r v a l X H W 1 8 9 0 h 1 0 m i...

Page 31: ...emperature to the heating system is shown here The value is adjustable between 10 and 65 C The calculated flow temperature never exceeds the set level irrespective of the outdoor temperature curve slo...

Page 32: ...of 20 is chosen here The value is adjustable between 0 and 60 Menu 2 6 3 Set temperature Here you select at what outside temperature the break point shall occur The value is adjustable between 0 and...

Page 33: ...ts is set here The val ue is adjustable between 10 and 60 2 0 m i n T i m e b e t w e e n s t a r t s 5 3 N N Menu 5 4 Compr starts at How low the degree minutes may drop before the a compressor start...

Page 34: ...C o m p r e s s o r t y p e 5 1 4 U Menu 5 21 Return Pressing the enter button returns you to menu 5 0 R e t u r n 5 2 1 Menu 7 1 Date The current date is set Menu 7 3 0 Day change period 1 Settings e...

Page 35: ...e time for the day change e g night reduction is chosen here S e t T i m e M o n d a y 7 4 3 U U Menu 7 5 0 Timer XHW Settings are made in the submenus of this menu when extra hot water is required on...

Page 36: ...nd menu type are set on the submenus to this menu D i s p l a y s e t t i n g s 8 1 0 Menu 8 1 1 Operation mode types The menu type is chosen here Normal extended or service Normal covers the normal u...

Page 37: ...ting selected on the load monitor card 2 is shown here knob 100 1 6 A F u s e s i z e 8 3 4 Menu 8 3 1 Current phase 1 Shows the measured current from phase 1 3 5 A C u r r e n t p h a s e 1 8 3 1 Men...

Page 38: ...actory settings can be made on the sub menus in this menu O p e r a t i n g m o d e s e t 9 2 0 Menu 9 2 1 Max HW temp Here the maximum boiler temperature is shown The value is selected on the load mo...

Page 39: ...y i n g s e t 9 2 9 0 S Menu 9 2 9 1 Floor drying The floor drying program is chosen from this sub menu The options are Prog 1 On Prog 2 On or Off The heat pump must be in Winter mode selected with t...

Page 40: ...f B r i n e p r e s s o s t a t 9 2 1 1 S Menu 9 2 12 Brinepump 10 days The brine pump can be active for 10 days when the installation is started The basic setting is Off O f f B r i n e p u m p 1 0...

Page 41: ...Q u i c k s t a r t 9 3 S TEST Forced driven operation Menu 9 4 0 TEST Forced operat Test of outputs automatic return after 8 hours Only for service personnel T E S T F o r c e d o p e r a t 9 4 0 S M...

Page 42: ...he compressor is blocked and FIGHTER 1220 switches to electric boiler mode No hot water is produced This may be due to No or low flow on the brine pump 16 Closed thermostat valves A L A R M H P 1 1 0...

Page 43: ...T W A T E R S E N S O R 1 0 A L A R M F L O W 1 0 Alarm Flow High flow temperature 1 High flow temperature 2 extra shunt group accessory High return temperature The following alarm stops the compress...

Page 44: ...trips repeatedly call an electrician Cause Compressor and electric module do not heat Action Check and replace blown circuit and main fuses Cause The compressor does not run because of a too low set...

Page 45: ...e bent down and emptied in a small bowl Now loosen the connection on Brine in a little to allow air to enter so the heat pump s collector side is emptied completely When the circuit is empty the requi...

Page 46: ...for servic ing An area of 800 mm is required in front of FIGHTER 1215d for service work When FLM 30 is fitted on FIGHTER 1215 the distance to the wall should be 50 mm 598 179 525 525 30 399 454 144 32...

Page 47: ...e 65 Drying filter 67 Contactor electric module step 2 69 Contactor compressor operation 70 Connection heating flow 22 mm o d 71 Connection heating return 22 mm o d 72 Hot water circulation VVC Enamel...

Page 48: ...I I II I II 5 0 0 C Va r m v a t t e n t e m p 1 0 8 88 75 116 115 1 Component placement 46 FIGHTER 1220 For the Installer LEK 41 18 65 17 112 111 110 27 7 42 48 28 33 LEK 16 76 87 24 35 96 19 4 86 94...

Page 49: ...Component placement 47 For the Installer FIGHTER 1220 LEK 9 3 39 26 25 6 69 67 10 LEK 1 32 29 LEK 73 70 99 71 58 75 95 72 74 LEK 2 34 97 100 101 102 14...

Page 50: ...Wiring diagram 3 x 400 V N FIGHTER 1220 For the Installer 48 Sheet 1 4 Compressor Immersion heater Supplied connectied 6 kW Relay board...

Page 51: ...Wiring diagram 3 x 400 V N 49 For the Installer FIGHTER 1220 Sheet 2 4 Compressor Soft starter Heating medium pump 3 way valve Relay card...

Page 52: ...Wiring diagram 3 x 400 V N FIGHTER 1220 For the Installer 50 Sheet 3 4 Brine pump Relay board...

Page 53: ...temp Current phase 3 Current phase 2 Current phase 1 Not function Tariff B Tariff A EBV card Temp set back 1 Outdoor sensor Extra hot water Hot water Heating water return 1 Heating water flow 1 Hot ga...

Page 54: ...edium flow l s 0 13 0 18 0 22 0 26 Max temp supply return C 60 50 IP 21 Volume water heater litres 160 Starting current A 24 24 24 26 Fuse incl imm heater 6 kW A 16 16 20 20 Output brine pump W 130 17...

Page 55: ...40 Two 4 5 LEK LEK LEK NIBE AB Utete mp era tur giv are Ou tdo or tem perature sensor Aussentem peratur f h ler Artikel 018764 Level vessel with safety valve Part no 85 024413 52 424091 15 85 Particle...

Page 56: ...PAC Part no 089 265 Level monitor NV 10 Part no 089 315 L E K L E K 1 0 15 20 25 30 C Room thermostat RT 10 Part no 418 366 Extra shunt group Used when there is a need of two different supply tem pera...

Page 57: ...55 For the Installer FIGHTER 1220...

Page 58: ...FIGHTER 1220 For the Installer 56...

Page 59: ......

Page 60: ...aajat NIBE AB n sivuliike Pohjant hdentie 17 01451 Vantaa Puh 09 274 697 0 Fax 09 274 697 40 E mail info haato com www haato fi NIBE Systemtechnik GmbH Am Reiherpfahl 3 29223 Celle Tel 05141 7546 0 Fa...