- 34 -
ERRORS
The installation, assembly and repair of the equipment can only be carried out by qualified technicians.
Symbol
Description
Problem / Checking
Er01
–
S1
Probe 1 OFF.
•
Lack of temperature probe. Check for probe.
•
Probe disconnected from controller
–
Check that the connector is well
attached to the electronic plate and/or the connection terminals are
secure
Er02
–
S2
Probe 2 OFF.
Er03
–
S3
Probe 3 OFF.
Er04
–
S4
Probe 4 OFF.
Er11
–
S1
Probe 1 short circuit
•
Damaged probe
–
Measure internal resistance of probe which
is
approximately 10 KΩ at the temperature of
25
°
C
Er12
–
S2
Probe 2 short circuit
Er13
–
S3
Probe 3 short circuit
Er14
–
S4
Probe 4 short circuit
Er20
–
TA
Anomaly detected in
the water temperature
•
Water temperature in storage water heater is too hot
–
Check that there
is no anomaly in the electronic board, such as a damaged relay.
•
Temperature probes in short-circuit
–
Measure internal resistance of
probe, it should be approximately 10 KΩ at the tempe
rature of 2
5 °
C,
check that the connector is well attached to the electronic plate and the
connection terminals are in good condition.
Er21
–
DF
Anomaly detected in
the defrost cycle (Too
many defrost cycles in a
short period of time)
•
Measure internal resistance of probe, it should be approximately 10 KΩ
at the temperature of 2
5 °
C, check that the connector is well attached
to the electronic plate and the connection terminals are in good
condition.
•
Low external temperatures
•
Lack of refrigerant
•
Leak on the fluid circuit
Er22
–
LT
Water low temperature
alarm
•
Water temperature in the boiler lower than
0 °
C.
Er23
–
LP
Protection
system
active
•
Low Pressure switch
–
Verify if the switch is well connected in the
command panel.
•
Low external temperatures
•
Lack of refrigerant
–
Incomplete refrigerant charge or leak
Er24
–
HP
Protection
system
active
•
High pressure switch
–
Verify if the switch is well connected in the
command panel.
•
Fluid circuit obstructed (expansion valve or filter).
Er25
–
FS
Protection
system
active
•
Lack of water / water circuit obstructed in the solar thermal installation
LINK
ERROR
Communication failure
between display and
power board
•
Connection cable between display and command panel
–
Check the
cable is in good condition or that the plugs are correctly inserted (display
and command panel)