- 32 -
Code
Type
Description
Min
Max
Setting
Units
F08
Parameters
(continuation)
H02 TCC
–
Gradient de P02 TCC
2
20
15
°C
P03
–
Setpoint start defrost cycle
-15
10
-8
°C
P04
–
Temperature finish defrost cycle
-10
20
10
°C
P05
–
Safety temperature
70
80
75
°C
P06
–
Setpoint disinfect
60
70
65
°C
P07
–
Temp. min Evaporator to activate electrical
heater (AUTO mode)
-20
20
-5
ON
°C
P08
- Temp. min water to activate electrical heater
(AUTO mode)
10
40
30
ON
°C
P09
–
Air temperature to allow defrost cycle
-5
15
5
°C
P10
–
Setpoint to activate the LAT protection mode
(Low ambient temperature)
-10
10
-2
°C
H10
–
Gradient P10
2
20
7
°C
P11
–
Gradient to activate the Solar Thermal Pump
2
10
5
°C
P12
–
Additional Functions
0
4
0 - inactive
---
P13
–
Minimum water temperature to activate the
recirculation pump
20
50
30
°C
T01
(timer)
–
Delay time to compressor starts running
1
20
2
min
T02
–
Not used
-
-
-
-
T03
(timer)
–
Maximum defrost cycle time
1
10
5
min
T04
–
Not used
-
-
-
-
T05
(timer)
–
Maximum time compressor running
6
15
12
hours
T06
(timer)
–
Delay for defrost cycle
30
360
60
s
T07
(timer)
–
Delay time to compressor starts running
after LP error
1
20
10
min
T08
(timer)
–
Time between defrost cycle
10
120
30
min
T09
(timer)
–
Delay for LAT mode starts
2
20
5
min
T10
(timer)
–
Minimum time for defrost cycle
1
10
2
min
T11
(timer)
–
Delay time LP alarm
1
10
1
min
T12
(timer)
–
Delay time water flow alarm
5
120
10
sec
T13
(timer)
–
Delay time to restart the solar thermal
pump
1
10
5
min