Nibe Contura Ci50 Installation Instructions Manual Download Page 15

!

GB

95

Service

Make sure it is possible to access the damper control and 
counterweight through hatches or ventilation grilles in the surround. 

RECESSING THE INSERT

Convection air

Sealing

The recess must not go all the way up to the ceiling, leave an air 
gap of at least 20 mm closest to the ceiling. The recess must be 
sealed off above the convection exhaust. The seal must be 100 
mm above the convection exhaust’s upper edge and must be made 

of 100 mm non-flammable material according to the material 
requirements above. Use heat-resistant silicone, for example, 
between the seal and chimney.  

The building material must not be combustible.
The thermal conductivity coefficient 

λ

 must be a maximum of 

0.14 W/mK.
The thickness of the building material must always be at least 
100 mm.
In cases where the building material’s insulation properties 
are given as a U-Value, this must be a maximum of 1.4 W/ m²K.

Material requirements

The convection air ventilates the surround, cools the insert and 
transports the hot air out into the room. The effective cross 
section area on the air intake and exhaust must not be less than 
the stated values. The air intake must be positioned somewhere 
between floor level and the bottom of the insert, at the front or 
on the sides of the recess. The vent must be positioned above the 
insert’s highest point at the front or to the sides of the recess.

If the air intake respectively the vent is positioned on the sides, 
the areas for the left respectively right sides must be the same 
size to ensure that the insert is evenly cooled.
The distance from the exhausts on the sides to the combustible 
wall behind must be 100 mm. 
Observe the minimum distance up to the ceiling (see diagram on 
page 97).

Convection air in: 600 cm²
Convection air out: 600 cm²

If the convection outlets are directed upwards the following 
applies 
- the recess must be free-standing or placed against a 
non-combustible wall. 
- the distance from the air outlet to combustible roof must be at 
least 750 mm.

When recessing the insert, adjacent walls that are not classed 
as fire walls or are considered unsuitable for heat loads must 
be protected by non-combustible material according to the 
specification below.
All joints on the non-combustible material must be sealed using 
the manufacture’s recommended method. The area between 
the insert and the recess must be ventilated according to the 
specification/dimension diagrams on page 97.

When connecting a steel flue, please refer to the particular 
manufacturer's installation instructions. Observe the safety 
distance to combustible material required by the steel flue Heat 
radiation from the door is strong and because of this combustible 
material must not be placed closer than 1.5 m in front of the door. 
When recessing, building material must not be in direct contact 
with the insert due to the thermal expansion of the insert.
Note that building regulations apply regarding the area below and 
in front of the insert, see section ”Hearth plate”.

Recessing the insert

List of suitable materials:
Aerated concrete  

λ 

=0.12-0.14

Vermiculite  

λ 

=0.12-0.14

Calcium silicate  

λ 

= 0.09

Summary of Contents for Contura Ci50

Page 1: ...Ci50 contura eu Installation instructions...

Page 2: ...classification A1 Minimum distance to flammable materials Rear 150 mm With heat shield Side 700 mm Ceiling 550 mm Front grate Ceiling 750 mm Top grate Front 1500 mm Floor 0 mm Corner NPD Fire hazard d...

Page 3: ...qualified inspector Your local chimney sweep must also be informed of the installation as this will affect the routines for regular chimney sweeping services A warm welcome to Contura Welcome to the...

Page 4: ...how to install the Contura i50 We recommend the insert be installed by a qualified tradesperson to ensure it functions safely and properly Our Contura dealers can recommend suitable installers Dealer...

Page 5: ...10 390 1600 1125 670 230 505 925 480 500 270 GB 85 Opening a side glass panel Prior to installation IMPORTANT DIMENSIONS PRIOR TO INSTALLATION Important dimensions The insert can be lowered 80 mm at 1...

Page 6: ...x3 GB 86 PRIOR TO INSTALLATION...

Page 7: ...10 mm GB 87 PRIOR TO INSTALLATION...

Page 8: ...Check the performance of the insert as follows Use the adjustable feet to level the insert Check that the door can be opened and closed Check that the damper knob can be moved back and forth to the m...

Page 9: ...when burning wood logs and operated in accordance with these instructions and when fitted with a permanent stop to prevent closure of primary air control beyond the 52 mm open position secondary air c...

Page 10: ...1 2 GB 90 PRIOR TO INSTALLATION Installation of metal ba e plate...

Page 11: ...1 2 3 4 5 6 7 8 GB 91 PRIOR TO INSTALLATION Removing the hearth cladding...

Page 12: ...GB 92 Option Installing Powerstone OPTION...

Page 13: ...below The connection sleeve on the stove has an external diameter of 100 mm In warm spaces the duct should be insulated to prevent condensation using 30 mm mineral wool covered with a vapour barrier...

Page 14: ...east 12 Pa The draft is affected primarily by the length and area of the chimney and also by how well sealed it is The minimum recommended chimney length is 3 5 m and a suitable cross section area is...

Page 15: ...s for the left respectively right sides must be the same size to ensure that the insert is evenly cooled The distance from the exhausts on the sides to the combustible wall behind must be 100 mm Obser...

Page 16: ...on body before the stove is used You should also read the Lighting instructions before lighting the stove for the first time RECESSING THE INSERT The distance between the exhausts on the sides and a c...

Page 17: ...a in 600 cm2 Area in 600 cm2 Area in 600 cm2 Area in 600 cm2 Max 100 Max 100 Max 100 Area out 600 cm2 Area out 600 cm2 Area out 600 cm2 Area out 600 cm2 Sealing Can be excluded if the chimney breast b...

Page 18: ......

Page 19: ......

Page 20: ...0 1 2021 09 14 NIBE AB Box 134 285 23 Markaryd Sweden contura eu Contura reserves the right to change dimensions and procedures specified in these instructions without prior notice Access the latest v...